Battery Replacement

We recommend cleaning with a soft dry cloth. Do not use solvents or abrasive cleaners as these could damage the finish.
For your safety, always switch off the power supply before cleaning.

Care and Safety

Technical data

220-240 V~, 50 Hz

Supply

Voltage: 

If after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack may be required.

• Switch off the electricity at the mains, both switched and permanent supply.
• Allow batteries to fully discharge then reconnect to supply and allow to charge for 24 hours.
• Test again for 3 hours, if light does not remain lit change the battery pack as follows:
    - Disconnect from the mains supply both permanent and switched supply.
    - Undo the cover on the back of the product.
    - Unplug the battery lead from the lead coming.
    - Remove the battery pack and lift the battery pack out of the fitting. Waste electrical products should not be disposed of

       with household waste. Please recycle where facilities exist. Check with your local authority or retailer for recycling advice.
    - 

Replace the battery with a LiFePO4 6.4V 1500mAh only

. Use of a different type of battery will damage the product.

    - Write current date on the new battery pack.
    - Fit new battery pack in position.
    - Plug battery pack into circuit board.
    - Close and secure cover on the back of the product.
    - Restore power and allow to charge for 24 hours.
    - Perform full operation check and update test record.  

Conformity with all relevant EC Directive requirements.

The power supply is Double Insulated and does not require connection to an Earth circuit.

Waste electrical products should not be disposed of with household waste. Please recycle where facilities

exist. Check with your Local Authority or local store for recycling advice. 

Live Voltages may be present in this unit even when turned off or when completely disconnected.

Conformity with all relevant UKCA Directive requirements.

V1 28/07/2021

EU Manufacturer: 1 Gnarrenburg, 27442

UK Manufacturer: BH17 7BY

Duration:

 3 hours (180 minutes)

Operating Temperature

: -20ºC to 45ºC

Maximum Operatin Humidity:

 10-90%

Output:

 9-80VDC - 3W Maximum

Charge Current:

 100mA

This product is rated at IP20.

IP

20

Battery Current:

 1.5A Maximum

Change over Time:

 Approximately 1s

Battery Specification:

 LiFePO4 6.4V 1500mAh

Battery Charge Time:

 24 hours

Battery warranty:  

2 years