Page
39
of
45
BACNET
OBJECT
ID
BACNET OBJECT NAME
READ/
WRITE
MODBUS
ID
NOTE
zero
calibration
BV8
BV-8
Internal Use
-
-
C8
BV9
BV-9
Internal Use
-
-
C9
BV10
No Airflow in
main duct
Airflow =0, No Airflow =1
-
R
C10
BV11
Need low er
temp. air for
AHU
No =0,Yes=1
-
R
C11
BV12
Alarm for 90%
of the airf low
achieve for
more
than
300 Sec
–
Cooling
Mode
No =0,Yes=1
-
R
C12
BV13
Alarm for 90%
of the airf low
achieve for
more
than
300 Sec
–
Heating
Mode
No =0,Yes=1
-
R
C13
BV14
BV-14
Internal Use
-
-
C14
BV15
BV-15
Internal Use
-
-
C15
BV16
BV-16
Internal Use
-
-
C16
BV17
BV-17
Internal Use
-
-
C17
BV18
BV-18
Internal Use
-
-
C18
-
BV19
BV-19
Internal Use
-
-
C19
-
BV20
Alarm icon
No =0,Yes=1
0 RW
C20
(HMI)
-
BV21
Lock icon
No =0,Yes=1
0 R
C21
(HMI)
-
BV22
Valve icon
No =0,Yes=1
0 RW
C22
(HMI)
-
BV23
Cooling icon No =0,Yes=1
1 R
C23
(HMI)
-