Orion Planning Guide

HOISTWAY AND PIT ELECTRICAL NOTES

o

A load bearing wall is required to sustain rail reactions. See page 18 for rail reactions.

o

Suggested hoistway pit 

fl

 oor construction consists of an 8“ (203 mm) concrete slab poured on a natural  or 

compacted soil with a minimum allowable bearing pressure of 1.0 KSF. 

o

The minimum compressive strength of the concrete at 28 days must be no less than 3000 PSI.
#5 reinforcing steel (grade 60) must be placed at the bottom of the slab in 2 traverse directions and at a 
spacing of 12“ (305 mm).

o

Hoistway pit 

fl

 oor to support a load of 10 kips (10,000 lbs)/44.48KN (includes impact).

o

120“(3048 mm)

 

overhead clearance

 required above the top landing 

fl

 oor with top prop 

(existing 

construction)

.

o

134” (3404 mm) overhead clearance

 required above the top landing 

fl

 oor without top prop 

(new 

construction)

.

o

14” (356 mm) minimum pit. (A clearance device is provided to attain required 36“ (914 mm) refuge 
space).

o

Hoistway sizes re

fl

 ect running and access clearances only. Consult your local AHJ to assure compliance with 

local codes.

o

Hoistway is required to be free of all pipes, wiring and obstructions not related to the operation of the 
elevator.

o

If a dedicated pit light is required by your local AHJ, please follow the guidelines below for accommodating 
this in your hoistway

8¼”

5”

Type 1 Cab

Approximate space available for 
a dedicated light with guard. We 
recommend mounting the light 
after the elevator doors have 
been installed to ensure adequate 

clearance.

GFI

9”

9” Clear Distance (from inside 

fi

 nished surface of hoistway to 

edge of electrical box).

The dedicated GFI outlet 

is approximately 24” up 

from the lower landing 

fi

 nished 

fl

 oor light switch 

mounted directly above.

Type 2 Cab

10”

5”

15¾”

9”

GFI

Summary of Contents for Orion

Page 1: ...uide Limited Use Limited Application Elevator Applicable Codes ASME A17 1 Section 5 2 CAN CSA B44 Section 5 2 ORION TM Part No 000682 15 m10 2015 2015 Savaria Corporation LIMITED USE LIMITED APPLICATION ELEVATOR ...

Page 2: ... TYPE 1 WITH 2 SPEED DOORS 14 ORION 42 X 60 TYPE 2 WITH 2 SPEED DOORS 15 ORION 48 X 54 TYPE 1 WITH SWING DOORS 16 ORION 48 X 54 TYPE 2 WITH SWING DOORS 17 LOADS ON BUILDING AND PIT LOADING 18 ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH DRYWALL CONSTRUCTION 19 ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH DRYWALL CONSTRUCTION 20 ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH MASONRY CONST...

Page 3: ...ber 14 2012 Revised July 9 2013 Revised August 19 2013 Revised October 21 2013 Revised November 29 2013 Revised March 12 2014 Revised October 21 2014 Revised November 5 2014 Revised January 13 2015 Revised January 29 2015 Revised February 4 2015 Revised February 19 2015 Revised March 10 2015 Revised September 24 2015 Revised October 15 2015 IMPORTANT NOTICE This Planning Guide provides nominal dim...

Page 4: ... Americans with Disabilities Act Requirements The Orion meets the requirements of the ADA Accessibility Guidelines as a means to provide public building access Design Assistance With over 30 years of experience Savaria has the expertise to provide solutions to practically every design challenge you face Please call our Customer Service Department for professional advice at 800 661 5112 or 905 791 ...

Page 5: ... directional indicator Emergency manual lowering stop key switch and alarm buttons Emergency battery back up for lighting alarm and emergency lowering Floor specific battery lowering Illuminated cab operating buttons Limited warranty covers the repair or replacement of any defective parts for a period of 36 months from date of shipment Magnetic floor selection stopping and re levelling Manual rese...

Page 6: ...e CAB TYPE SELECTION SHEET IMPORTANT Finished hoistway dimensions must include the drywall Determine the fire rating of the hoistway the type and layers of sheet rock and build only off the final shop drawings specific to your project Type 1 Type 2 Type 3 and 4 ...

Page 7: ...are D EK 300 Z o 30 wide x 36 deep work space required in front of the disconnects and the elevator controller o Machine room lighting shall be a minimum of 19 foot candles 204 lux at working surfaces The switch for the light must be within 18 of the strike side of the machine room door The light must be guarded to prevent accidental breakage or contact with the hot bulb The switch light wiring an...

Page 8: ...Part No 000682 15 m10 2015 Page 8 of 27 Orion Planning Guide MACHINE ROOM DIMENSIONS ...

Page 9: ... mm overhead clearance required above the top landing floor without top prop new construction o 14 356 mm minimum pit A clearance device is provided to attain required 36 914 mm refuge space o Hoistway sizes reflect running and access clearances only Consult your local AHJ to assure compliance with local codes o Hoistway is required to be free of all pipes wiring and obstructions not related to th...

Page 10: ...d motor wiring Controller Layout PLC Keyed Lock to Tank Yes Machine Room Required Yes Tank Capacity gal ltr 15 16 5 gal 57 63 ltr Max Dry Weight lbs kgs 147 lbs 55 kg Max Filled Weight lbs kgs 312 lbs 117 kg Operating Environment 50 F 80 F 10 C 27 C Operating Volume 57 dBA 1 2 6 0 4 6 3 9 3 0 2 0 5 7 2 5 1 6 1 PLC Controller Tank Controller Tank Features Hydraulic hose connection ports on either s...

Page 11: ... hoistway dimensions must include the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project Type 1 48 x 54 w 2 Speed Doors For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm For Masonry or Drywall Entrance Details refer to drawings on pages 19 22 ...

Page 12: ...the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm For Masonry or Drywall Entrance Details refer to drawings on pages 19 22 Type 2 48 x 54 w 2 Speed Doors ...

Page 13: ...mensions must include the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Type 3 or 4 Type 3 4 51 x 51 w 2 Speed Doors For Masonry or Drywall Entrance Details refer to drawings on pages 19 22 ...

Page 14: ...ic Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Finished hoistway dimensions must include the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Masonry or Drywall Entrance Details refer to drawings on pages 19 22 Type 1 42 x 60 w 2 Speed Doors ...

Page 15: ...wall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Type 2 For Masonry or Drywall Entrance Details refer to drawings on pages 19 22 Type 2 42 x 60 w 2 Speed Doors ...

Page 16: ...ht Hand applications Type 1 Finished hoistway dimensions must include the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Type 1 48 x 54 w Swing Doors ...

Page 17: ...hed hoistway dimensions must include the drywall where applicable Determine the fire rating of the hoistway the type and layers of sheet rock Build only from shop drawings specific to your project For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Type 2 48 x 54 w Swing Doors ...

Page 18: ...idered in hoistway design 720 lbf 260 lbf 1200 lbf 300 lbf 2400 lbf 400 lbf Seismic zones 0 and 1 Seismic zone 2 Seismic zone 3 or greater Rails Support Wall Orientation R3 Condition I when fully loaded car hits buffer bumper R4 Condition II when safeties engage on rails with 110 loaded car at governor tripping speed R5 Condition III normal running with 1 2 times impact for starting and stopping j...

Page 19: ...Part No 000682 15 m10 2015 Page 19 of 27 Orion Planning Guide ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH DRYWALL CONSTRUCTION ...

Page 20: ...0682 15 m10 2015 Page 20 of 27 Orion Planning Guide ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH DRYWALL CONSTRUCTION Contractor please note Grouting at the sill may be required after the door frames are set ...

Page 21: ...Part No 000682 15 m10 2015 Page 21 of 27 Orion Planning Guide ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH MASONRY CONSTRUCTION ...

Page 22: ...0682 15 m10 2015 Page 22 of 27 Orion Planning Guide ENTRANCE MOUNTING DETAILS FOR 2 SPEED DOORS WITH MASONRY CONSTRUCTION Contractor please note Grouting at the sill may be required after the door frames are set ...

Page 23: ...door centerline 2 Door panels and frame are primed for painting Door Frame Elevation 80 Clear Inside 82 2 Spd Frame 88 Lintel 52 88 4 min to 8 max Measured from Top of Finished Floor 2 Speed Door Rough Opening For Swing Doors the rough opening is 46 Wide For Metric Equivalents Multiply inches times 25 4 for mm Example 40 25 x 25 4 1022 35 mm Rails ands Sling in Hoistway ...

Page 24: ...0682 15 m10 2015 Page 24 of 27 Orion Planning Guide PIT AND OVERHEAD CLEARANCE DETAILS A minimum pit depth of 14 is required 14 Pit Depth 120 Overhead for Existing Constructions 134 Overhead for New Constructions ...

Page 25: ...or frames are not designed to support overhead wall loads ELECTRICAL o Power supply with a lockable fused disconnect and auxiliary contact to brake the battery feed or circuit breakers with a 3 pole breaker for battery feed required in compliance with electrical code contact your Savaria dealer or refer to the table below for OEM part numbers o Permanent power of 240V single phase 40 Amp or 208V t...

Page 26: ...lectromechanical interlocks 5 Handrail specify Stainless steel or brass 6 Pit Switch 7 Car top inspection station with UP and DOWN test switches emergency stop light outlet 8 Automatic homing to the lowest floor optional 9 Slack rope safety 10 Anti creep device 11 Overspeed governor may not be required consult AHJ 12 Dual direction leveling Upper and lower terminal limit Pump run timer Pit clearan...

Page 27: ...tlet inside the hoistway 3 Telephone circuit in the machine area PART 3 EXECUTION 3 1 ACCEPTABLE INSTALLERS A Installers shall be experienced in performing work of this section who have specialized in work comparable to that required for this project B Installers shall be certified and trained by the manufacturer 3 2 EXAMINATION A Use field dimensions and approved manufacturer s shop drawings to e...

Page 28: ...2 Walker Drive Brampton ON Canada L6T 5E1 Phone 905 791 5555 Fax 905 791 2222 Sales 800 661 5112 www savaria com ...

Reviews: