12
Room distribution blower units
Refer to the manual supplied with the Room Distribution Units for specifics on the blower units themselves.
Clearances required are shown below.
A B C D E F H
Minimum
dimension
(inches)
20 72 72 24 20 72 24
Model
SMP001 SMP003 SMP005 SMP008 SMP009 SMP010 SMP015 SMP025 SMP035 SMP045 SMP065
Room Blower
Unit Model
VSDU0A
VRDXL
Rated Power
Watts
30 35
Air Volume
CFM
100 380
Noise Level
dBA
50 40
Operating Temp/Humidity
(°F / %RH)
14 to 104°F
/ 10 to 60%
14 to 140°F
/ 10 to 80%
Cold rooms can be humidified using a Room Distribution Unit, making sure that this operates within its operating
limits. The room must have operating temperatures of between -10°C and +20°C, with a percentage of relative
humidity of no greater than 80% RH. If these limits are not possible, the steam can be distributed in the cold room
using a distributor pipe in duct work. In any case, the steam must not come into direct contact with air discharge
from the refrigeration unit in the cold room, to avoid possible condensation.