Satel APS-412 Manual Download Page 8

APS-412 

SATEL 

 

3.  If  the  connector  for  supplying  power  to  SATEL  devices  is  to  be  used,  connect  to  it  the 

cable shown in Fig. 4 (Fig. 6). 

4.  If screw terminals are to be used for supplying power to devices, screw the wires to +12V 

and COM terminals. 

5.  Connect the battery wires (Fig. 3) to the connector on the electronics board (Fig. 7). 

 

6.  You  can  connect  the  trouble  signaling  outputs  with  control  panel  zones,  or  you  can 

connect e.g. LEDs to these outputs. 

7.  Run the 230 VAC power cable through the cable gland (Fig. 8). 
8.  Screw  the  230  VAC  power  wires  to  terminals:  phase  conductor  to  L  terminal,  neutral 

conductor to N terminal, and protective conductor to PE terminal (Fig. 9). 

9.  Screw the element fastening the 230 VAC power cable (Fig. 10). 
10. Replace the cover of power supply terminals (Fig. 11) and fasten it with a screw (Fig.12). 
11. Connect  the  battery  to  the  dedicated  wires  (battery  positive  to  red  wire,  negative 

– 

to black). 

12. Turn on  230 VAC  power. When  the  AC  power  is  present, the power  supply  will  signal  it 

with a single beep sound and the 

 LED turning ON. 

If the power output is shorted to common ground or the F3 fuse is defective, the power 
supply will turn off. 

Summary of Contents for APS-412

Page 1: ...APS 412 Power supply EN Firmware version 1 02 aps 412_en 08 22 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Page 2: ...zed by the manufacturer shall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and softwa...

Page 3: ...S 1 Features 2 2 Description of the power supply 3 2 1 Electronics board 3 3 Configuration 4 4 Installation 5 5 Standard requirements for battery 8 6 Battery testing by the power supply 8 7 Specificat...

Page 4: ...nnect system Ability to work without a battery connected Output current operation with battery 3 5 A 3 A operation without battery 4 A Battery charging current 0 5 A 1 A selectable Connector for integ...

Page 5: ...tatus ON battery OK or the battery testing mode disabled flashing low battery battery voltage below 11 5 V OFF no battery or blown F3 fuse green LED AC power status ON AC power OK flashing no AC power...

Page 6: ...th SATEL devices It is used to power SATEL devices and transmit information on the power supply status The SATEL device must have the same connector The connecting cable is included in the set Fig 4 F...

Page 7: ...ircuit For a backup power supply use a 12 V sealed lead acid battery or other 12 V battery with similar charging characteristics The battery capacity must be selected to match the current consumption...

Page 8: ...e through the cable gland Fig 8 8 Screw the 230 VAC power wires to terminals phase conductor to L terminal neutral conductor to N terminal and protective conductor to PE terminal Fig 9 9 Screw the ele...

Page 9: ...SATEL APS 412 7...

Page 10: ...Ah 1 A or 0 5 A 3 A 24 Ah 1 A or 0 5 A 2 A 12 Ah 1 A or 0 5 A 1 A Table 2 6 Battery testing by the power supply After starting the power supply provided that the battery testing mode is enabled and a...

Page 11: ...ery connected 3 5 A 3 A Battery charging current selectable 0 5 A 1 A Current consumption of power supply circuits 57 mA Battery failure voltage threshold 11 5 V 10 Battery cut off voltage 10 5 V 10 O...

Reviews: