37
Figure 52 - Disconnect link
After making connections FBD is ready to be uploaded to the device.
Just check that you have set addresses for all variables (see
3.7.3) and
you can proceed to uploading the configuration to the PM180 device
(see
3.8.2).
3.9.6
Making time delays
To make time delays use functions TON and TOF. For detailed
information see
2.3.9 and
2.3.10. Time values are set via local variables
with TIME data type.
Time delay example is shown in the figure below.
Figure 53 - Time delay
Time delay is set in Initial value property in one of these formats (in
accordance with IEC 61131): “
T#100ms
”, “T#2
00ms
”
or
“
T#1s0ms
”
(if
a value is more than 1 second).
In the figure below you can see the result of this logic in PAS (after
uploading to the device).