53
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
Alarm/Event Setpoints Setup
2576-2703
+0
Trigger parameter ID
F12
UINT16
R/W
+1 Action
F14
UINT16
R/W
+2 Operate
delay
0-9999
×
0.1 sec
UINT16 R/W
+3 Release
delay
0-9999
×
0.1 sec
UINT16 R/W
+4,5
Operate limit
See Section 3.3
UINT32
R/W
Scaled value
+6,7
Release limit
See Section 3.3
UINT32
R/W
Scaled value
2576-2583
Setpoint #1
2584-2591
Setpoint #2
2592-2599
Setpoint #3
2600-2607
Setpoint #4
2608-2615
Setpoint #5
2616-2623
Setpoint #6
2624-2631
Setpoint #7
2632-2639
Setpoint #8
2640-2647
Setpoint #9
2648-2655
Setpoint #10
2656-2663
Setpoint #11
2664-2671
Setpoint #12
2672-2679
Setpoint #13
2680-2687
Setpoint #14
2688-2695
Setpoint #15
2696-2703
Setpoint #16
Pulse Counters Setup
2940-2947
+0
Source digital input ID
0=not assigned, 1-12=DI1-DI12
UINT16
R/W
+1 Multiplier
0-9999
UINT16
R/W
2940-2941
Counter #1 Setup
2942-2943
Counter #2 Setup
2944-2945
Counter #3 Setup
2946-2947
Counter #4 Setup
Analog Outputs Setup
3148-3153
+0
Output parameter ID
F18
UINT16
R/W
+1
Zero scale value (0/4 mA)
See Section 3.3
UINT16
R/W
Scaled value
+2
Full scale value (1/20 mA)
See Section 3.3
UINT16
R/W
Scaled value
3148-3150
AO1 Setup
3151-3153
AO2 Setup
Network Setup
46576-46703
+0,1
Device IP Address 0x01000000-0xFFFFFFFF UINT32
R/W
Network byte order