Novenco

®

  jet fan types AUO/ARO - ARP/AUZ - AUT/ART - AZT

3

It is essential for the 
performances and sound levels 
that the airflows are unimpeded 

and free from eddies.

2.

Drill holes in the ceiling in 
accordance to the mounting 
specifications. See figure 3 and table 
5.

If unapproved expansion bolts 
for high temperature are to be 
used, these must be made from 

steel, must at least be size M8 and must 
be mounted twice as deep as 

recommended – at least 60

mm deep. 

The static load must not exceed a pull of 
more than 500 N.

3. Optional:

 Install lowering brackets 

in the ceiling, if applicable.

4.

Place the fan on a platform that can 
be raised, for example a scissor lift.

5. AUO/ARO-ARP/AUZ-AUT/ART: 

Fasten the fan in the suspension 
points to the ceiling or, if applicable, 
to the lowering brackets.

Notice:

It is recommended to install 
vibration dampers. These 
are optional and not 
included as standard.

6. AZT:

 Mount the base plate to the 

ceiling or. if applicable, to the 
lowering brackets and install the 
vibration dampers.

Expansion bolts certified for fire 
conditions must be used and 
loaded according to the 

approval.

Lift the fan in place with attention to 

the correct insertion of the bolts, 
which must enter and slide back in 
the base plate slits.

7.

Check that the rotor rotate freely in 
the fan casing.

8. AUO/ARO-ARP/AUZ:

 Remove the 

transport brackets on the underside 
of the fan casing. Reinsert the screws 
from the brackets in the casing.

AZT:

 Reinsert the screws from the 

transport brackets in the casing.

4.3 Electric connection

The installation and connection 
to the supply network must be 
done by authorised personnel 

and according to current legislation, 
e.g. the EU standard for 
electromagnetic compatibility (EMC).

Figure 1.

Minimum distance requirements 

for unidirectional jet fans

Figure 2.

Minimum distance requirements 

for reversible jet fans

500

500*

500

2000

500*

* Minimum 500 mm
   free for air intake

Detail
figure 4

Detail
figure 4

Use lowering brackets
in areas with high beams

Bottom jet fan
= beam height

2000

2000

2000

2000

Use lowering brackets
in areas with high beams

Bottom jet fan
= beam height

Figure 3.

Principle of installation

Dimensions [mm]

Bolts

Types and sizes

H

A

B

C

AUO/ARO 290 320 506 560 4 x ø14 M12

AUO/ARO 380 420 506 720 4 x ø14 M12

AUO/ARO 500 540 600 830 4 x ø14 M12

ARP 340

422 283 520 4 x ø14 M12

AUZ 340

422 283 520 4 x ø14 M12

AUT/ART 400 423 779 470 4 x ø14 M12

AZT 280

343 340 150 4 x ø11 M10

AZT 355

437 428 205 4 x ø11 M10

AZT 450

530 540 260 4 x ø11 M10

Table 5.

Mounting specifications

Figure 4.

Example of ceiling installation 

with vibration dampers

Item 01 Jet fan

Item 02 Expansion bolt

Item 03 Ceiling

01

02

03

B

A

C

H

Airflow

Top view

Side view

Airflow

Vibration
dampers
Disc

Concrete
screw 10x130

Steel pipe

Figure 5.

AZT: Example of ceiling 

installation

Figure 6.

AZT: Slide bolts in slits

Steel pipe

Vibration
dampers

Disc

Concrete
screw 10x130

Summary of Contents for NOVENCO ARO

Page 1: ...Pure competence in air ENGLISH 919044 0 NOVENCO JET FAN TYPES AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE...

Page 2: ...plates on the fan casings Fan nameplate information Manufacturer information Product type e g AUO 380 160 4 Serial no Fan speed Year of manufacture Weight CE marking For smoke fans also Air performanc...

Page 3: ...d the operational conditions and the natural frequency of the foundation and supports Follow the below guidelines to avoid resonance Soft suspension Fan is fixated through springs or dampers The natur...

Page 4: ...the underside of the fan casing Reinsert the screws from the brackets in the casing AZT Reinsert the screws from the transport brackets in the casing 4 3 Electric connection The installation and conn...

Page 5: ...airflow Electrical connections The electrical connections must be correct and in accordance to the prescribed requirements Switch the fan power briefly On then Off to check the rotational direction of...

Page 6: ...fasteners item 01 and take down the fan 3 AUO ARO Remove set screws item 02 and dismount silencers items 03 Mark the silencers with tape so they are not mixed up ARP AUZ Remove set screws item 02 and...

Page 7: ...mance Inlet or outlet blocked Auxiliary fans stopped Motor defective Motor disconnected Electric connection defective Wrong direction of rotation Noise and vibrations Motor bearings defective Rotor in...

Page 8: ...to changes without furthernoticeduetocontinuousproduct development Copyright 1985 2020 Novenco Building Industry A S All rights are reserved 14 Quality management Novenco is ISO 9001 and 14001 certif...

Page 9: ...eclaration is valid provided that the installation and maintenance instructionsarefollowed Changestothe product without prior consultation with Novenco Building Industry A S invalidates the declaratio...

Page 10: ...r 10 Suspension brackets AZT Base plate 5 Motor suspension and guide vanes 11 Wire guard 6 Start stop switch or terminal box 12 Centre fairing Figure 11 Main components 10 07 03 01 04 11 09 05 06 10 0...

Page 11: ...s 12 Rivets 16 Stiffeners Figure 12 Main components Figure 13 Switch and connection diagram for AUO and ARO for both standard temperatures and 300 C optional Figure 14 External terminal box and connec...

Page 12: ...Pure competence in air ttt EKs E K h E KD...

Reviews: