SATEL 

APS-412 

2.  Description of the power supply 

 

Explanations for Fig. 1: 

 F1 fuse (T 3.15 A) 

– AC circuit protection. 

 LEDs indicating status of the power supply: 

 

–  red LED – power output status: 

OFF 

– OK (current consumption below 4 A), 

flashing 

– overload (current consumption above 4 A). 

 

–  yellow LED – battery status: 

ON 

– battery OK (or the battery testing mode disabled), 

flashing 

– low battery (battery voltage below 11.5 V), 

OFF 

– no battery or blown F3 fuse. 

 

–  green LED – AC power status: 

ON 

– AC power OK, 

flashing 

– no AC power or blown F1 fuse. 

2.1  Electronics board 

Description of terminals: 

–  terminal for connecting phase conductor. 

–  terminal for connecting neutral conductor. 

PE 

–  terminal for connecting protective conductor. 

+12V 

–  +12 VDC power output. 

COM 

–  common ground. 

WS 

–  OC type output signaling 230 VAC power loss. 

Summary of Contents for APS-412

Page 1: ...APS 412 Power supply EN Firmware version 1 02 aps 412_en 08 22 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Page 2: ...zed by the manufacturer shall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and softwa...

Page 3: ...S 1 Features 2 2 Description of the power supply 3 2 1 Electronics board 3 3 Configuration 4 4 Installation 5 5 Standard requirements for battery 8 6 Battery testing by the power supply 8 7 Specificat...

Page 4: ...nnect system Ability to work without a battery connected Output current operation with battery 3 5 A 3 A operation without battery 4 A Battery charging current 0 5 A 1 A selectable Connector for integ...

Page 5: ...tatus ON battery OK or the battery testing mode disabled flashing low battery battery voltage below 11 5 V OFF no battery or blown F3 fuse green LED AC power status ON AC power OK flashing no AC power...

Page 6: ...th SATEL devices It is used to power SATEL devices and transmit information on the power supply status The SATEL device must have the same connector The connecting cable is included in the set Fig 4 F...

Page 7: ...ircuit For a backup power supply use a 12 V sealed lead acid battery or other 12 V battery with similar charging characteristics The battery capacity must be selected to match the current consumption...

Page 8: ...e through the cable gland Fig 8 8 Screw the 230 VAC power wires to terminals phase conductor to L terminal neutral conductor to N terminal and protective conductor to PE terminal Fig 9 9 Screw the ele...

Page 9: ...SATEL APS 412 7...

Page 10: ...Ah 1 A or 0 5 A 3 A 24 Ah 1 A or 0 5 A 2 A 12 Ah 1 A or 0 5 A 1 A Table 2 6 Battery testing by the power supply After starting the power supply provided that the battery testing mode is enabled and a...

Page 11: ...ery connected 3 5 A 3 A Battery charging current selectable 0 5 A 1 A Current consumption of power supply circuits 57 mA Battery failure voltage threshold 11 5 V 10 Battery cut off voltage 10 5 V 10 O...

Reviews: