1. Wiring method
(1) Remove screws that fixture both end of the terminal cover and dismount the terminal block.
Side view Enlarged view of alarm setting section
Re-install the cover after wiring. Refer to the 'Wiring method' section for cover removal.
(2) Connect the AC adapter to the unit while the alarm switches No. 1 to 4 (see the figure below) are set
to the left (OFF), and turn on the unit.
•
Set the upper limit temperature alarm.
(3) Slide the alarm switch No. 1 for the upper limit temperature to the right (ON).
The upper limit temperature value flashes on the temperature display.
(4) Press the
△
button to increase the setting value or the
▽
button
to decrease it.
Set to the desired value for the upper limit temperature alarm.
Pressing and holding the key quickly increases (decreases) the
value.