Chapter 5 Configuring the PM135
Configuring Recorders
108
PM135 Powermeter Series
Billing/TOU Daily Profile Log File
Data log #16 is configurable to store TOU daily profile log records on a
daily basis.
The file is organized as a multi-section file that has a separate section of
the same structure for each billing energy and maximum demand register.
The number of sections is taken automatically from the Billing/TOU Registers
setup (see
Configuring Billing/Tariff Registers
). If the maximum demand
profiling is used, then the number of sections in the file will be twice the
number of the allocated billing registers.
To configure a daily profile log file:
1.
Configure your Billing/TOU registers and tariff schedule in
the meter (see
Configuring Billing/Tariff Registers
) first.
2.
Double click on the
Data Log#16
partition with the left
mouse button.
3.
Select the
TOU Daily Profile
file type.
4.
Select the number of season tariffs in your TOU schedule.
Add one additional parameter if you selected to record the
Summary (TOU total) registers as well.
5.
Select the maximum number of records you want to be
recorded in the file assuming that a new record will be
added once a day.
6.
Click
OK
and send your setup to the meter or save to the
meter database.
Factory Preset Data Log Files
Conventional Data Log #1
Data log #1 is factory preset for 15-min periodic recording of the standard
energy and demand quantities. You can freely change the list of recorded
parameters and the file update rate.
The default list of parameters is shown in the following table.
No.
Parameter
1
kWh import
2
kWh export
3
kW import sliding demand
4
V1 demand
5
V2 demand
6
V3 demand
Periodic recording data is triggered by Setpoint #1 that is linked to the
meter clock. To change the periodic rate at which data is recorded,