background image

A7395C

4

1. Turn the power to the unit “On”. Red LED pilot light should illuminate at 8 sec. intervals

2. Open door to the hold open point. The door should hold open. Manually pull door out of hold open and release. Door should close

3. Open door to the hold open position. Depress (maintained type) On/Off “test switch” button on the power supply board. Door should close

4. Depress On/Off test switch again. Open door to the hold open position. Introducing smoke into the smoke detector chamber assembly will bring the unit 

  into alarm. The red LED will be continuously illuminated and the door will close. After clearing the smoke chamber, reset unit per instructions below

Checkout Procedure for both 12- and 9- units

1. Remote Reset: Cycle main power by turning the facility main power supply OFF then ON. 

  NOTE: If there are other units connected to the same power supply, those doors will close. 

  They will have to be reopened returning them to the hold open position

2. Local Reset: Insert a small flat head screwdriver through the cover and into the slotted 

  light tube on the smoke detector as shown. Turn screwdriver slightly (about 1/8 turn)

  clockwise until hitting stop and hold for 2 seconds until the Red LED turns OFF 

  WARNING: Do not force past the stop. Doing so may damage the smoke detector

Once the detector is reset and the smoke has cleared, the detector’s Red LED should flash 

once every 8 seconds. The door(s) should hold open now

Resetting Instructions

SARGENT recommends cleaning smoke detectors at least every six months. The frequency of cleaning will depend upon local ambient conditions

The smoke detector in this door closer-holder has been enhanced with a feature that detects when a smoke-sensing chamber requires cleaning 

due to dirt and dust. The need for cleaning is indicated by the flashing of the Red LED light once per second

•  Normal Supervisory Operation — Red LED flashes once every 8 seconds

•  Dirty Chamber needs cleaning — Red LED flashes once every second

•  Smoke Detection — Red LED is continuously illuminated

To clean the smoke detector assembly, follow the instructions below:

NOTE: Before servicing the system, notify the proper authorities
that the smoke detector system is undergoing maintenance
and will be temporarily out of service. Disable the zone undergoing
maintenance to prevent unwanted alarms

Smoke Detector Maintenance

•  Remove detector cover and screen assembly using a standard screwdriver. Turn the screwdriver in the cover slot to loosen the cover and carefully 

  rock the cover back and forth until it snaps out of place. See slot location above

•  Inspect chamber for particles and dust. Vacuum the screen, cover, and photo chamber. Then, use clean compressed air to loosen and blow out

  any remaining debris

•  Before reassembling the detector, be sure all parts are free of dust and debris

•  Replace cover and screen, aligning cover snaps, press cover onto chamber until it snaps into place

•  Measure and record the test voltage at test points RP1 and RP2 (see above). If the smoke detector is operating normally and was cleaned

  effectively, the test voltage will be greater than .90VDC and less than 1.58VDC. The test voltage will increase with dust accumulation in the

  smoke sensing chamber. A difference in test voltages over time will provide an indication of dust accumulation

•  Enable system and inform proper authorities that system is operational

RP2 test point

RP1 test point

Slot for screwdriver

To remove cover

Cover and 

screen

Chamber

Slotted light tube (Red LED)

A7395C.indd   4

10/29/18   12:44 PM

Summary of Contents for Fireguard 2900 Series

Page 1: ...ater date place cover on chassis now to prevent its loss see Step F 5 Installation of arm on closer With appropriate size wrench rotate closer top spindle approximately 45ϒ see step C below NOTE Closing both valves for door speed and latching speed makes this procedure much easier Position closer arm on bottom spindle approximately parallel to the door and arm length away from hinge Secure arm wit...

Page 2: ...g and latching speeds Turn valves clockwise to slow down or counterclockwise to speed up door movement Backcheck To regulate the intensity of backcheck action turn valve clockwise to increase or counterclockwise to decrease checking Caution Set valve for slight cushioning effect Closer can be damaged if the checking action is too abrupt Never use the backcheck as a door stop Always use a door stop...

Page 3: ...s On Off Switch Door should close and latch Adjustment of spring power may be necessary to ensure proper latching Depress on off switch again Open door to hold open position door will hold open 3 ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES ORDINANCES AND REGULATIONS 4 MAXIMUM WIRE SIZE IS 18AWG CAUTION Input power supply must match circuit board voltage rating either 24VAC DC or ...

Page 4: ... a feature that detects when a smoke sensing chamber requires cleaning due to dirt and dust The need for cleaning is indicated by the flashing of the Red LED light once per second Normal Supervisory Operation Red LED flashes once every 8 seconds Dirty Chamber needs cleaning Red LED flashes once every second Smoke Detection Red LED is continuously illuminated To clean the smoke detector assembly fo...

Page 5: ...A7395C 5 A7395C indd 5 10 29 18 12 44 PM ...

Page 6: ...A7395C 6 FIREGUARD A7395C indd 6 10 29 18 12 44 PM ...

Reviews: