Assembly and operating instructions ALD1B5F10K
32 A bidirectional Single Phase active power energy meter with S0 interface, Pic. 1
Description
Energy meter with S0-interface for the integrated
transmission of measured values in building automation.
The LC - display add value such as power and read voltage
and current.
Indicating elements (Pic. 4)
T (kWh)
■
Indicates the total consumption
T (kWh)
■
Indicates the total feeding back
P (kW)
■
Indicates the instantaneous power
Current = consumption (pos.)
Current = feeding back (neg.)
U (V)
■
Indicates the voltage
I (A)
■
Indicates the current
2000 pulses/kWh
■
Pulsates according to the amount
of used power.
Technical data
Connection
■
Pic. 2
diagram
Dimensions
■
Pic. 3
Accuracy class
■
B according to EN50470-3,
1 according to IEC62053-21
Reference, Maxi-
■
I
ref
= 5 A, Im
ax
= 32 A, Ist
=
20 mA
mum, initial current
operating voltage
■
230 V
AC
, 50 Hz
Tolerance −20%/+15%
Counting range
■
00 000,00…999 999,9 kWh
S0-Ouptut
■
Optocoupler max. 30V/20mA
and min. 5V, impedance 100Ω,
pulse duration 30ms
1000 Imp./kWh
Connections
■
Conductor cross-section max. 6 mm
2
,
Main circuit
screwdriver pozi no. 1, slot no. 1,
torque 1,2 Nm
Connections
■
Conductor cross-section max. 2,5 mm
2
,
Control circuit
screwdriver pozi no. 0, slot no.1,
torque 0,5 Nm
Operating
■
−25… +55°C (noncondensing
temperature
according standard EN50470)
Environment
■
Mechanical M2
Electromagnetic E2
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk of
an electric shock.
Declaration of Conformity CE
We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-
land), herewith declare, on our own responsibility that
the products:
■
ALD1B5F10KA3A00
which this certificate refer to, are in accordance with the
directive 2004/22/EG (MID) and the following standards:
■
EN50470 parts 1 and 3 (electronic meter), of
October
2006.
ESD on equipment side: 13 kV.
Murten, 30.04.2013
Conformity Assessment Body:
METAS-Cert, Nr. 1259
CH-3003
Bern-Wabern
Signed: Urs Tanner, Site Quality Leader
English
Installation instructions
The energy meter can be attached to a 35 mm rail
(EN60715TH35).
The meter can be used only in installation cabinets.
Operation of the LCD display
See page with LCD menu navigation.
4 319 5138 0E
03.2017
Subject to change without notice
Method of operation
Energy is added as indicated by the arithmetic operator.
Positive output in the meter indicates that energy is being
supplied, while negative output indicates that energy is
being delivered.
The S0 pulses are issued depending of the direction of the
energy flow. This function can be set from the menu.
in = pulses only for energy consumption
out = pulses only for energy recovery
bi = both energy flow directions