background image

3/6

www.sauter-controls.com

3.

Press the input knob

4.

Turn the input knob, show code

5.

Press the input knob; the fi rst SERVice 
parameter appears

  

The commissioning level provides access to the main 

 

 

SERVice parameters. These are shown in italics in the 

 

 

following list (cf. 3.6).

View/change service parameters

3.4.1 

1.

°C

°C

Turn the input knob; select SERVice 
parameter

2.

Press the input knob; the value of the 
parameter appears

3.

Turn the input knob; the value of the 
parameter changes

4.

Press the input knob to confi rm the new 
value

Press the ESC key to cancel the operation. The value is not accepted 
unless it was already confi rmed beforehand. The parameters in the 
communication level can be viewed/amended in the same manner.

Access to SERVice mode

3.4.2 

In the SERVice position, it is possible to choose between 
commissioning, SERVice and communication levels. After pressing 
the input knob at the relevant display, proceed as described for the 
commissioning mode.

1.

Set rotary switch to 

2.

Press the input knob

For further steps, see Section 3.4.1 and 3.4.2

Floor drying

3.5 

SERVice parameter SP60 (for second heating circuit: SP260, cf. 3.6) 
is used to activate a fl oor drying process (functional heating or screed 
curing). After the fl oor drying has been completed, the controller 
operates regularly according to the switch position and the switching 
commands. SERVice parameter SP60 (or SP260) then shows ‚9‘.

Extract from list of SERVice parameters

3.6 

For a detailed description, see document 7010042.

No.

Explanation

SP01

X.xx

Software version (read only)

SP02

-

Show device status (0 = OK, >0 = error has occurred)

SP03

Logbook (read only)

SP04

0

Software reset 
0 = no reset; 1 = default SE + CP; 2 = default switching 
commands; 3 = default SE + CP + switching commands

SP05

0

Manual mode
0 = not enabled; 1 = enabled

SP06

1

Control model
1 = one regulating valve, primary, re-adjusted HC sec.
2 = one regulating valve, secondary, re-adjusted HC +DW 
sec. 
3 = two regulating valves, primary, for HC/HC +DW 
4 = two re-adjusted circuits (2 x HC)
5 = two re-adjusted circuits (1 x HC, 1 x DW) sec.
6 = two re-adjusted circuits (1 x HC, 1 x DW with HC)
7 = direct control of DW and HC, plus one re-adjusted HC
8 = two regulating valves (1 primary for HC, 1 for direct DW 
charge w/o mixing control)
For details, see ‹Application› sheet.

No.

Explanation

SP07

0

Effect of binary input (terminal 21, 22) on HC1
0 = No infl uence on HC1
1 = HC in standby mode if contacts are closed
2 = HC in reduced mode if contacts are closed
3 = HC in nominal mode if contacts are closed
4 = pulse input for metering
5 = seepage limitation
6 = input for alarm

SP08

0

Measure room temperature for HC1
0 = no room temperature measurement; 1 = connect room 
sensor; 2 = connect EGS52/15 or EGT333 with room 
sensor; 3 = connect EGS52/15 or EGT333 without room 
sensor; 4 = second fl ow sensor for domestic water

SP09

0

Transmit room temperature for HC1
0=not active; 1=active if T

Ri

 > T

Rs

; 2= active if T

Ri

 < T

Rs

; 3= 

active if T

Ri

 <> T

Rs

SP10

20

Sampling time (in minutes) for T

R1

 when transmitted

SP11

0

Adjust room temperature T

R1

SP12

0

Adjust outside temperature T

A

SP13

0

RMeasure return temperature T

RF1

0 = not active; 1 = max. limitation of T

RF

; 2 = maintain T

RF

SP14

0

Adjust return temperature T

RF1

SP15

40

P-band for PI-controller, control unit 1

SP16

240

Integral action time for PI-controller, control unit 1

SP17

120

Valve running time for fi rst control unit

SP18

5

Minimum limitation T

F

 for HC1 in °C

SP19

75

Maximum limitation T

F

 for HC1 in °C

SP20

90

Upper limit of max. limitation for T

RF

 for HC1,2 in °C

SP21

90

Lower limit of max. limitation for T

RF

 for HC1,2 in °C

SP22

0

T

A

, at which the fl oating part of the limiting function of T 

begins for HC1,2

SP23

1.0

Slope of limiting function for T

RF

 for HC1,2

SP24

90

Limit value for T

RF

 for charge of drinking water in °C

SP25

5

Level of intervention for control of control unit 1 when limit 
value for T

RF1

 is breached

SP26

no

Limit lmp/min for max. through fl ow/output of heating and 
DW

SP27

no

Limit lmp/min for max. through fl ow/output of heating only

SP28

no

Limit lmp/min for max. through fl ow/output of DW only

SP29

0

Level of intervention for T

F1

 in K/min when limit is breached 

for through fl ow/output

SP30

no

Limit lmp/min for min. through fl ow/output

SP31

1

Functions for domestic water:
0 = no treatment of domestic water
1 = treatment of domestic water, 1 sensor
2 = treatment of domestic water, 2 sensors
3 = treatment of domestic water with through fl ow control

SP32

60

Max. setpoint for DW in °C

SP33

5

MOD 1,2: switching difference DW in K

SP34

70

Max. setpoint for increased DW temperature

SP35

10

Setpoint boost for DW in K

SP36

-30

T

A

 limit value for charging domestic water in °C

T

A

 < limit value 

 parallel mode 

T

A

 > limit value 

→ 

domestic water with priority

SP37

4

Integral action time for charge pump for DW in min

SP38

1.4

Slope of heating characteristic HC1

SP39

0.0

Portion of external heat in K

SP40

10

Setpoint boost when request for re-adjusted circuit or via 
device bus in K

SP41

15

Heating limit in °C

SP42

21

Measurement of outside temperature for heating limit
0 = unattenuated; <>0 = time constant for attenuation in 
hours

SP43

-16

Design temperature in °C

SP44

2

After-run factor for heating pump
(× valve›s running time)

SP45

1

Frost-protection function
0= not enabled; 1 = enabled

SP46

0

Confi gurable output
0 = no function; 1 = pilot-timer function; 2 = second charge 
pump; 3 = RPM change-over for pump, HC1; 4 = RPM 
change-over for pump, HC2; 5 = collective-alarm notice; 
6 = circulation pump; 7 = heat requirement

SP47

0

Anti-jamming facility for pumps
0 = not enabled; 1 = enabled

SP48

25.10

Summertime/wintertime change-over

SP49

25.03

Wintertime/summertime change-over P55 = P56 denotes 
no change-over

SP50

0

Optimisation for HC1
0 = not enabled; 1 = enabled

Summary of Contents for equitherm EQJW245

Page 1: ... is active Sensor is faulty Heating pump for HC1 HC2 is switched on Control unit 1 2 is opened c or closed d Setpoint temperature Flashing actual temperature is displayed Flow temperature Outside temperature Room temperature Return temperature Charge temperature of domestic water Domestic water temperature 1 Domestic water temperature 2 Display refers to HC1 or HC2 Controller is in summer mode Cal...

Page 2: ...r will alternate 3 Press input knob year number flashes 4 Turn input knob to change year 5 Press input knob to confirm year and view day month 6 Turn input knob to set date 7 Press input knob to confirm new date 1 The middle and bottom rotary switches should be set at one of the positions for an operating mode Manual mode 3 3 First enable manual mode in SERVice mode cf 3 6 by setting SP 05 to 1 Th...

Page 3: ...room sensor 4 second flow sensor for domestic water SP09 0 Transmit room temperature for HC1 0 not active 1 active if TRi TRs 2 active if TRi TRs 3 active if TRi TRs SP10 20 Sampling time in minutes for TR1 when transmitted SP11 0 Adjust room temperature TR1 SP12 0 Adjust outside temperature TA SP13 0 RMeasure return temperature TRF1 0 not active 1 max limitation of TRF 2 maintain TRF SP14 0 Adjus...

Page 4: ...via modem telephone number of the control station CP07 SMS via modem telephone number of the provider No Explanation CP08 SMS via modem telephone number of the mobile phone CP09 0 Device bus time synchronisation 0 not active 1 active CP10 0 Device bus send outside temperature 0 not active 1 active CP11 0 Device bus receive outside temperature 0 not active 1 active CP12 0 Device bus send heat requi...

Page 5: ...mmand 4 6 4 Show the switching command as described in the section entitled View switching commands e g 1 Press input knob the switching command is called up 2 Turn the input knob select whether to delete Clr or change SEt the switching command 3 Press input knob the selection is confirmed If the switching command was deleted the next switching command will be shown 4 To make a change proceed as d...

Page 6: ...temperature START daily 0 00 hours Call up weekly switching programme 4 11 1 domestic water 1 1x Set lower rotary knob to 2 Turn input knob select day of week 1 Monday 2 Tuesday 1 7 daily 3 Press the input knob the first switching command is shown View switching commands 4 11 2 Turn the input knob each switching command is shown An empty switching command is shown as _ _ _ _ Enter switching comman...

Reviews: