17
Point
ID
Description
Options/Range
2
Units
2
Type
R/
W
Notes
0x140C
3-phase average current
0-Imax
U2
UINT32
R
1-Second Auxiliary Values
0x1500
Not used
UINT32
R
0x1501
In (neutral) Current
0-Imax
U2
UINT32
R
0x1502
Frequency
0-Fmax
0.01
Hz
UINT16
R
0x1503
Voltage unbalance
0-3000
0.1
%
UINT16
R
0x1504
Current unbalance
0-3000
0.1
%
UINT16
R
Present Volt, Ampere and Power Demands
0x1600
V1/V12 Volt demand
0-Vmax
U1
UINT32
R
1
0x1601
V2/V23 Volt demand
0-Vmax
U1
UINT32
R
1
0x1602
V3/V31 Volt demand
0-Vmax
U1
UINT32
R
1
0x1603
I1 Ampere demand
0-Imax
U2
UINT32
R
0x1604
I2 Ampere demand
0-Imax
U2
UINT32
R
0x1605
I3 Ampere demand
0-Imax
U2
UINT32
R
0x1606
kW import block demand
0-Pmax
U3
UINT32
R
0x1607
kvar import block demand
0-Pmax
U3
UINT32
R
0x1608
kVA block demand
0-Pmax
U3
UINT32
R
0x1609
kW import sliding window demand
0-Pmax
U3
UINT32
R
0x160A
kvar import sliding window demand
0-Pmax
U3
UINT32
R
0x160B
kVA sliding window demand
0-Pmax
U3
UINT32
R
0x160C
Not used
0
UINT32
R
0x160D
Not used
0
UINT32
R
0x160E
Not used
0
UINT32
R
0x160F
kW import accumulated demand
0-Pmax
U3
UINT32
R
0x1610
kvar import accumulated demand
0-Pmax
U3
UINT32
R
0x1611
kVA accumulated demand
0-Pmax
U3
UINT32
R
0x1612
kW import predicted sliding window demand
0-Pmax
U3
UINT32
R
0x1613
kvar import predicted sliding window demand
0-Pmax
U3
UINT32
R
0x1614
kVA predicted sliding window demand
0-Pmax
U3
UINT32
R
0x1615
PF (import) at Max. kVA sliding window demand
0-1000
0.00
1
UINT16
R
0x1616
kW export block demand
0-Pmax
U3
UINT32
R
0x1617
kvar export block demand
0-Pmax
U3
UINT32
R
0x1618
kW export sliding window demand
0-Pmax
U3
UINT32
R
0x1619
kvar export sliding window demand
0-Pmax
U3
UINT32
R
0x161A
kW export accumulated demand
0-Pmax
U3
UINT32
R
0x161B
kvar export accumulated demand
0-Pmax
U3
UINT32
R
0x161C
kW export predicted sliding window demand
0-Pmax
U3
UINT32
R
0x161D
kvar export predicted sliding window demand
0-Pmax
U3
UINT32
R