11
Part No. 001123, 16-m05-2018
Vuelift Planning Guide
Site Preparation (Round)
The following items MUST be completed prior to installation of the elevator.
Finished Floors
• Finished floors be installed at all landing levels.
230V Power (with Switched Disconnect)
• Permanent 230V, single-phase, 30-Ampere dedicated power to a lockable fused (cartridge
type) disconnect switch.
• Disconnect switch must be mounted in a location within line of sight of the elevator or
controller.
• 230V source must be run from the disconnect switch to a junction box in a discrete location at
the top of the elevator hoistway location.
• Disconnect must be installed according to all applicable local codes.
110V Power (with Switched Disconnect)
• Permanent 110V, single-phase, 15-Ampere dedicated power to a lockable, fused (cartridge
type) disconnect switch.
• Disconnect switch must be mounted near the 230V disconnect switch.
Telephone Works
• Telephone jack must be provided next to the electrical disconnects. This can be the common
house line in most jurisdictions. Please check with your local installer or building contractor for
code requirements.
Floor Built for Load
• Smooth level surface for installing the elevator, with floor load bearing capacity for the elevator
plus rated load. An exact specification can be provided by contacting Savaria.
Floor and Pit Cutouts Complete
• If a pit is to be used, a smooth, level surface of at least 4” must be provided. For pit depths
greater than 12”, contact Savaria to ensure proper equipment will be provided.
• It is recommended that any pit floor and walls be finished prior to installation. Pit floor and walls
are visible after elevator installation is completed.
• Hole in floor, or modified balcony rail as directed by drawings.
Check Floor to Floor Maximum and Minimum Distances
• 106” (2692 mm) minimum overhead distance from upper floor level to the underside of the
finished ceiling for standard cab configuration.
• 96” (2438 mm) minimum overhead distance from upper floor level to the underside of the
finished ceiling for modified short cab configuration.
Drywall and Painting
• All drywall and painting must be complete.
Summary of Contents for Vuelift
Page 5: ...5 Part No 001123 16 m05 2018 Vuelift Planning Guide Chapter 1 Round Elevator Acrylic ...
Page 14: ...14 Vuelift Planning Guide Part No 001123 16 m05 2018 Figure 1 Plan view round ...
Page 16: ...16 Vuelift Planning Guide Part No 001123 16 m05 2018 Figure 3 Balcony detail round ...
Page 17: ...17 Part No 001123 16 m05 2018 Vuelift Planning Guide Figure 4 Thru floor detail round ...
Page 18: ...18 Vuelift Planning Guide Part No 001123 16 m05 2018 Figure 5 Elevation view round ...
Page 19: ...19 Part No 001123 16 m05 2018 Vuelift Planning Guide Figure 6 Provisions by others round ...
Page 20: ...20 Vuelift Planning Guide Part No 001123 16 m05 2018 Figure 7 Pit cutout detail round ...
Page 33: ...33 Part No 001123 16 m05 2018 Vuelift Planning Guide Figure 10 Plan view octagonal type 1 ...