Terminal 1 should be used for main control unit. 

Terminal 2 should be used for additional 

power-switching unit.

For cables longer than 2m, you have to assign the 

cable cross section to VDE 0100 respective to  EVU.

NOTE:

For more details please look 

your control unit or contactor 

unit manual.

NOTE:

Terminals and power rating

TYPE

POWER(MAX.)

VOLTAGE

CURRENT

Innova Control Unit 15kW

15 kilowatt

400V

21.5 Amp.

15 kilowatt

21.5 Amp.

Innova Contactor Unit 15kW

400V

Control and Contactor Specification

MODEL

(kW)

NIM-90NS

9
6   4.5
6   6
9   6
6   12

9   9
9   12
12 

  12

NIM-105NS
NIM-120NS
NIM-150NS
NIM-180NS
NIM-180NS-V12
NIM-210NS-V12
NIM-240NS-V12

TERMINAL 1

(kW)

TERMINAL 2

NIM-240NS-V12

24,0 kW

400V 3N~ 50/60Hz

G

N

U

V

W

N

U

V

W

G

2.

0K

W H

1

2.

0K

W H

2

2.

0K

W H

3

2.

0K

W H

4

2.

0K

W H

5

2.

0K

W H

6

2.

0K

W H

7

2.

0K

W H

8

2.

0K

W H

9

2.

0K

W H1

0

2.

0K

W H1

1

2.

0K

W H1

2

12kW

12 kW

TERMINAL 1

TERMINAL 2

SAUNA CONTROL UNIT

POWER DISTRUBUTION

400V 3N~ 

50/60Hz

TERMINAL1

SAUNA CONTROL UNIT

POWER DISTRUBUTION

400V 3N~ 

50/60Hz

TERMINAL1

TERMINAL 2

Control Unit

Control Unit

 Contactor Unit

CONTACTOR UNIT

SAUNA 

CONTROL UNIT

N

U

V

W

U

V

W

G

N

G

L

3

L

2

L

1

L

3

L

2

L

1

NIM-105NS

NIM-120NS
NIM-150NS

TERMINAL 1

TERMINAL 2

  4.5 kW

6 kW

6 kW

9 kW

6 kW

6 kW

HEATING SYSTEM

TERMINAL 1

TERMINAL 2

Using Contactor Unit

G

N

G

N

U

V

W

U

V

W

CONTROL

UNIT

CONTACTOR
UNIT

18,0-24,0kW

NIM-105NS

10,5 kW 400V 3N~ 50/60 Hz

6,0 kW

TERMINAL 1

4,5 kW

TERMINAL 2

G

G

N

N

W

V

U

W

V

U

W

V

U

W

V

U

2.0KW H1

2.0KW H3

1.5KW H4

1.5KW H6

1.5 H2KW

2.0KW H5

W

V

U

W

V

U

W

V

U

N

NIM-120NS

12,0 kW

400V 3N~ 50/60 Hz

6,0 kW

6,0 kW

TERMINAL 1

TERMINAL 2

G

G

2.0KW H1

2.0KW H3

2.0KW H4

2.0KW H6

2.0KW H2

2.0KW H5

NIM -180NS

18,0 kW 400V 3N~ 50/60 Hz

6 kW

12 kW

TERMINAL 1

TERMINAL 2

N

U

V

W

U

V

W

G

N

G

2.0KW H2

2.0KW H4

2.0KW H6

2.0KW H7

2.0KW H8

2.0KW H9

2.0KW H5

2.0KW H3

2.0KW H1

NIM-210NS-V12

21,0 kW

400V 3N~

50/60Hz

9 kW

12 kW

TERMINAL 1

TERMINAL 2

N

U

V

W

U

V

W

G

N

G

1.5KW H1

2.0KW H2

1.5KW H3

2.0KW H4

1.5KW H5

2.0KW H6

1.5KW H7

2.0KW H8

1.5KW H9

2.0KW H10

1.5KW H

11

2.0KW H12

U

V

W

U

V

W

NIM-180NS-V12

18,0 kW

400V 3N~

50/60Hz

9 kW

9 kW

TERMINAL 1

TERMINAL 2

N

G

N

G

1.5KW H1

1.5KW H2

1.5KW H3

1.5KW H4

1.5KW H5

1.5KW H6

1.5KW H7

1.5KW H8

1.5KW H9

1.5KW H10

1.5KW H1

1

1.5KW H12

NIM-150NS

15,0 kW 400V 3N~ 50/60 Hz

9,0 kW

6,0 kW

TERMINAL 1

TERMINAL 2

G

G

1.5KW H1

2.0KW H2

1.5KW H1

1.5KW H4

2.0KW H1

1.5KW H6

1.5KW H7

2.0KW H8

1.5KW H9

N

N

W

V

U

W

V

U

N

W

V

U

W

V

U

-90NS

NIM

9,0 kW 400V 3N~ 50/60 Hz

TERMINAL 1

9,0 kW

U

V

W

N

G

1.5KW H1

1.5KW H2

1.5KW H3

1.5KW H4

1.5KW H5

1.5KW H6

HUOM! 

Terminaali 1 varattu pää ohjauskeskuk-

selle.

Terminaali 2 varattu lisäkytkimelle.

2m pidempien johtojen läpimitan tulee 

täyttää EVU:n määrittämä VDE0100 

standardi.

HUOM!

Lisätietoja ohjauspaneelin 

tai kontaktoriyksikön man-

uaaleissa.

ELECTRICAL DIAGRAM

KYTKENTÄKAAVIO

Summary of Contents for NIM-105NS

Page 1: ... 180NS Super Nimbus V12 18 0 kW 21 0 kW 24 0 kW Super Nimbus 15 0 kW 18 0 kW Nimbus 9 0 kW 10 5 kW 12 0 kW NIM 105NS NIM 180NS V12 NIM 120NS NIM 210NS V12 NIM 150NS NIM 240NS V12 Onnittelut loistavasta kiuasvalinnastanne Tutustu käyttöohjeisiin huolellisesti ennen käyttöönottoa Congratulations on your purchase of SAWO sauna heater Please read the manual carefully before using the heater ...

Page 2: ...ER CAUSES FIRE HAZARD Turvaohjeet 4 Käyttäjälle 4 Asentajalle 6 Kiukaan asentaminen 8 Kytkentäkaavio 10 Sensorin sijainti NS mallit 12 Kiuaskivet 13 Vuolukivien latominen kiukaaseen 14 Kivien latominen kiukaaseen 14 Saunahuoneen lämmitys 16 Ilmanvaihto 18 Eristys 18 Saunan huolto 20 Vianetsintäkaavio 22 Varaosat 24 Tekniset tiedot 24 SISÄLLYSLUETTELO ...

Page 3: ...nstallation 9 Electrical diagram 10 Sensor location NS MODELS 12 Heater stones 13 Loading soapstones into the heater 15 Loading stones into the heater 15 Heating of the sauna room 17 Air ventilation 19 Insulation 19 Sauna maintenance 21 Diagnostic table 23 Spareparts 24 Technical data 24 ...

Page 4: ...ta ilman valvontaa Älä anna koskaan lasten leikkiä kiukaalla Älä käytä kiuasta grillinä Älä laita puita sähkökiukaalle Älä peitä kiuasta Se aiheuttaa palovaaran Älä kuivata vaatteita kiukaalla Se aiheuttaa palovaaran Älä istu kiukaalla Se on todella kuuma ja aiheuttaa palovammoja Älä käytä kloorivettä esim uima tai porealtaasta tai merivettä löylyvetenä Se tuhoaa kiukaan Kiukaan asentamisen jälkee...

Page 5: ...nces should children be allowed to play with the device Do not use the heater as a grill Do not put wood of any kind on the electric heater Do not cover the heater It may cause a fire Do not use the heater as clothes dryer It may cause fire Never sit on the heater It is really hot and can cause serious burns Do not use chlorinated water e g From the swimming pool or jacuzzi or seawater It can dest...

Page 6: ...va raitisilma ei vaikuta niiden toimintaan Julkisessa käytössä olevaan kiukaaseen jossa on viikkoajastin tai kauko ohjaus mahdollisuus on asennettava erillinen ovitunnistin saunan oveen Tunnistin kytkee pois päältä kaikki esiajastustoiminnot kun kiuas on valmiustilassa ja ovi avataan Ennen kiukaan asennusta tarkista valmistajan saunalle määrittelemät maksimi ja minimikoot Katso sivu 24 Varmista et...

Page 7: ...d control panel must be mounted outside the sauna cabin If this sauna heater is used for public saunas or saunas that may be switched on by a separate remote control system the door of the sauna room must be fitted with an interlock such that the stand by mode setting for remote operation is disabled if the sauna door is opened when the stand by mode setting for remote operation is set Observe the...

Page 8: ...saa tehdä kiukaan kytkennät Väärät kytkennät voivat aiheuttaa oikosulkuja ja palovaaran Katso sivu 10 kytkentäkaavio Kuva 1 Fig 1 HUOM Poista suojapahvi vastuksista ennen kiukaan asentamista Pahvi on tarkoitettu ainoastaan suojaamaan vastuksia kuljetuksen aikana HUOM Tarkista ohjauskeskuksen teholuokka ohjauskeskuksen käyttöohjeesta Tarkista ohjaimen maksimikapasiteetti ja hanki tarvittaessa lisäk...

Page 9: ...al Data See page 24 Do not install the heater to the floor or wall niche Do not install more than one heater in a sauna room unless you follow the special instructions for twin heater installations In most countries there is a law that requires heaters to be screwed to the floor The heater gets very hot To avoid the risk of accidental contact with the heater it is recommended that a heater guard b...

Page 10: ...W U V W CONTROL UNIT CONTACTOR UNIT 18 0 24 0kW NIM 105NS 10 5 kW 400V 3N 50 60 Hz 6 0 kW TERMINAL 1 4 5 kW TERMINAL 2 G G N N W V U W V U W V U W V U 2 0KW H1 2 0KW H3 1 5KW H4 1 5KW H6 1 5 H2KW 2 0KW H5 W V U W V U W V U N NIM 120NS 12 0 kW 400V 3N 50 60 Hz 6 0 kW 6 0 kW TERMINAL 1 TERMINAL 2 G G 2 0KW H1 2 0KW H3 2 0KW H4 2 0KW H6 2 0KW H2 2 0KW H5 NIM 180NS 18 0 kW 400V 3N 50 60 Hz 6 kW 12 kW ...

Page 11: ...ta ilmavent tiilistä NOTE Temperature sensor with safety fuse which prevents the heater from overheating must always be installed in the ceiling directly above the heater Do not install the temperature sensor with fuse closer than 1 meter from the ventilation louvers Do not place the sensors under 1 m from non directional air ventilation or not under 0 5 m from a directional air ventilation which ...

Page 12: ...tarkoitettuja kiuaskiviä oliviini tai oliviinidiabaasi Vääränlaisten kivien käyttö voi aiheuttaa mm vastusten ennenaikaisen hajoamisen Älä käytä kiukaassa keraamisia kiuaskiviä HEATER STONES The main purpose of the stones in the heater unit is to store enough energy to efficiently vaporize the water thrown on top of the stones to maintain correct humidity in the sauna room The stones must be remov...

Page 13: ...ittyvät mahdollisimman hyvin ulkoapäin katsottuna Vastusten ollessa kosketuksissa toisiinsa vastusten elinikä lyhenee huomattavasti HUOM Takuu ei korvaa vastuksia jotka ovat rikkoutuneet väärän kivilajin käytöstä tai virheellisen ladonnan aiheuttaman ylikuumenemisen tai sen aiheuttamista mekaanisista vaurioista Ennen kivien ladontaa tulee kiukaan toimivuus testata Testatessa kiuas laitetaan hetkek...

Page 14: ...the stones are loaded carefully in a way that they do not block air circulation through the heater Load the stones to the heater so that the heating elements are not visible from any angle Larger stones that won t fit between the heating elements must not be forced in place instead they must be completely removed Small crumble or stone pieces smaller than 35mm in diameter must not be loaded into t...

Page 15: ...ytön Mikäli savua tai hajua muodostuu yhä poistu saunasta välittömästi ja toista vaiheet 1 3 uudelleen Tarkistasaunaainaennenkiukaanpäällekytkemistä etteikiukaallataisensuojaetäisyyksien sisällä ole mitään palavaa Varmista että saunan tuuletus on riittävä ja asianmukainen Teholtaan oikean kokoinen kiuas lämmittää saunahuoneen valmiiksi noin tunnissa Katso sivu 24 Saunan lämpötilan tulisi olla noin...

Page 16: ... for the first time 4 If no smoke or odor is produced the next time the sauna heater is heated up you can start to use the sauna If smoke or odor is produced again leave the sauna cabin immediately and repeat the initial heating up process followed by ventilation Always check the sauna room before switching sauna heater on to be sure that there is no combustible things within the safety distances ...

Page 17: ...tse kylpyhuoneessa sijaitsevaan poistoilmaventtiiliin Tällöin saunan kynnysraon on oltava vähintään 5cm ja kylpyhuoneessa olisi suotavaa olla koneellinen ilmastointi Poistoilmaventtiilin tulee olla kaksi kertaa suurempi kuin tuloilmaventtiilin ERISTYS Saunassa tulee olla asianmukaiset eristykset seinissä katossa ja ovessa Mikäli saunassa on yksi neliömetri m eristämätöntä seinäpintaa esim lasiovi ...

Page 18: ... through a pipe from the floor going to a vent to the sauna ceiling or under the door to the washroom In this case the sill slot must be at least 5cm and it is recommended that there is mechanical ventilation in the washroom The size of the exhaust should be twice that of the inlet INSULATION The sauna must have proper insulation on the walls ceiling and door One square meter m of un insulated sur...

Page 19: ...uteet lattia katto ja seinät Älä käytä puupintojen pesuun ammoniakkia tai klooria sisältävää pesuainetta Huuhtele pesuaine pois kylmällä vedellä Tuuleta sauna hyvin Halutessasi voit käsitellä lauteet saunapinnoille tarkoitetulla suoja aineella Lue suoja aineen käyttöohjeet tarkasti pakkauksesta ennen tuotteen käyttämistä 9 9 Jos lauteet eivät puhdistu pesemällä hio lauteet kevyesti ja käsittele su...

Page 20: ...sh Wash sauna benches ceiling floor and walls Do not use detergent which includes ammonia or chlorine Rinse surfaces with cold water and ventilate sauna room well If needed protect wood surfaces with wood treatment oil Read carefully the instructions of wood treatment oil from product packaging 9 9 If sauna benches are not getting clean after washing sand the benches with sandpaper Protect benches...

Page 21: ... NI JA NS MALLIT Onko kiuas laitettu päälle ohjauskeskuksesta Onko tavoitelämpötila säädetty saunan lämpötilaa korkeammaksi Onko kiukaan pääkytkin päällä Ni malleissa kytkin sijaitsee kiukaan alaosassa ja Ns malleissa tehoyksikössä Ovatko kytkintaulun sulakkeet ehjät ja toiminnassa Sulakkeen laukeamisen syy tulee aina selvittää ennen kiukaan uudelleenkäyttöä Tarkista hehkuvatko kaikki vastukset ki...

Page 22: ...igher than the temperature inside the sauna room Is the main switch ON In Ni models main switch is located at the bottom of the heater and in NS models it is on the power control Are the switchboard fuses ON and unbroken If broken find out the reason before turning ON your heater Are all heating elements glowing red when the heater is ON Is the heater s heating power enough for the sauna room See ...

Page 23: ... 3 6 6 3 6 5 x 2 5 5 x 2 5 5 x 2 5 5 x 2 5 5 x 2 5 5 x 1 5 5 x 1 5 9 6 5 x 4 0 5 x 2 5 5 x 2 5 KIUAS MALLI KIUKAAN KOKO JÄNNITE KIVET OHJAUS SULAKE SAUNAN TILAVUUS V U O L U K I V E Ä Vastusten lukumäärä JOHDON POIKKIPINTA VASTUS TYYPPINUMERO LEVEYS SYVYYS KORKEUS kW erillinen erillinen erillinen erillinen erillinen erillinen erillinen erillinen SPAREPARTS 1 NIM Top Cover Stone 1 2 NIM Top Cover S...

Page 24: ... 21 SAV150 SAV200 HP23 002 HP23 003 HP24 001 HP25 001 HP23 005 HP23 004 HP24 002 HP25 002 HP23 006 HP23 007 HP02 001 HP23 003 HP24 003 HP25 003 HP23 008 HP03 002 SAV150 1 5kW HP03 003 SAV200 2 0kW HP03 004 HP23 012 HP03 005 HP04 003 HP04 002 HP01 008 HP01 021 HP01 066 HP04 007 ...

Page 25: ...www sawo com info sawo com Pidätämme oikeuden muutoksiin Subject to change without notice PX 4 NIM_ML_3P_FiEn_0120 ...

Reviews: