Novenco
®
jet fan types AUO/ARO - ARP/AUZ - AUT/ART - AZT
3
It is essential for the
performances and sound levels
that the airflows are unimpeded
and free from eddies.
2.
Drill holes in the ceiling in
accordance to the mounting
specifications. See figure 3 and table
5.
If unapproved expansion bolts
for high temperature are to be
used, these must be made from
steel, must at least be size M8 and must
be mounted twice as deep as
recommended – at least 60
mm deep.
The static load must not exceed a pull of
more than 500 N.
3. Optional:
Install lowering brackets
in the ceiling, if applicable.
4.
Place the fan on a platform that can
be raised, for example a scissor lift.
5. AUO/ARO-ARP/AUZ-AUT/ART:
Fasten the fan in the suspension
points to the ceiling or, if applicable,
to the lowering brackets.
Notice:
It is recommended to install
vibration dampers. These
are optional and not
included as standard.
6. AZT:
Mount the base plate to the
ceiling or. if applicable, to the
lowering brackets and install the
vibration dampers.
Expansion bolts certified for fire
conditions must be used and
loaded according to the
approval.
Lift the fan in place with attention to
the correct insertion of the bolts,
which must enter and slide back in
the base plate slits.
7.
Check that the rotor rotate freely in
the fan casing.
8. AUO/ARO-ARP/AUZ:
Remove the
transport brackets on the underside
of the fan casing. Reinsert the screws
from the brackets in the casing.
AZT:
Reinsert the screws from the
transport brackets in the casing.
4.3 Electric connection
The installation and connection
to the supply network must be
done by authorised personnel
and according to current legislation,
e.g. the EU standard for
electromagnetic compatibility (EMC).
Figure 1.
Minimum distance requirements
for unidirectional jet fans
Figure 2.
Minimum distance requirements
for reversible jet fans
500
500*
500
2000
500*
* Minimum 500 mm
free for air intake
Detail
figure 4
Detail
figure 4
Use lowering brackets
in areas with high beams
Bottom jet fan
= beam height
2000
2000
2000
2000
Use lowering brackets
in areas with high beams
Bottom jet fan
= beam height
Figure 3.
Principle of installation
Dimensions [mm]
Bolts
Types and sizes
H
A
B
C
AUO/ARO 290 320 506 560 4 x ø14 M12
AUO/ARO 380 420 506 720 4 x ø14 M12
AUO/ARO 500 540 600 830 4 x ø14 M12
ARP 340
422 283 520 4 x ø14 M12
AUZ 340
422 283 520 4 x ø14 M12
AUT/ART 400 423 779 470 4 x ø14 M12
AZT 280
343 340 150 4 x ø11 M10
AZT 355
437 428 205 4 x ø11 M10
AZT 450
530 540 260 4 x ø11 M10
Table 5.
Mounting specifications
Figure 4.
Example of ceiling installation
with vibration dampers
Item 01 Jet fan
Item 02 Expansion bolt
Item 03 Ceiling
01
02
03
B
A
C
H
Airflow
Top view
Side view
Airflow
Vibration
dampers
Disc
Concrete
screw 10x130
Steel pipe
Figure 5.
AZT: Example of ceiling
installation
Figure 6.
AZT: Slide bolts in slits
Steel pipe
Vibration
dampers
Disc
Concrete
screw 10x130