SBS SBS-H2 Installation, Operating,  & Maintenance Instructions Download Page 7

SBS-H2 Users Manual 

Rev 1.4 

January 6

th

 2013 

For installation of a second sensor 

One additional sensor may be added to each detector.  Multiple detectors can be installed to 
meet the space coverage requirements of your particular installation. 

 

Locate the 2

nd

 sensor installation point within 25 feet of the detector and mount the sensor.  

Connect the cable from the second sensor to the Sensor 2 input labeled on the cover.  On the 
detector printed circuit board, remove the jumper on P9 to enable the second sensor input. 
Either sensor is capable of triggering a warning or alarm condition. 
 

Switching from Voltage to Current Output-

 Required when using cable longer than 100 ft. 

When using cable exceeding  the 100FT sensor cable (

SBS Part# H2-100FT-CABLE), 

 the 

Sensor jumper must be moved on the sensor input from the off condition to the on condition, so 
it covers both pins.   

1.  Removing the front snap on cover will reveal the inner electronics of the alarm box. 
2.  Locate the signal output select jumper(s) (P5 for Sensor 1 and P6 for Sensor 2). 
3.  Install the jumper across the two pins to enable the current output mode (see photos) 

 

 

 
 
 

 

Wiring Diagram: 

 

 
1. The detector has 2 internal relays.  One relay energizes when the sensor detects a 1% 
concentration of hydrogen gas in the air surrounding it. The second relay contact energizes at a 
2% concentration. 
The detector's internal relays are rated: 10 amps at 250 volts ac; 10 amps at 30 volts dc; 1/3 
horsepower at 125 volts ac; 1/2 horsepower at 250 volts ac. 

    Sensor Disabled

 

(40mA Signal Output)

 

Sensor Enabled

 

(Voltage Signal Output)

 

Note:

  (Alarm  will  emit  a 

“chirp”  noise if  sensors are 
not connected)

 

Pre-March 2016 Version

Summary of Contents for SBS-H2

Page 1: ...rooms and other areas where hydrogen gas may be present INSTALLATION OPERATING MAINTENANCE INSTRUCTIONS Protects Life Property and Profits 1 800 554 2243 www sbsbattery com TEST sbsbattery com Compli...

Page 2: ...have to use two or more detectors with 1 or 2 sensors each for increased detection The hydrogen sensor does not provide protection from fires or hydrogen explosions The relay contacts are intended to...

Page 3: ...ive limit LEL of 4 1 2 0 Benefits In addition to protecting your employees and your property the detector may also reduce the following costs Electricity Heating Air Conditioning Instead of continuous...

Page 4: ...t supply to the unit Relays 1 Warning Relay 1 Normally Open 1 Normally Closed contact 2 Alarm Relay 1 Normally Open and 1 Normally Closed contact 5 0 Sensor The sensor consists of a ceramic sensing el...

Page 5: ...gen gas concentration in the air immediately surrounding the sensor Hydrogen gas may accumulate in several areas of the battery compartment or room therefore individual detectors should be installed i...

Page 6: ...2 alarm relay that is energized at 2 concentration of hydrogen gas The relays can be used to switch on a remote exhaust fan and or to turn on an alarm For 120 VAC power use 18 gage stranded wire minim...

Page 7: ...le SBS Part H2 100FT CABLE the Sensor jumper must be moved on the sensor input from the off condition to the on condition so it covers both pins 1 Removing the front snap on cover will reveal the inne...

Page 8: ...er Select between single or multiple sensor set up default jumper settings single sensor Jumper on P9 Only Place a jumper on P8 to disable SENSOR 1 Place a jumper on P9 to disable SENSOR 2 B Signal Ou...

Page 9: ...ion you would like to use the relay to be related to Use Relay C for the warning condition 1 H2 and relay D for the alarm condition 2 H2 3 Restore the front covering of the alarm box and re secure the...

Page 10: ...alarm will stop and the 2 relay will de energize When the concentration falls below 1 the 1 relay will de energize and the Yellow LED will turn off 9 0 Electrical Testing after the input power is on...

Page 11: ...11 SBS H2 Users Manual Rev 1 4 January 6th 2013 Pre March 2016 Version...

Page 12: ...ther application intended to support or sustain life or for any application in which the failure of the SBS product could create a situation where personal injury or death may occur Should buyer purch...