Contactors C137/C163/C164/C165 – Installation and Maintenance Instructions
Installation
A 2.8 x 0.5 mm
2
1
Fig. 22: C137 Series: Connect the auxiliary contact (SPDT)
A 6.3 x 0.8 mm
2
1
Fig. 23: C163, C164, C165 Series: Connect the auxiliary con-
tact (S840)
(the figure shows C164, the procedure for C163 and
C165 is the same)
Connect the coil terminals
The control wires for the coil connection must be fitted
with flat receptacles for tabs (A 6.3 x 0.8 mm).
NOTICE
X
Bending of the coil terminals is not permissible!
X
Move and lay the control wires and flat recepta-
cles for tabs only in plugging direction, see
Fig. 24
und
Fig. 25
.
X
Attach the control wires mechanically, in order
to minimize retroactivities (e. g. shock, vibra-
tions) from the wires to the terminals.
X
Plug the prepared control wires with the flat re-
ceptacles (3) to both coil terminals A1 and A2 (4).
A 6.3 x 0.8 mm
3
4
Fig. 24: C137 Series: Connect the coil terminals
A 6.3 x 0.8 mm
3
4
Fig. 25: C163, C164, C165 Series: Connect the coil terminals
(the figure shows C164, the procedure for C163 and
C165 is the same)