Sauter flexotron®800
ventilation
Configuration
P100012082
82
16.2
Control function
Control function
Mode:
Supply air control
There are six different control functions to choose from:
1. Supply air control.
2. Outdoor-temperature compensated supply air control.
3. Cascaded room temperature control
4. Cascade connected extract air temperature control.
5. Outdoor temperature dependent switching between outdoor compensated
supply air temperature control and room temperature control
6. Outdoor-temperature controlled switching between Outdoor-temperature
compensated supply air control and Cascade connected extract air
temperature control.
For detailed description of the control modes, see section 5.1.1 Control modes.
In control modes five and six, there is a submenu for setting of the change-over outdoor
temperature.
Outdoor temp for
control mode change
13°C
16.3
Fan control
Fan control
1-speed
Choose between "Single-speed", "Two-speed", "Pressure control", "Flow control",
"Frequency manual" (fixed output), "Frequency external control", "SAF with EAF slave",
or "SAF with EAF flow control".
For detailed description of fan control alternatives, see section 5.4 Fan control.
Flow control
If flow control has been configured, there is a submenu for setting of calculation
parameters for conversion of pressure to flow. There are two menus, one for "SAF" and
one for "EAF".
SAF flow control
factors
K-constant: 100
X-constant: 0.50
For more detailed description, see the section Air flow control under 5.4.1 Pressure
control.