Warning 

Please read these instructions carefully before commencing any work
This Emergency pack must be fitted by a competent and qualified electrician.
Install in accordance with the IEE Wiring regulations and current Building Regulations.

Please Note:

 The limited warranty shall be deemed null and void in the following circumstances: Failure by the installer, end

user or any third party to exercise caution to protect any covered product or part from outside damage, adverse temperature
(normal operating ambient temperature 0 - 25°C), humidity conditions, fluctuations in the electrical system or physical abuse
as well as failure related to workmanship in the installation of the products or parts.
These products are designed for connection to a 220-240V~50Hz supply.
Check the pack and make sure you have all the parts listed.
To prevent electrocution switch off at the mains supply before installing or maintaining this fitting. Ensure other persons
cannot restore the electrical supply without your knowledge.
This Emergency pack is suitable for indoor use only.
If replacing an existing fitting, make a careful note of the connections.
Do not use Megger or similar high voltage instruments. Due to the fact this Emergency pack contains electronic components
that maybe damaged by high test voltages, they must be disconnected from the circuit before testing.
To prevent damage to the Emergency pack, do not mix with conventional magnetic ballasts on the same electrical circuit.
Any faulty, broken or damaged modules should be replaced immediately.
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with
your local authority or retailer for recycling advice.

Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory

operation of this product. Please retain these instructions for future reference. 

This light fitting is double insulated and does

not require connection to an Earth circuit.

Check that...

•  You have correctly identified the wires.
•  The connections are tight.
•  No loose strands have been left out of the connection block.

Familiarize yourself with the installation procedure and ensure the power is safely isolated before installing the Emergency pack.

Ensure the LED luminaire is within the specification 9-80VDC.

Installation

Existing fittings must be completely removed before installation of a new product. Before removing the existing fitting, carefully

note the position of each set of wires.
Note that the switch is turned off  before installation.  

Wire as required below (Fig.1):

Non-Maintained Emergency:

Connect the mains input Unswitched Live (

PL

), Neutral (

N

). The low voltage side just requires output to the LED luminaire

positive (

+

) and negative (

-

). Then connect the battery. Install the LED indicators in a suitable location.

Maintained Emergency:

Connect the mains input Unswitched Live 

(PL

), Neutral (

N

) and Switch Live (

SL

). Connect the Live out (

L

D

) and Neutral out

(

N

D

) to the driver mains input. The low voltage side connect the output from the LED driver to the LED Driver output (

+

) and

Negative (

-

) luminaire output to the output to LEDs positive (

+

) and negative (

-

). Then connect the battery. Install the LED

indicators in a suitable location.

Please note: For manual testing purposes a provision is made inside the cover of the low voltage side of the driver
(Fig.1) marked as Test on the casing. See overleaf for details on manual testing. 

Turn on the power and ensure that the module is showing charge indicator.
This fitting requires a minimum 24 hours initial charge period prior to any manual emergency testing.
The battery has a rated duration of at least 4

years but should be replaced if the duration

of operation is less than 3 hours after a 24hr

charge time with no interrupted supply.
All full duration tests should be where 

possible be undertaken at times of low risk

adjacent emergency luminaires we 

recommend that you you reset the inbuilt

timer or run a manual 30 day test to stagger

testing times. Once commissioned fill in the

date of the first test/install date this will

allow the end user to monitor and record 

subsequent test information on the supplied

report. All tests with the exception of the

visual inspection will be completed

automatically including battery charge

condition and lamp status.      

L
N
N
SL
PL

BAT -
BAT +

Test

G+

G-

R+

R-

+

-

+

-

Output to LEDs

LED Driver output

Output to LED

Luminaire

N

L

-
+

Output to LED

LED Driver

240VAC Input

Input from mains

supply

Battery connector

Red/Green Status LED

Maintained Emergency optional wiring

Manual Test Button

D

D

Daily:

The battery in this product has self testing

function. Visual inspection of the battery

charge LED as below:

Automatic Monthly (Every 30 Days):

(in addition to the daily check)The results of
the short duration test shall be recorded.

Automatic Annually (Every 180 & 360

Days):

 (in addition to the daily check)

The results of the full duration tests shall

be recorded.

Manual Testing - 

Can only be completed under mains conditions

Manual Simulated Power Failure
Manual 30 Day Test
Manual 180/360 Day Test
Manual Fast Test (24 minutes)

Hold test button until you hear 1 beep
Hold test button until you hear 2 beeps
Hold test button until you hear 3 beeps
Hold test button until you hear 4 beeps

Abort Test

Hold the test button for 15 seconds, when you

hear the long sound, the self-test function will

restore the defaults

Fault Indicators:

Red LED flashing once a second, Green LED off,

Beeps twice every minute until fault rectified
Red LED flashing twice a second, Green LED off,

Beeps twice every minute until fault rectified

Battery/Charging Fault

Lamp Fault

Failed Duration Test

Red LED solid, Green LED off, Beeps twice every

minute until fault rectified

Performance Indicators:

Normal Operation

Automatic 30 Day Test
Automatic 180/360 Day Test

Manual Simulated Power Failure
Manual 30 Day Test
Manual 180/360 Day Test
Manual Fast Test (24 minutes)

Red LED off, Green LED Solid
Red LED off, Green LED flashing once a second
Red LED off, Green LED flashing twice a second
Red LED off, Green LED off

Red LED off, Green LED four times a second

Red LED off, Green LED flashing once a second
Red LED off, Green LED flashing twice a second