ADDRESSABLE ZONES EXPANDER

 

CA-64 ADR 

 

ca64adr_e 12/05

 

The CA-64 ADR addressable zones expander is a device intended to work with the CA-64 
and INTEGRA alarm control panels. It allows extension of the alarm system by up to 

48

 

zones

 (depending on the control panel type) which have identical features as the main board 

zones. The expander module is fitted with a built-in switching-mode power supply of 2.2A 
capacity. It also has short-circuit protection of the supply output, and battery charging and 
testing circuits with disconnection of discharged battery. 

Note: Installation of the CA-64 ADR expander in the CA-64 alarm system will exclude 

the option to install other zones expanders as well as the CA-64 PP zone / 
output expander. 

This manual has been drawn up for the expander with firmware in version 1.5 or later. 

1.  Description of electronics board 

 

 

Fig. 1. Schematic view of the module electronics board. 

 
Explanations to Figure 1: 
1 – 

package of DIP-switches 

designed for setting individual address of the module

 

(switches 1-5) and for selecting the type of control panel the module interacts with 
(switch 8: OFF – CA-64; ON – INTEGRA). 

2 – 

LED

 indicator of the process of communication with the control panel. In the normal 

operating mode of the module, the LED is blinking with variable frequency. 

red

black 

Summary of Contents for CA-64 ADR

Page 1: ...ed battery Note Installation of the CA 64 ADR expander in the CA 64 alarm system will exclude the option to install other zones expanders as well as the CA 64 PP zone output expander This manual has b...

Page 2: ...connect windings of the secondary mains transformer The minimum input voltage at the maximum load of the transformer by the module can be 16V AC 2 Operation description Operation of the expander consi...

Page 3: ...der then during the identification procedure addresses 30 31 and also 0 1 and 2 will be additionally assigned to the module Should these addresses be already taken the control panel would be unable to...

Page 4: ...module Note Do not set the same addresses in the CA 64 ADR MOD modules because the detectors having such modules will have the same zone number assigned in the system 4 1 Interaction with the CA 64 co...

Page 5: ...signed to the keypad zones 29 32 zones assigned to the detectors with addressable zones installed detector with address 20 zone 29 detector with address 21 zone 30 etc In order to obtain continuity of...

Page 6: ...600m 3 Table 4 Fig 5 Connecting of addressable detectors to internal expander bus Fig 6 Example of connecting the addressable detector without tamper control 6 Installation The addressable zones expan...

Page 7: ...Connect the leads of internal data bus to the inputs INT 12V and COM and connect the addressable detectors to the bus If current consumption by the addressable detectors and battery exceeds capacity o...

Page 8: ...e module presence in the system Replacement of the expander with another even one having the same address set up on the switches without a new identification will trigger alarm module tamper verificat...