32 A Single Phase active power energy meter with Modbus interface, Pic. 1

Description

Energy meter with Modbus interface enables the reading of 

all relevant data like consumption, current, voltage, power 

(active and reactive) and cos phi. 

Indicating elements (Pic. 4)

unidirectional:

T total (kWh) 

 

Indicates the total consumption 

T part (kWh) 

  

Indicates the partial consumption. 

This value can be reset 

P (kW) 

 

Indicates the instantaneous power 

2000 pulses/kWh  

  

Pulsates according to the amount 

of used power. Error indication 

(line 1L/2L inverted) with pulse of 

600/600 ms.

bidirectional:

T   (kWh) 

  

Indicates the total consumption 

T   (kWh) 

 

Indicates the total feeding back 

P (kW) 

  

Indicates the instantaneous power  

Current   = consumption (pos.) 

Current   = feeding back (neg.)

2000 pulses/kWh  

  

Pulsates according to the amount 

of used power. 

common:

U (V)  

 

Indicates the voltage 

I (A)  

 

Indicates the current

Technical data

Connection  

  Pic. 2

diagram

Dimensions 

 

Pic. 3

Accuracy class 

 

B according to EN50470-3,  

 

 1 according to IEC62053-21

Reference, Maxi- 

 

I

ref

 = 5 A, Im

ax 

= 32 A, Ist

 =

 20 mA

mum, initial current

operating voltage 

 

230 V

AC

, 50 Hz 

 

  Tolerance −20%/+15%

Counting range 

  00 000,00…999 999,9 kWh

Connections 

 

Conductor cross-section max. 6 mm

2

Main circuit 

  screwdriver pozi no. 1, slot no. 1,  

 

  torque 1,2 Nm

Connections 

 

Conductor cross-section max. 2,5 mm

2

,  

Control circuit 

  screwdriver pozi no. 0, slot no. 1, 

 

  torque 0,5 Nm

Operating  

 

−25… +55°C (noncondensing

temperature 

  according standard EN50470)

Environment  

  Mechanical M2

 

  Electromagnetic E2

Notes before connecting 

In order to avoid moisture in the meter due to condensate 

build-up, acclimatise the meter at room temperature for 

about half an hour before connecting.

Attention!

These devices must only be installed by a professional 

electrician, otherwise there is the risk of fire or the risk of 

an electric shock. 

Declaration of Conformity CE

We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-

land), herewith declare, on our own responsibility that 

the products:

 

 

ALD1D5FD00A3A00  

 

 

ALD1B5FD00A3A00 

which this certificate refer to, are in accordance with the 

directive 2004/22/EG (MID) and the following standards:
 

  EN50470 parts 1 and 3 (electronic meter), of  

  October 

2006. 

ESD on equipment side: 13 kV.

Murten, 30.04.2013

Conformity Assessment Body:

    METAS-Cert, Nr. 1259

  CH-3003 

Bern-Wabern 

Signed: Urs Tanner, Site Quality Leader

English

Installation instructions

The energy meter can be attached to a 35 mm rail 

(EN60715TH35). 

The meter can be used only in installation cabinets. 

Operation of the LCD display

See page with LCD menu navigation. 

431951150G  

03.2017  

Subject to change without notice

Summary of Contents for Saia PCD ALD1B5FD

Page 1: ... kWh Zeigt den totalen Energie verbrauch T kWh Zeigt die totale Energierück speisung P kW Zeigt die momentane Leistung Strom Bezug positiv Strom Rückspeisung negativ 2000 Imp kWh Pulsiert entsprechend der bezogenen Leistung gemeinsam U V Zeigt die Spannung I A Zeigt den Strom Hinweise vor dem Anschliessen Um Feuchtigkeit im Zähler durch Kondenswasser zu ver meiden den Zähler vor dem Anschliessen c...

Page 2: ...Abschlusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Datenübertragung Nur Read Holding Registers 03 Write Multiple Registers 16 Anweisungen werden erkannt Es können bis zu 20 Register auf einmal gelesen werden Das Gerät unterstützt Broadcast Nachrichten Gemäss Modbus Protokoll wird ein Register R bei der Übertragung als R 1 n...

Page 3: ... cross section max 6mm2 Main circuit screwdriver pozi no 1 slot no 1 torque 1 2 Nm Connections Conductorcross sectionmax 2 5mm2 Control circuit screwdriver pozi no 0 slot no 1 torque 0 5 Nm Operating 25 55 C noncondensing temperature according standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before connecting In order to avoid moisture in the meter due to condensate build up acc...

Page 4: ...ve a terminal resistor this must be provided external For a description of the used registers please look at the register page Data transmission Only Read Holding Registers 03 Write Multiple Registers 16 instructions are recognized Up to 20 Registers can be read at a time The device supports broadcast messages In accordance with the Modbus protocol a register R is numbered as R 1 when transmitted ...

Page 5: ... tempo di cyclo 600 600 ms bi direzionale T kWh Indica il consumo totale T kWh Indica il recupero totale P kW Indica l uscita istantanea corrente consumo pos corrente recupero neg 2000 impulsi kWh Impulsi secondo l uscita indicata in generale U V Indica la tensione I A Indica la corrente Dichiarazione di conformità CE Noi Saia Burgess Controls AG CH 3280 Murten Svizzera dichiarammo in nostra propr...

Page 6: ...sta dovrebbe essere disponibile esternamente Per una descrizione dei registri utilizzati consultare la Pagina Registri Trasmissione dei dati Vengono riconosciute solo le istruzioni Read Holding Registers 03 Write Multiple Registers 16 Possono essere letti fino a 20 registri alla volta L apparecchio supporta messaggi braodcast In base al protocollo Modbus un registro R verrà numerato come R 1 quand...

Page 7: ...ons en fonction de la puis sance absorbée Indication d erreur inversion de ligne impulsion 600 600 ms bidirectionnelle T Consommation totale T Récupération totale P kW Puissance instantanée courant consommation pos courant récupération neg 2000 pulses kWh Impulsions en fonction de la puissance absorbée en général U V Tension I A Courant Déclaration de conformité CE Nous Saia Burgess Controls AG CH...

Page 8: ... est pas dotée d une résistance de terminaison celle ci doit être mise en place de façon externe Les registres utilisés sont décrits dans la liste de registres Transfert de données Seules les instructions Read Holding Registers 03 Write Multiple Registers 16 sont supportées Jusqu à 20 registres peuvent être lus en même temps L appareil prend en charge les messages de broadcast Selon le protocole M...

Page 9: ...kW kW kW I A 2000 Imp kWh T part kWh T total kWh ALD1D5F 5560 L1 N B U V P P P kW kW kW I A 2000 Imp kWh T part kWh T total kWh ALD1D5F D D Modbus pair of wires twisted max 1200 meters 230 V B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5F T T ...

Page 10: ... Status 0 no Problem 1 problem with last communication request 23 X Response Timeout ms 24 X X1 Modbus Address Range 1 247 25 X Error register 0 No error 1 Error 26 X Not Used Will give 0 27 X Not used Tariff register Will give 0 0 4 28 29 X Counter Energy Total Tariff 1 WT1 total WT 10 2 kWh multiplier 0 01 Ex WT1 total High 13 WT1 total Low 60383 13 65536 60383 912351 9123 51 kWh 30 31 X X Count...

Page 11: ...Menu to display the value on LCD Start T total Total consumption T Tariff consumption T part Partial consumption T Tariff feeding back P Instantaneous power 3 s 3 s only only ...

Page 12: ...y management combined heat and power station protocol VISI energy lift cooling heating ventilation temperature setpoint lighting shade control sanitation sheduler VISI trending remote alarming VISI visualization VISI building traffic control water treatment IT Data Logistic system tele communication graphic editor VISI 3 s 2 s ...

Reviews: