Chapter 4 PAS Application Software
Configuring Summary Energy and TOU Registers
Series PM172 Powermeters
83
The available options are shown in the following table:
Parameter Options Default
Description
Summary/TOU Registers
TOU Unchecked
Checked
Unchecked Links tariff registers to the selected
energy source
Use Profl
Unchecked
Checked
Unchecked Enables automatic daily profiling for
energy usage registers (both total and
tariff registers if TOU is enabled)
Dmd Profl
Unchecked
Checked
Unchecked Enables automatic daily profiling for
maximum demand registers (both total
and tariff registers if TOU is enabled)
Sum Profl
Unchecked
Checked
Unchecked Enables daily profiling for summary
registers (total of all tariffs)
Units
kWh, kvarh, kVAh,
m3, CF (cubic foot),
CCF (hundred cubic
feet)
None
The register measurement units. When
a register is linked to an internal energy
source, it is set automatically. When an
external pulse source is used, the user
can select a measurement unit for the
register.
Register Source List
Source
Input
None
kWh Import
kWh Export
kvarh Import
kvarh Export
kVAh,
DI1-DI2
None
Links an energy source to the register
Multiplier
0.001 to 100.000
1.000
The multiplication factor for the energy
source.
Target
Reg#1- Reg#8
None
Defines the target billing register for the
energy source. It is set automatically.
Configuring the Daily Tariff Schedule
To configure your daily tariff schedule, select Energy/TOU from the Meter
Setup menu, and then click on the TOU Daily Profiles tab.
The daily profile setup allows you to specify the daily tariff change points with
a 15-minute resolution for 4 seasons using 4 different daily schedules for
each season.
To configure your daily profiles:
1. Select the desired season and day type.
2. Select the start time for each tariff change point and the corresponding
active tariff number.
3. Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and the last tariff change
you specified will be in use until 00:00 hours on the next day.
The energy daily profile log will be automatically configured for the number of
active tariffs you defined in the meter TOU daily profile.