background image

 

 

APS-30 S 

Power supply 

aps-30_s_en 05/21 

The  APS-30 S  switch  mode  power  supply  is  designed  for  devices  that  require  12 VDC 
nominal voltage. 

The  set  includes:  power  supply,  transformer,  enclosure  and  additional  accessories:  tamper 
switches, spacers, connecting cables for transformer, wall plugs (anchors) and screws. 

1.  Features 

  Nominal output voltage (according to IEC 38): 12 VDC. 

  Output voltage stabilization. 

  Battery status control and low battery disconnect system. 

  Ability to work without a battery connected. 

  Output current: 

  operation with battery: 2,5 A / 2 A, 

  operation without battery: 3 A. 

  Battery charging current: 0,5 A / 1 A (selectable). 

  Pins enabling configuration of the power supply settings. 

  3 LEDs to indicate: 

  AC mains power supply status, 

  battery status, 

  battery charging. 

  2 OC outputs to indicate the following troubles: 

  AC mains power loss, 

  low battery. 

  Acoustic signaling of troubles. 

  Electronic short-circuit protection of AC mains power supply circuit. 

  Short-circuit protection fuse for battery charging circuit (T 3,15 A). 

  Electronic short-circuit and overload protection of the power output. 

  Tamper protection against enclosure opening and removal from mounting surface. 

Summary of Contents for APS-30 S

Page 1: ...a battery connected Output current operation with battery 2 5 A 2 A operation without battery 3 A Battery charging current 0 5 A 1 A selectable Pins enabling configuration of the power supply settings...

Page 2: ...low LED to indicate the battery charging process It is ON when the battery is being charged brightness of light depends on current consumption When the battery status control is enabled the LED goes O...

Page 3: ...OC type outputs are shorted to ground 0 V but when a trouble occurs the output is disconnected from ground 3 Configuring the power supply Beeper for signaling trouble You can enable disable the acoust...

Page 4: ...ling familiarize yourself with the electrical installation of the facility Make sure that the circuit you choose for powering will be always alive The circuit should be protected with a proper safety...

Page 5: ...s of surface drywall styrofoam use the appropriately selected wall plugs 3 Run the wires through the openings in the enclosure base Fig 6 4 Fasten the enclosure base to the wall with four screws Fig 6...

Page 6: ...ctronics board on the plugs 13 Using two screws secure the LED board from above to the post inside the enclosure Fig 9 Make sure the LEDs enter their corresponding holes according to the symbols on th...

Page 7: ...ry charge status can take up to 12 minutes If the battery voltage drops below 11 V the power supply will indicate trouble on the AWB output and the green LED will start flashing optionally the trouble...

Page 8: ...ions 140 x 99 mm Enclosure dimensions 266 x 286 x 100 mm Weight without battery 2 45 kg The declaration of conformity may be consulted at www satel eu ce SATEL sp z o o ul Budowlanych 66 80 298 Gda sk...