background image

4

mm/s, rms*, is not allowed in case of 
position on feet or anti-vibration 
mountings.
* ISO 2954, Requirements for instruments 
for measuring vibration severity.

After thirty minutes of operation check that 
the fan operates normally.

6. Maintenance

6.1 Prior to maintenance

When the fan is out of operation for reasons 
of inspection or repair/maintenance, the 
electric system must be switched off and 
protected so that the fan is not cut in 
unintentionally.

6.2 Fan casing

The fan casing requires as standard no 
maintenance other than ordinary cleaning.

If the fan casing is painted, the painted 
surface should be checked regularly and 
repaired where necessary.

6.3 Impeller

The impeller (rotor unit) is supplied from 
the factory with the blades adjusted to the 
pitch corresponding to the desired 
operating point (pressure and airflow) at 
the fan speed in question. To ensure 
vibration-free operation the impeller has 
been carefully balanced in this position.

Vibrations occurring during operation will 
normally be due to accumulations of dust 
or dirt on hub and blades, and will 
disappear after cleaning. Should this not be 
the case, expert assistance should be called 
in immediately, as continued vibrations 
will shorten the life of the blades and the 
motor bearings.

6.4 Motor

The motor normally only requires 
maintenance of the bearings as indicated in 
the maintenance instructions for electric 

motors.

6.5 Dismounting of motor

Prior to commencing the work, switch off 
the current and disconnect the motor cable. 
Next, dismount any ducts and 
downstream guide vane arrangement (fig. 
7, items 13, 10, 11, and 14) on the fan outlet 
side.

Remove the impeller centre screw (item 09) 
and centre disc (item 08).

Dismount the impeller by means of a puller 
fastened in the two threaded holes of the 
hub boss (item 12).

Detach the motor by loosening the screws 
in the motor shell (items 05 and 06). Now 
the motor (item 01) and motor flange (item 
02) can be removed.

In dismounting and disassembling the fan 
be careful not to expose the individual 
parts to shocks etc. likely to damage the 
motor bearings or other fan components.

6.6 Mounting of motor

After servicing remount the motor, check 
that the motor flange (fig. 7, item 02) is 
correctly located and that the motor shaft is 
concentrically placed in the fan casing, 
before tightening the bolts (item 06).

Mount the impeller (item 07) on the motor 
shaft by means of a tool fastened in the 
threaded hole of the motor shaft. Fix the 
impeller hub to rest against the motor shaft 
collar.

Check that the mean blade clearance is 
within the minimum allowable value. See 
section “ 4.1 Prior to installation” for values 
and calculation of mean blade clearance.

Now mount the centre screw (item 09) and 
centre disc (item 08). Replace lock washers 
and lock nuts during fan assembly. Finally, 
connect the motor cable in the terminal box 
(item 01) and any ducts and downstream 
guide vane arrangement (item 13). 

To start the fan follow the procedure 
described in section “ 5. Start of operation”.

6.7 Blade pitch adjustment

The blade pitch has been adjusted in the 
factory with a special tool (fixture) to 
deliver the performance required by the 
customer/order on delivery.

If the fan performance is required to be 
changed it is possible to change the blade 
pitch. It requires knowledge of the motor 
load and the max. permissible blade pitch 
on the graph as related to the motor rating 

(in case of blade pitch increase).

Contact Novenco before any such 
adjustment of the blade pitch.

Novenco can supply special tools for blade 
pitch adjustment and instructions for 
impeller balancing.

The brochure "Blade-angle tool" is 
available on request.

6.8 Troubleshooting

These are likely causes of breakdowns/
failures.

Deficiency in performance

Blocked air supply to the fan inlet side
–  Damper closed
–  Duct choked
–  Supply fan, if any, stopped
–   Motor  defective
–  Motor cut out
–  Wrong direction of rotation of impeller.

Noise/vibrations

–  Bearings in electric motor defective
–  Impeller out of balance
–  Impeller worn/damaged
–  Bolts/components loose
–  Impeller blades have different pitch 

angles

–  Fan operates in the stalling area. May 

result in break-down - repair failures, 
see "Deficiency in performance".

7. Sound

The sound generation of the fans 
depends on installation and operating 
conditions, which means that no general 
data of the sound generation can be 
given.

Reference is made to our catalogues or 
computer programs for calculation of the 
specific sound generation.

Important:

The fan is designed for 
continuous operation. The 
following kinds of 
operation may cause fatigue 
break in the impeller and 
endanger people.
- Operation in stall area
- Operation with pulsating 
counter pressure - called 
pump mode
- Operation with repeated 
starting and stopping
If in doubt Novenco should 
be contacted to assess the 
suitability of the fan.

Reviews: