COMMISSIONING

• Set boiler thermostat to maximum and check
that any external controls are calling for heat.
• Check that the reading on the gauge matches
that given in '

Technical Data

' for the type of gas

being used.
• Adjust the range rating adjuster screw as neces-
sary to obtain the desired input.
• Shut down boiler.
• Remove pressure gauge, tighten up test point
screws and check for gas soundness.
• Using a ball point pen, clearly indicate on the
data label the input the boiler is set to.

Note

: This adjustment does not affect the domes-

tic hot water output.
If measured burner pressure differs greatly from the
given figure, check the gas inlet pressure as follows:
• Shut down boiler.
• Remove screw from inlet test point on the side of
the gas valve, 

see diagram 15

.

• Connect a suitable pressure gauge.
• Start boiler as described in '

Instructions for Use

'.

• Check that the inlet pressure reading matches
that given in '

Technical Data

' for the type of gas

being used.

Reg 014

Diagram 17

• Shut down boiler.
• Remove pressure gauge, tighten up test point
screws and check for gas soundness.
• If the gas pressure is incorrect, refer to the Fault
Finding section in '

Servicing Instructions

'.

• If the inlet pressure is below that given, the gas
supply pipework/meter must be checked and any
fault corrected.
• In the case of an LPG installation, check the stor-
age tank or cylinder, regulator and pipework.

OPERATING SAFETY DEVICES

Important notice: 

A central heating system cannot

operate satisfactorily unless it is properly filled with
water and unless the air initially contained in the
piping systems has been properly bled off. If these
conditions are not satisfied, air noise will occur
within the system.

Air in the heating system

Persistent air in the heating system may indicate
leaks in the system or corrosion taking place. Call
your Installation/Servicing company.

Overheat safety

In the event of a problem, the overheat safety
devices cause safety shutdown of the boiler. If this
happens, call your Installation/Servicing company.

The 

THELIA 30 E  

boiler has a built in  frost protection

device that protects the boiler from freezing. If the
boiler is to be left and there is a risk of frost, ensure
that the gas and electrical supplies are left con-
nected and that the OFF/Summer/Winter switch is
left in the'Summer' or 'Winter' position.The frost pro-
tection device will light the boiler when the tem-
perature of the boiler water falls below 6

°

C. When

the temperature reaches 16

°

C, the boiler stops.

Note: 

This device works irrespective of any room

thermostat setting and only protects the boiler. Al-
ways ensure that adequate frost protection is given
to the entire system where necessary.

Gas leak or fault

If a gas leak or fault exists or is suspected, turn the
boiler off and consult the local gas undertaking or
your installation/servicing company.

In case of power supply failure

The boiler no longer operates.
As soon as power supply is restored, the boiler will
be automatically restarted.

Air flow rate safety device

If an obstruction, even partial, of the flue occurs,
for any reason whatsoever, the built in safety sys-
tem of the boiler will turn the boiler OFF and the
fan will continue to run.
The boiler will be ready to operate when the fault
has been cleared.

In case of loss of water in the system
CAUTION

. The boiler is installed as part of a sealed

system which must only be
drained and filled by a com-
petent person.
If the pressure shown on the
pressure gauge is less than 1
bar or if the red loss of water
warning light is ON, the sys-
tem
must be filled up immediately. Call your Installation/
Servicing company.

Summary of Contents for Thelia 30 E

Page 1: ...1 THIS IS A CAT II 2H3 APPLIANCE 01773 828100 I N W A R R A N T Y T E C H N I C A L H E L P L I N E 01773 828400 THELIA 30 E ...

Page 2: ...INSTRUCTIONS THELIA 30 E Note The boiler serial number is marked on the label attached to the top of the inner bulkhead Refer to the Introduction section page 3 for a description of the basic functions of the boiler The Users section describes how to safely operate the boiler Mandatory warning for CEE countries Warning This appliance was designed approved and inspected to meet the requirements of ...

Page 3: ...d on the outside wall face The installation must be carried out by a compe tent person in accordance with the relevant re quirements of The Building Regulations The Water Byelaws The Building Standards Scotland Regu lations and any applicable local regulations These instructions should be carefully followed for the safe and economical use of your boiler Ancillary equipment A range of flue accessor...

Page 4: ...m 1 To obtain domestic hot water open a hot water tap Hot water always has priority over central heating DRAINING Setting to WINTER mode Heating and hot water Turn the OFF Summer Winter selector switch to K to the Winter position see diagram 1 Turn the central heating temperature control J to the desired setting see diagram 1 Turn the domestic hot water temperature con trol I to the desired settin...

Page 5: ...alve 19 Safety valve 3 bar 20 Domestic hot water expansion vessel A Heating return B Cold water inlet C Heating flow D Domestic hot water flow E Gas supply The boiler is delivered in three separate packages The boiler itself The fixing jig The flue system Hab 036 260 80 Ø 100 520 217 393 889 between 0 5 and 1 5 m fit diaphragm a a diaphragm seal Net weight 55 kg Gross weight 57 kg For flue systems...

Page 6: ... hot water flow 12 l min Expansion vessel effective capacity 0 5 l Electrical supply 230 V Maximum absorbed power 165 W Natural Nas Butane Propane G20 G 30 G 31 Burner injector 1 2 mm 0 75 mm 0 75 mm Inlet pressure 20 mbar 28 mbar 37 mbar Burner pressure 2 6 12 0 mbar 5 4 25 5 mbar 7 2 34 6 mbar Gas rate maximum 3 54 m3 h 2 64 kg h 2 6 kg h Gas rate minimum 1 56 m3 h 1 16 kg h 1 15 kg h Available ...

Page 7: ...uted to a position so that any discharge of water possibly boiling or steam can not create any danger to persons damage to property or external electrical components and wiring Tighten all pipe connection joints Connect the safety valve discharge pipe to the boiler the discharge must be extended using not less than 15 m o d pipe to discharge in a visible position outside the building facing downwa...

Page 8: ...ng suitable screws Check that both the hook and connecting plate are level If the boiler is not installed immediately protect the various couplings to prevent any ingress of foreign materials e g plaster paint etc Terminal position The minimum acceptable spacings from the ter minal to obstructions and ventilation openings are shown in diagram 8 The boiler must be installed so that the terminal is ...

Page 9: ... the lowest point of the system Where thermostatic radiator valves are fitted not all radiators must be fitted with this type of valve and in particular where the room thermostat is installed In the case of an existing installation it is ESSENTIAL thatthesystemisthoroughlyflushedpriortoinstalling the new boiler Filling the system Provision must be made for filling the system at low level The use o...

Page 10: ...s with internal access only Use a 125 mm diameter core drill Important Before cutting the hole for flues to the rear of boiler always cover fixing jig to make sure it is not damaged Calculation of flue cutting lengths Measure wall thickness e mm see diagram 9 For side flues measure distance from inside face of side wall to centre line of flue and subtract 260 mm for right and left hand flue to get...

Page 11: ...r P into groove at the outer end of pipe N see diagram 11 Fit outer pipe N into wall with groove to the outside Pull pipe inwards to bring rubber sealing collar hard up against external wall see diagram12 Fit internal plastic flange Q onto outer pipe Push along the pipe until engaged against inter nal wall From inside insert inner pipe O into outer pipe Fit both O rings T into the flue elbow V one...

Page 12: ...N THE HEATING CONTROLS CONNECTION PLUG Warning This appliance must be wired in accord ance with these instructions Any fault arising from in correct wiring cannot be put right under the terms of the Saunier Duval guarantee External controls The boiler will work for heating without a room ther mostat and or timeswitch being connected provid ed that the wire link fitted between the top two ter minal...

Page 13: ...s if fitted are calling for heat Allow the temperature to rise to the maximum value with all radiator valves open The temperature rise will cause release of the gases contained in the water of central heating system Gases driven towards the boiler will be automati cally released through the automatic air vents The gases trapped at the highest point of the sys tem must be released by bleeding the r...

Page 14: ...tem Persistent air in the heating system may indicate leaks in the system or corrosion taking place Call your Installation Servicing company Overheat safety In the event of a problem the overheat safety devices cause safety shutdown of the boiler If this happens call your Installation Servicing company The THELIA 30 E boiler has a built in frost protection device that protects the boiler from free...

Page 15: ... the pressure ANTICLOCKWISE To decrease the pressure After adjustment refit the cover to the gas valve adjuster Bypass The THELIA 30 E has a built in bypass This must be adjusted according to the requirements of the sys tem refer to the flow rate pressure curve diagram 4 The boiler is supplied with the built in bypass open a half a turn It is adjusted by turning the by pass screw see diagram 19 Tu...

Reviews: