Installation, Mounting and Maintenance DISA-360

Z11/35 - 4

Construction subject to change.

No return possible!

20.10.2015

Version:

General information

Identification of the delivered model

The ceiling induction diffuser type DISA-360 is available in four

different nozzle configurations: 

B

C

D

 and 

E

.  The entire series

is available in the following nominal lengths: 

600

 (592, 597,

617, 622 mm) and 

1200

 (1192, 1197, 1242, 1247 mm). 

Housing (1): 

Galvanised sheet steel with 1 or 2 connection pipes

DN 

98

 and 

123

 mm (standard). Connection pipe position hori-

zontal (

-H

) or vertical (

-V

).

Register (2): 

2-pipe system (cooling or heating) or optionally 4-

pipe system (cooling and heating) The registers consist of cop-

per pipes 12 mm in thickness, aluminium ribs and a steel frame.

Grille (3): 

Possible designs: perforated sheet grille made of gal-

vanised sheet steel (perforated sheet grille models: 

-SR, -SQ, -

RE

 and 

-OB

) made of extruded aluminium profile (

-PA

). Both

painted to RAL 9010 (white, standard).

Hydraulic connections (4)

: Copper pipes ø 12 mm

Function

The primary air (1) supplied from the plenum box induces sec-

ondary air in the room (2), which is cooled or heated via the reg-

ister (4).

The combined (3) primary (external) and secondary air (room

air) flows are supplied to the room at low velocity via 4 linear

supply air slots.

Schematic diagram of the mode of operation

Schematic diagram of the jet path

1

2

4

3

DISA-...-SR DISA-...-SQ DISA-...-RE DISA-...-OB

1

3

4

2

Summary of Contents for DISA-360

Page 1: ...Ferdinand Schad KG Steigstra e 25 27 D 78600 Kolbingen Telephone 49 0 74 63 980 0 Fax 49 0 74 63 980 200 info schako de www schako de Installation Mounting and Maintenance DISA 360...

Page 2: ...ered model 4 Function 4 Installation and commissioning 5 Operating conditions 5 Material reception 5 Transport lifting and handling 5 Storage 5 Installation 6 Mounting 6 Hydraulic connections 6 Connec...

Page 3: ...lacement of defec tive materials Recycling The inspection installation hydraulic connection and com missioning of the device must be carried out by qualified skilled personnel only in compliance with...

Page 4: ...ing or optionally 4 pipe system cooling and heating The registers consist of cop per pipes 12 mm in thickness aluminium ribs and a steel frame Grille 3 Possible designs perforated sheet grille made of...

Page 5: ...Foldable perforated sheet perforation 6 mm B Nozzle configuration B 592 total width 592 mm 592 total length 592 mm WS1 Water connection left H Connection horizontal AS1 Number of connecting pieces 1 c...

Page 6: ...void excessive tighten ing or twisting of the register connections Make sure that places that are intended as openings for air admission and air discharge are free of pipes electric ca bles crossbeams...

Page 7: ...ends on the select ed model Please follow the instructions enclosed with each model Adjustment of the air deflection blades To regulate the air flow ro tate the air deflection blades manually With blo...

Page 8: ...by spraying it with a non aggressive cleaner Hydraulic connections were tightened properly and exhib it no leaks Connecting and fastening elements have been sufficiently tightened Adequate access for...

Page 9: ...lean it by spraying it with water or compressed air or by evacua tion Please do not use any scouring agents for cleaning since these materials may impair or damage the DISA 360 gal vanised steel alumi...

Page 10: ...e nozzles at the primary air plenum box see drawing and the other end is con nected to the hose connection of a Pa meter The values read on the meter and the following formula can be used to to determ...

Page 11: ...or Install thermostat in a different place Clogging of the cooling heating register Clean the register in accordance with the maintenance instructions The unit is losing water Condensate in the regist...

Reviews: