VLV55|VLV65 - Volumetric flow controller

 

 

 

TECHNICAL DOCUMENTATION

 

 

Prior to assembly and commissioning |   Legend

  

 

 

 

Construction subject to change 

 

No return possible 

Version: 2017-04-24 | Page  29 

PRIOR TO ASSEMBLY AND COMMISSIONING 

 
An instruction leaflet containing  
information on safety, transport dis-
posal, installation  
commissioning and maintenance is 
enclosed with each SCHAKO prod-
uct. 
For safety reasons, this instruction 
leaflet must  

                                                                             e read under all circumstances and  

                                                                            completely adhered to. 

 
These devices are NOT suitable for use in zones where there is 
a risk of explosion according to ATEX 94/9/EC. The operating 
safety of the devices is only guaranteed when used in accord-
ance with their designated use. 
 

Disposal 

The devices have been prepared in accordance with the RoHS 
directive restricting the use of certain hazardous substances in 
electrical and electronic equipment (2002/95/EC). After its final 
decommissioning, the volumetric flow controller must be 
properly disposed of. 

 
 

INSTALLATION INFORMATION 

 

Installation and commissioning 

 

Installation with horizontal or vertical damper axle possible 

 

position-independent 

 

direct connection to moulded parts, such as bend or T-piece 
possible 

 
 

MAINTENANCE AND SERVICE 

 

Service and maintenance instructions 

 

Assemble in a way to allow inspection 

 

maintenance-free, as there is no wear 

 

not suitable for air containing sticky and oily particles 

 

For maintenance, service, retrofitting, etc., inspection open-
ings in sufficient number and size must be provided on site. 

 

LEGEND 

D

e

 [dB/Okt] = 

Insertion 

loss 

EK (m/s) 

Calibration 

curve 

f

m

 

(Hz) 

=  Octave band centre frequency 

V

min

 

(m³/h) [l/s]  =   Minimum volumetric flow 

V

max

 

(m³/h) [l/s]  =   Maximum volumetric flow 

Hz 

(fm)  

=   Hertz 

K

L

 

(-)  

=   Correction value; relative  

sound power level, relative to L

WA

 

K

Lw 

(-)

 

=

  

Relative sound spectrum 

LOA 

(-)  

=   Number of holes in flat flange 

(mm) 

=   Packing thickness duct silencer 

NW (mm) 

Nominal 

width 

U

5

 

(V) DC 

=  Measurement output (electric voltage) 

V (m

3

/h) [l/s]  =  Air volume 

[%] 

=  Tolerance for the volumetric flow setpoint 

value 

v

K

 (m/s)  = 

Duct 

velocity 

øD (-) 

Hydraulic 

diameter 

p (Pa) 

Pressure 

difference 

p

t min

  (Pa) 

=  Minimum static pressure difference 

p

t

 (Pa) 

Pressure 

loss 

 
 
 
 

 

 

Summary of Contents for VLV55

Page 1: ...ES after moulded parts no inflow area required optimised for air velocities from 0 5 m s high control accuracy at low pressures and air veloci ties position independent installation resistant to pollu...

Page 2: ...55 radiated noise relative sound spectrum 11 VLV65 flow generated noise 12 VLV65 flow generated noise relative sound spectrum 13 VLV65 Radiated noise 14 VLV65 Radiated noise relative sound spectrum 15...

Page 3: ...stems also at low duct pressures and air velocities When suitable controller types are used room or duct pressure regulation can be achieved For the measurement of the effective pressure SCHAKO is us...

Page 4: ...n connecting SCHAKO components to customer installa tions any compatibility problems are beyond our scope of re sponsibility and must be solved on site Tests and standards The volumetric flow controll...

Page 5: ...flow controller is no longer guaranteed If only Vmax is specified in the order a variable volumetric flow controller will be delivered The Vmin value will be set to the value specified in the catalog...

Page 6: ...l mineral wool filling DIMENSIONS OF ACCESSORIES METU flange MF1 Tension ring provided by the customer VLV Metu flange MF1 Counter flange provided by the customer Flat flange FF1 on both sides to DIN...

Page 7: ...96 100 5 200 0 5 55 15 5 15 2 218 61 20 10 4 436 121 60 7 5 546 152 100 5 250 0 5 86 24 5 15 2 344 96 20 10 4 687 191 60 7 5 859 239 90 5 315 0 5 137 38 5 15 2 549 153 20 10 4 1097 305 65 7 5 1372 38...

Page 8: ...4 59 62 64 5 132 37 56 61 65 67 125 0 5 21 6 35 38 43 45 48 2 84 23 49 54 58 59 61 4 167 46 47 58 63 65 67 5 209 57 56 63 67 69 160 0 5 35 10 38 45 46 50 51 2 139 38 51 57 60 62 63 4 277 77 50 60 64 6...

Page 9: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 6 5 1 0 7 11 18 26 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Page 10: ...0 5 13 4 2 53 15 25 28 30 4 105 29 27 30 33 34 5 132 37 32 34 36 38 125 0 5 21 6 2 84 23 25 29 30 4 167 46 25 28 32 33 36 5 209 57 33 35 38 42 160 0 5 35 10 25 2 139 38 28 31 33 36 4 277 77 34 37 39 4...

Page 11: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 3 4 8 6 7 6 7 9 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Page 12: ...57 62 65 66 8 210 58 62 66 69 125 1 42 12 41 45 49 51 53 3 125 35 50 58 61 63 64 5 210 60 47 59 63 67 70 8 334 93 65 69 71 160 1 69 19 45 49 53 54 57 3 208 58 50 58 63 65 67 5 345 95 51 59 64 67 69 8...

Page 13: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 5 3 0 1 6 11 18 27 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Page 14: ...6 7 3 79 22 26 28 30 5 130 35 25 30 32 35 8 210 58 35 39 40 125 1 42 12 3 125 35 26 29 30 5 210 60 30 33 34 36 8 334 93 38 40 41 42 160 1 69 19 25 28 31 3 208 58 33 36 38 40 5 345 95 39 41 43 45 8 554...

Page 15: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 0 2 6 4 7 7 7 11 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Page 16: ...50 50 34 21 7 19 28 40 50 50 50 32 125 4 11 21 33 50 50 32 19 6 17 25 34 49 50 36 22 160 3 8 15 23 34 9 18 14 5 12 18 28 41 48 26 16 200 2 5 11 18 30 24 14 11 4 10 15 24 35 41 22 13 250 2 4 9 15 27 1...

Page 17: ...tching contact If the Compact controllers of the Belimo make must be deliv ered with the operating mode 0 10V DC on customer request please note that a positive control CLOSED can only be ef fected vi...

Page 18: ...ied out with a 0 10 V signal Attention Controller DDC must be able to pull the command signal to 0 V Cable designations Com mand sig nal Y Volumetric flow Function 0 1 V 0 Damper CLOSED VAV control in...

Page 19: ...0 10 V 0 10 V 2 10 V 2 10 V 2 10 V 2 10 V 2 10 V Signal 0 10 V 2 10 V Function 3 3 3 3 3 Damper CLOSED a CLOSED c CLOSED Vmin Vmax b VAV CAV Vmin everything open Vmin active Damper OPEN e OPEN CAV Vma...

Page 20: ...are pressed again after 2 hours have passed LED 1 LED 2 Lack of air Damper opens as actual volume is too low LED 1 LED 2 Target volume reached Control circuit balanced LED 1 LED 2 Air excess Damper cl...

Page 21: ...et the required actual volumetric flow unit in m3 h and l s Vmin To set the required min volumetric flow setpoint value Y 0V 2V Vmax To set the required max volumetric flow setpoint value Y 10V Mode t...

Page 22: ...nn or Vmax volumetric flow depending on con troller type Information regarding the set value Vmin in the following controllers Vmin refers to Vnenn Product Type Belimo LMV D3 MP LMV D3 MF Gruner 227VM...

Page 23: ...ignal 0 10 V DC Example Assume Measurement output signal U5 6 3 V DC see calibration value VRA E 12 m sec Measured va lue Duct velocity 7 6 m s Air volume Duct velocity x area m x 3600 m h U5 signal 2...

Page 24: ...s III safety extra low voltage Protection type IP 54 hose connected EMC CE according to 39 336 EEC Measuring air and ambient tempera tures 0 C 50 C 5 95 rH non condensing Storage temperature 20 C 80 C...

Page 25: ...0 100 of Vnom Vkonst 0 100 of Vnom Command variable Y Z inherent resistance min 100 k DC 0 10 V 0 20 mA min 500 inherent resistance DC 2 10 V 4 20 mA min 500 inherent resistance Setting range actual...

Page 26: ...internally by means of DC DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be down...

Page 27: ...ctional test of MP bus backward compatible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position i...

Page 28: ...le in a switch cabinet Structure and operation The relevant parameters can be set and queried in the individ ual menu items while the operating parameters programmed in factory can be queried under me...

Page 29: ...properly disposed of INSTALLATION INFORMATION Installation and commissioning Installation with horizontal or vertical damper axle possible position independent direct connection to moulded parts such...

Page 30: ...227VM 024 05 setting values 150 600 m h with METU flange ORDER DETAILS 01 Type VLV55 version with diameter ratio 55 0 5 5 m s VLV65 version with diameter ratio 65 1 8 m s STANDARD 02 Size 100 NW 100...

Page 31: ...seal made of EPDM silicone and halogen free Ring chamber sealing made of EPDM silicone and halogen free Venturi nozzle made of aluminium with attached measuring points for determining average values...

Reviews: