background image

TRA 410, 421

17/19

P100015830 B

Description of operation

Symbol

Procedure

Display the status of the output signal.

Factory setting: 1 

When the output for thermal actuators is active, the heating or 

cooling symbol flashes slowly. If this output is inactive, the symbol 

is displayed continuously.

0 = deactivated

1 = activated

Set the direction of operation of the room controller (NC or NO).

Factory setting: 0

The direction of operation of the room controller and the connected 

thermal actuators can be defined.

0 = normally closed (NC)

1 = normally open (NO)

Set the frost-protection temperature.

Factory setting: 5 °C

Activates the frost-protection facility when the temperature falls be-

low the set temperature.

Setting range: 5 °C to 10 °C.

Activate the “optimised time programme” function.

Factory setting: 0

If the “optimised time programme” function is activated, the set-

point is reached at the defined time. In order to reach the setpoint, 

heating or cooling mode is initiated in good time ahead of the de-

fined time.

0 = deactivated

1 = activated

Set the cycle time for the valve protection facility.

Factory setting: 14 days

Prevents the plug from sticking inside the valve.

Setting range: 0 to 28 days

Determining a pilot clock output.

Factory setting: 0

0 =  

Pilot clock output active by time program

1 =  

Pilot clock output is inactive according to time program

 

Pilot clock output active when operating mode “ECO” is slected;

 

Pilot clock output active when operating mode “Off” is selected

Note: If parameter P230 = 1, the time program for local reduced 

temperature can be used.

Defining the actuation duration while the valve protection facility 

is active.

Factory setting: 5 minutes

The actuation time can be optimised depending on the running 

time of the thermal actuator.

Setting range: 0 to 10 minutes.

Change the service code for the service menu.

Factory setting: 1234

Note: In order to avoid unwanted access to the service parameters, 

we recommend that the service code be changed by the installer 

and documented securely.

The service code can be reset - see the settings in “Reset to fac-

tory settings”.

Summary of Contents for TRA 410

Page 1: ...ECC room thermostat TRA 410 TRA 421 Technical manual...

Page 2: ...2 19 TRA 410 421 P100015830 B...

Page 3: ...Liability limitation 6 2 3 Intended use 6 3 Setting the setpoint temperature 7 4 Functions settings parameterisation 8 5 Connection diagrams 9 6 Dimension drawing 10 7 Overview of display 11 8 Descrip...

Page 4: ...4 19 TRA 410 421 P100015830 B...

Page 5: ...l when it is dis connected from the power supply Only use the device when it is in a technically perfect condition Adhere to the ambient conditions specified in the fitting instructions 1 1 Meaning of...

Page 6: ...ctions Failure to observe the operating instructions Improper usage Use of untrained staff Unauthorised modifications Technical changes In all other cases the obligations agreed to in the supply contr...

Page 7: ...the setpoint temperature The setpoint temperature is set by turning the rotary knob to the left or the right 1 Turn the rotary knob to the LEFT The temperature is decreased Or 1 Turn the rotary knob t...

Page 8: ...ple operation and settings Standard display In the standard display all room temperature controllers show the current actual temperature and the active functions The TRA421 also has a clock function O...

Page 9: ...TRA410F210 TRA410F212 2 pt NTC 230 V 230 V L N 1 2 1 2 1 2 1 2 a b c d 2 pt NTC 24 V LS LS MM 1 2 1 2 1 2 1 2 a b c d TRA421F210 TRA421F212 2 pt NTC 230 V L L CO N NTC 22k out N 230 V 1 2 1 2 1 2 1 2...

Page 10: ...10 19 P100015830 B TRA 410 421 Dimension drawing 6 Dimension drawing...

Page 11: ...0 B Overview of display 7 Overview of display 1 2 1Display 2Rotary knob with turning and pressing mechanism TRA 410 TRA 421 Symbol Description P P Operating modes P P Settings P Parameters P P Heating...

Page 12: ...ale for time pro gramme one unit one hour P P Current temperature setpoint temperature P P C Correction of effect of wall temperature P P Celsius temperature unit P Fahrenheit temperature unit P P Min...

Page 13: ...nfirm the selection Note Decrease via the room thermostat or an external signal or time programme Both cannot be activated TRA 410 Decrease of 2 C Note When the decrease is selected the Decrease input...

Page 14: ...rm the entry P Set the setback temperature in the Cooling ECO mode Factory setting 23 C Press to confirm the selection Turn to set the setpoint temperature that you want Press to confirm the entry P S...

Page 15: ...he button to select the finishing point Press to confirm Turn to the right to call up the next time programme Turn to the left BACK to leave the time programme P P Correction of effect of wall tempera...

Page 16: ...k is activated and the operating mode is set to cooling the heating mode is also inactive Protects the locking of the operation with a code Factory setting 0 0 deactivated 1 activated Note The locking...

Page 17: ...ling mode is initiated in good time ahead of the de fined time 0 deactivated 1 activated Set the cycle time for the valve protection facility Factory setting 14 days Prevents the plug from sticking in...

Page 18: ...f f No external sensor present f f External sensor does not correspond to specifications f f Deactivate the external sensor in parameter setting 040 f f Check the external sensor and replace if necess...

Page 19: ...Fr Sauter AG Im Surinam 55 CH 4016 Basel Tel 41 61 695 55 55 Fax 41 61 695 55 10 www sauter controls com info sauter controls com Printed in Switzerland...

Reviews: