background image

Assembly and operating instructions ALD1B5F10K

32 A bidirectional Single Phase active power energy meter with S0 interface, Pic. 1

Description

Energy meter with S0-interface for the integrated 

transmission of measured values in building automation. 

The LC - display add value such as power and read voltage 

and current.

Indicating elements (Pic. 4)

T   (kWh) 

  

Indicates the total consumption 

T   (kWh) 

  

Indicates the total feeding back 

P (kW) 

    

Indicates the instantaneous power  

Current   = consumption (pos.) 

Current   = feeding back (neg.)

U (V)  

  

Indicates the voltage 

I (A)  

  

Indicates the current 

2000 pulses/kWh  

    

Pulsates according to the amount 

of used power. 

Technical data

Connection  

  Pic. 2

diagram

Dimensions 

 

Pic. 3

Accuracy class 

 

B according to EN50470-3,  

 

 1 according to IEC62053-21

Reference, Maxi- 

 

I

ref

 = 5 A, Im

ax 

= 32 A, Ist

 =

 20 mA

mum, initial current

operating voltage 

 

230 V

AC

, 50 Hz 

 

  Tolerance −20%/+15%

Counting range 

  00 000,00…999 999,9 kWh

S0-Ouptut  

  Optocoupler max. 30V/20mA  

 

  and min. 5V, impedance 100Ω,  

 

  pulse duration 30ms

 

  1000 Imp./kWh

Connections 

 

Conductor cross-section max. 6 mm

2

Main circuit 

  screwdriver pozi no. 1, slot no. 1,  

 

  torque 1,2 Nm

Connections 

 

Conductor cross-section max. 2,5 mm

2

Control circuit 

  screwdriver pozi no. 0, slot no.1, 

 

  torque 0,5 Nm

Operating  

 

−25… +55°C (noncondensing

temperature 

  according standard EN50470)

Environment  

  Mechanical M2

 

  Electromagnetic E2

Notes before connecting 

In order to avoid moisture in the meter due to condensate 

build-up, acclimatise the meter at room temperature for 

about half an hour before connecting.

Attention!

These devices must only be installed by a professional 

electrician, otherwise there is the risk of fire or the risk of 

an electric shock.

Declaration of Conformity CE

We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-

land), herewith declare, on our own responsibility that 

the products:

 

 

ALD1B5F10KA3A00

which this certificate refer to, are in accordance with the 

directive 2004/22/EG (MID) and the following standards:
 

  EN50470 parts 1 and 3 (electronic meter), of  

  October 

2006. 

ESD on equipment side: 13 kV.

Murten, 30.04.2013

Conformity Assessment Body:

    METAS-Cert, Nr. 1259

  CH-3003 

Bern-Wabern 

Signed: Urs Tanner, Site Quality Leader

English

Installation instructions

The energy meter can be attached to a 35 mm rail 

(EN60715TH35). 

The meter can be used only in installation cabinets. 

Operation of the LCD display

See page with LCD menu navigation.

4 319 5138 0E  

03.2017 

Subject to change without notice

Method of operation 

Energy is added as indicated by the arithmetic operator. 

Positive output in the meter indicates that energy is being 

supplied, while negative output indicates that energy is 

being delivered.

The S0 pulses are issued depending of the direction of the 

energy flow. This function can be set from the menu.

in    = pulses only for energy consumption 

out   = pulses only for energy recovery 

bi    = both energy flow directions

Summary of Contents for Saia PCD ALD1B5F10K

Page 1: ...c 2 Pic 4 B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5F T T B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5F T T L1 N 230 VAC 5 30V S0 S0 431951380E 4 319 5138 0E 03 2017 Subject to change without notice ...

Page 2: ...en Leistung Hinweise vor dem Anschliessen Um Feuchtigkeit im Zähler durch Kondenswasser zu ver meiden den Zähler vor dem Anschliessen ca eine halbe Stunde bei Raumtemperatur akklimatisieren Achtung Diese Geräte dürfen nur durch eine Elektrofachkraft installiert werden andernfalls besteht Brandgefahr oder Gefahr eines elektrischen Schlages EG Konformitätserklärung Wir Saia Burgess Controls AG CH 32...

Page 3: ...romagnetic E2 Notes before connecting In order to avoid moisture in the meter due to condensate build up acclimatise the meter at room temperature for about half an hour before connecting Attention These devices must only be installed by a professional electrician otherwise there is the risk of fire or the risk of an electric shock Declaration of Conformity CE We Saia Burgess Controls AG CH 3280 M...

Page 4: ...Menu to display the value on LCD Start P Instantaneous power T Tariff consumption T Tariff feeding back ...

Page 5: ...Saia Burgess Controls AG Bahnhofstrasse 18 I CH 3280 Murten I Schweiz T 41 26 580 30 00 I F 41 26 580 34 99 www sbc support com ...

Page 6: ...azione di conformità CE Noi Saia Burgess Controls AG CH 3280 Murten Svizzera dichiarammo in nostra propria responsabilità che i prodotti ALD1B5F10KA3A00 di quali si riferisce questa dichiarazione rispondono alla direttiva 2004 22 CE MID e alle normative seguente normativa EN50470 Parte 1 e 3 Contatori elettronici Octobre 2006 ESD sul lato dell apparato 13 kV Murten 30 04 2013 Organismi di valutazi...

Page 7: ...2000 pulses kWh Impulsions en fonction de la puissance absorbée Déclaration de conformité CE Nous Saia Burgess Controls AG CH 3280 Murten Suisse déclarons sous notre propre responsabilité que les produits ALD1B5F10KA3A00 pour lesquels cette déclaration se référe sont conformes à la directive 2004 22 CE MID et aux normes suivantes EN50470 Parties 1 et 3 Compteurs électroniques Octobre 2006 ESD sur ...

Page 8: ...Back to Start Instan Power P Current I Voltage U 3 s Start 20 s ...

Reviews: