flexotron®400 - RDT405
Configuration
P100012100
21
8
Configuration
All the configuration menus lie in the 10-seconds level. This level is accessed
from the Base Display by pressing and holding the encoder button for 10
seconds. The display must light up before the button is depressed. It lights up
when the button is touched.
There are numerous configuration menus covering all available options and
combinations.
In some cases, making a certain choice in one menu will mean that you will only
see certain other menus. For example, the menu for setting the damper minimum
limit is only shown if you have configured AO2 to be a damper control output.
8.1 Menus 1.0
– 5.0
In the first set of configuration menus you choose which of the five control modes
you wish to run. The upper text row, the lower text row number and the first digit
in the menu-number show which control mode is at hand.
1. Temperature control 2. CO2-control
3. General control
4. Pressure control
5. Pressure control with outdoor compensation
8.1.1
Menu X.1
Output signals (Control mode 1)
Transmitter range (Control modes 2, 3, 4 and 5)
Control mode 1.
For temperature control there is a choice of 8 different output signal
combinations. Select one fitting the application on hand.
Output
Graphic
AO1
/
AO2
symbol
symbol
1. Heating
/
-
\
2. Cooling
/
-
/
3. Heating
/
Cooling
\ /
4. Heating
/
Heating
\ \
5. Cooling
/
Cooling
/ /
6. Heating
/
Damper
\ /
7. Cooling
/
Damper
\ /
8. Change-over
/
-
In alternative 4, Heating-Heating AO2 will be activated first on increasing heat
demand.
In alternative 5, Cooling-Cooling AO2 will be activated first on increasing cooling
cemand.
In alternative 6, Heating-Damper, at temperatures above the setpoint the damper
on AO2 will be fully open. On increasing heating demand, the damper on AO2