modu600-LO
Functionality and operation
D100408262
R: 02, V: 01
35/60
Output configured
Output not configured
The
and
buttons can be used to set the
focus to the value field, and the button puts it into the
edit mode.
After focussing, the value can be changed using the
and
buttons.
A value change can be validated or rejected using
the
and
buttons.
The
button appears if the value has been
overridden manually. After you focus on this button
and validate using the
button, the AUTO mode
is reset.
Analogue outputs can be configured as:
▪
0
–10 V Out
▪
2
–10 V Out
The selection appears after focussing and
validation. Select using the
and
buttons
and validate
or cancel
.
Ranges of the analogue values
Nominal
0
Max. (nom.)
Peak
0(2) … 10 V
0(2) V
10 V
11.5 V
0(4) … 20 mA
0(4) mA
20 mA
22 mA
200
… 2500
100
2.5 k
2700
Table 3 Nominal and effective ranges of the analogue signals
Representation of the set unit in the BACnet object
BACnet Analogue objects can be configured with a unit, e.g: °C, km, %, etc... The
conversion of the measured value in V, mA or
into the corresponding value with the
unit set in the associated BACnet object takes place in the automation station. This
scaling is usually linear, with the exception of the Ni1000 and Pt1000 which are
converted with a curve. As long as the connection to the AS is present, this calculated
Summary of Contents for EY6LO00F001
Page 1: ...modu600 LO Operating instructions D100408262 ...
Page 2: ......
Page 3: ...modu600 LO D100408262 R 02 V 01 3 60 modu600 LO Operating instructions D100408262 ...
Page 16: ...modu600 LO Hardware description 16 60 R 02 V 01 D100408262 Installation instructions ...
Page 52: ...modu600 LO FAQ 52 60 R 02 V 01 D100408262 ...
Page 59: ...modu600 LO Annexe D100408262 R 02 V 01 59 60 ꞋꞌꞍ fifl ...