AVM 104S...115S

  51.362/5

Sauter Components

Coding switch for characteristics selection

Split-range unit. Accessory 0361529 001
The starting point U

0

 and the control span 

Δ

U can be set using the potentiometer. This makes it possi-

ble to activate several regulating units in sequence or in cascade using the controller’s control signal.
The input signal (partial range) is amplified into an output signal of 0...10V. This accessory cannot be
fitted in the drive. but should be located externally in an electric distribution box.

CASE Drives PC Tool, Accessory 0372462 001
CASE Drives enables all the actuator's parameters to be set and viewed on site. Connection is via a
serial port on the PC (laptop) and a socket on the actuator. The set comprises: software including
installation and operating instruction, fitting instructions, connectors, cable (1,2 metres in length) and
an interface converter for the PC. The application is designed for commissioning and service techni-
cians and for experienced users.
The last setting (i.e. whether with coding switch or CASE Drives) has priority. This setting is active
when the valve's running time or characteristic is changed via the coding switch. To ensure that the
settings with CASE Drives cannot be overwritten, the coding switch should be removed before setting
values through CASE Drives (special tool included).

7151362003  03

On

Off

Signal

Signal

v

Signal

v

Signal

Signal

v

Signal

Signal

v

Signal

v

= %

x

2

lin

= %

lin

v

v

v

v

v

Signal

Signal

On

Off

On

Off

On

Off

On

Off

B10705

1   2   3    

1   2   3    

1   2   3    

1   2   3    

1   2   3    

Stroke

Stroke

Stroke

Stroke

Stroke

Desired

character.

curve

Switch coding

Characteristic
curve for valve

Characteristic
curve for drive

Effective on valve

Stroke

Stroke

Stroke

Stroke

Eq

u

a

l

pe

rc

e

n

ta

ge

Q

uad

ra

ti

c

Li

near

E

qua

l

pe

rc

en

ta

g

e

Li

near

= factory setting

Stroke

AVM 115S 

Summary of Contents for AVM Series

Page 1: ... Switching range Xsh 200 mV Power supply 24V 20 50 60 Hz Protection horizontal IP 54 as per EN 60529 24V 2 20 10 Protection class III as per IEC 60730 Power consumption AVM 105S F132 4 8 W 8 5 VA Response time 1 200 ms AVM 115S F132 4 9 W 8 7 VA Wiring diagram A09673 Max media temperature 100 C Dimension drawing M09743 Permissible amb temp 10 55 C Fitting instructions 1 4S MV 505790 Ambient humidi...

Page 2: ...own wires In the end positions on hitting a stop in the valve or reaching the maximum stroke or in the event of an overload the electronic motor cut off responds no end switches The direction of the stroke can be changed by swapping the power supply wires over BN BK The unused red and grey wires should not be connected nor should they come into contact with other wires We recommend that you insula...

Page 3: ...g AVM 104 S 7 5 s 60 s 2 15 s 120 s 4 B10700 On Off On Off On Off On Off 1 2 3 1 2 3 1 2 3 Run time per mm Switch coding Run time for 8 mm stroke factory setting AVM 114S On Off Signal Signal v Signal v Signal v lin v v v Signal Signal On Off On Off B10701 1 2 3 1 2 3 1 2 3 Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve...

Page 4: ...me per mm Switch coding Run time for 8 mm stroke factory setting AVM 115S On Off v v v lin lin v v v On Off On Off B10704 1 2 3 1 2 3 1 2 3 Signal Signal Signal Signal Signal Signal Stroke Stroke Stroke Desired character curve Switch coding Characteristic curve for valve Characteristic curve for drive Effective on valve Stroke Stroke Equal percentage Linear Linear factory setting Stroke AVM 105S A...

Page 5: ...ing instructions connectors cable 1 2 metres in length and an interface converter for the PC The application is designed for commissioning and service techni cians and for experienced users The last setting i e whether with coding switch or CASE Drives has priority This setting is active when the valve s running time or characteristic is changed via the coding switch To ensure that the settings wi...

Page 6: ...via an opening with black lid in the housing cover The auxiliary contacts should be screwed onto the drive s top cover Before the mechanical connection can be established the indicator knob should be removed A new indicator is then visible on the lid of the auxiliary contacts N B The housing should not be opened Fitting outdoors If the devices are fitted outdoors we recommend that additional measu...

Page 7: ...AVM 104S 115S 51 362 7 Sauter Components Wiring diagram 7151362003 03 RD red BN brown BK black BU blue GY grey A10450 ...

Page 8: ...inal numbers denotes a decimal point Fr Sauter AG CH 4016 Basle 7151362003 03 372145 001 A09782 RD BN BK A10183 RD BN BK GN GY VT 372145 002 372273 M10203 Ø33 Ø26 7 SW30 Ø33 Ø26 5 8 10 10 4 24 15 5 3 2 2 5 Ø8 0372249 001 Ø42 5 15 60 Ø33 Ø8 3 2 10 2 5 55 8 Ø16 Z10214 43 5 35 M09743b 122 107 1 70 46 5 23 5 126 7 63 45 6 32 372145 372286 MM 01 02 03 ...

Reviews: