SATEL
INT-SZK
5
Relay ON time
– the time during which the relay output can be turned on after the access is
granted. You can program from 1 to 255 seconds.
Relay
[Relay type] – status of the deactivated relay:
NO
[Normal.open NO] – the relay contacts are open (they close on activating the relay).
NC
[Normal.closed NC] – the relay contacts are closed (they open on activating the relay).
Fig. 4. DLOADX program: parameters and options of code lock.
Authorization
control
[Unauth. event] – if this option is enabled, unauthorized opening of
the door will save the event to the control panel memory.
Alarm on unauth. access
[Unauth. alarm] – if this option is enabled, unauthorized opening
of the door when the partition is armed will trigger an alarm. The option is available if the
“Authorization control”
option is enabled.
Max. door open time
[Max. door open] – the maximum period of time during which the door
can be open (the door status input can be disconnected from common ground). If the door
is open longer, audible alarm will be triggered in the code lock, and the event will be saved
to the control panel memory. You can enter from the 0 to 255 seconds. If you enter 0, the
door can be open for any long period of time.
Dependent on door (1)
/
Dependent on door (2)
– you can select the door that must be
closed so that the user can get access (turn the relay output on). It allows you to create an
airlock. You may select a door supervised by another expander or alarm system zone
programmed as type “57 Technical – door open”.