A7395C
3
CAUTION
Typical Wiring
1. DISCONNECT ALL POWER BEFORE BEGINNING INSTALLATION
TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
2. INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE
PERSON
Stand-Alone Units 2960
• Wire stand-alone unit to appropriate
power supply and fire alarm
• Refer to data sticker for proper
input voltage and current specifications
• Energize power supply
• Open door to hold-open point
Door should hold open
• Depress On/Off Switch. Door should
close and latch
• Adjustment of spring power may be
necessary to ensure proper latching
• Depress on/off switch again. Open door to
hold open position; door will hold open.
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL
ELECTRICAL CODES, ORDINANCES AND REGULATIONS
4. MAXIMUM WIRE SIZE IS 18AWG
CAUTION: Input power supply must match circuit
board voltage rating, either 24VAC/DC or 120VAC.
Opening for
Concealed Wiring
Earth Ground
Negative (-)
Positive (+)
3
2
1
Appropriate
Power Supply
Data
Sticker
On/Off
Switch
Terminal Strip
for Power Input Connections
Optional remote
release connection