background image

 

 

Schaffner EMV AG

   Nordstrasse 11   CH-4542 Luterbach 

T +41 32 681 66 26   F +41 32 681 66 30   www.schaffner.com  

2004-176C 

safety for electronic systems 

Installation guidelines FN 3025 and FN 3026 

Thank you for choosing Schaffner FN 3025/FN 3026 filters to solve your EMC challenges. Please 
follow the guidelines below to ensure a satisfying and reliable filter function for many years of 
operation. 

 

1. General guidelines 

Q

  Mount the filter on a clean conductive surface (or DIN-rail) free of paint or lacquer. 

Q

  Install the filter as close as possible to the noise source, using short direct wire connections. 

Q

  Protect the filter from liquid, excessive dust and aggressive gases. 

Q

  Do not expose the filters to conditions beyond specifications in the datasheet. 

 

2.  Installation and electrical connection 

 

FN 3025/FN 3026 are delivered with 
closed plastic safety covers and 
unfastened terminals. To install the 
filter please proceed as follows: 

Q

  Mount the filter on a metal surface 

with four appropriate screws and 
washers or snap it onto a TS 35 
DIN-rail. 

Q

  First connect the green/yellow wire 

to the earth stud of the filter. 

Q

  Gently lift the two hinged plastic 

covers. 

Q

  Connect phase wires with cable 

lugs by pushing down and 
tightening the screws. 

Q

  Please note the torque 

recommendation on top of the 
filter. 

Q

  Push the covers back into their 

locked position to finish the filter 
installation. 