Multistat Smart Thermostat Deployment Guide (CLI-W210x/W200x)
17 of 21
45 Perseverance Way, Hyannis MA 02601
009-1959-00 | 200723
| 508.683.2500
Select Number of Stages
SKIP
NEXT
BACK
1
2
HEAT STAGES
1
2
COOL STAGES
Select Auxiliary Equipment
SKIP
NEXT
BACK
NONE
HUMIDIFIER
DEHUMIDIFIER
Select Indoor Sensor
SKIP
NEXT
BACK
Internal
RS1
RS2
fe-0021b10000a67
HEAT/COOL STAGES
- Select the number of
heating and /or cooling stages the thermostat
will control. Heat and cool stages are
supported in Electric, Gas, and Heat Pump
type systems.
Radiant type systems require a different set of
values to configure. The Radiant type system is
shown to the right
Select when either a humidifier or dehumidifier
is controlled by the thermostat. Wiring
diagrams are available in the
section above.
Select which sensor's temperature data to display on
the thermostat's main screen. Since the temperature
displayed is the indoor temperature, the sensor will
typically be mounted indoors, near the thermostat.
RS1 or RS2
- Temperature sensor wired to either the
RS1 or RS2 terminal in the thermostat's mounting plate.
The sensor connected to these ports must be a 10K
thermistor type sensor.
fe-0021b10000a67
- Select when a 1-Wire smart sensor
like the CLI-THFM1 provides the indoor temperature.
The label on the button is the UID of the sensor.
Internal
- Temperature sensor mounted inside the
thermostat. Select Internal when no other sensors are
installed.
FLOOR HYSTERESIS
- The number of degrees the
temperature of the floor must fall from the setting in the
max slab temperature field before the heat can switch
back on. Range = 0-10° F (0-6° C).
MAX SLAB TEMPERATURE
- The temperature set is the
maximum temperature the floor can reach before the
heating system is told to stop providing heat to avoid
the floor from getting too hot. A slab type sensor must
be mounted in the floor for this feature to function
accurately. Ideally, the max slab temperature should
never be reached. The Max Slab Temperature function is
simply a safety feature.
SLAB TEMP SENSOR
- Select which connection on
the thermostat's backing plate will connect to the slab
sensor. Select NONE when no sensor is installed.
What is Hysteresis?
- In radiant systems, hysteresis keeps the HVAC system from
switching on and off each time the temperature at the slab sensor reaches the
thermostats max slab temperature setpoint, which puts less wear on the HVAC
system.
Radiant Floor Settings
FLOOR HYSTERESIS
SLAB TEMP SENSOR
MAX SLAB TEMPERATURE
SKIP
NEXT
BACK
SKIP
5°
80°
None
RS1
RS2