OPERATION
CONTROL PANEL
The control panel is located below the doors on the rear of the appliance
TURN ON
1 Close the doors of the appliance
2 Connect the appliance to a mains power supply
3 Press the button to turn the light On or Off as required
MANUAL DEFROST
Press and hold the button for 6 seconds to begin automatic defrost The defrost light illuminates
SETTING THE OPERATING TEMPERATURE
1 Press the button The display will flash
2 Press the or buttons to display the required temperature
3 Press the button to store the temperature
SETTING THE OPERATING TEMPERATURE
1 Press and hold the button for 6 seconds The „E1“ parameter is displayed
2 Press the or buttons tuntil the required value is displayed
3 Press the button to store the new value and cycle to next parameter
NOTE: The controller times out after 10 seconds if no buttons are pressed
UK
TABLE OF CONTROLLER PARAMETERS
The operating parameters of this appliance have been preset for optimum performance and to maximise the life of the
appliance
DISPLAY
PARAMETER
PRESET VALUE
RANGE
E1
Lower set temperature
0 °C
-20 °C to 2 °C
E2
Upper set temperature
12 °C
2 °C to 45 °C
E3
Temperature buffer
4 °C
1 °C to 10 °C
E4
Temperature buffer time delay
3 minutes
0 to 10 minutes
E5
Fixed parameter
0
DO NOT CHANGE
E6
Fixed parameter
00
DO NOT CHANGE
F1
Defrost period
25 minutes
1 to 60 minutes
F2
Defrost interval
6 hours
1 to 24 hours
F3
Defrost temperature
20 °C
0 °C to 22 °C
F4
Centigrade/Fahrenheit
0 °C
°C / °F