3
System Controller
Mode Setting
According to the function of each system controller, set SW1
as Fig. 3-62.
(1) Central control/Remote control mode
Central control mode
System controller is used as central control
equipment.
Individual setting by remote controller can be
inhibited by system controller
Remote control mode
System controller is used as remote controller.
Setting by system controller is inhibited by other
central control equipments.
(2) ALL/ZONE mode
ALL mode
All indoor units can be controlled by system
controller.
ZONE mode
Indoor units in one of ZONE 1, 2, 3 or 4 can be
controlled by system controller
(3) Function of system controller is 10 types
according to combination of central control/remote
control mode and ALL/ZONE mode setting as the
table 3-1.
(4) Stick the system controller unit label in a
conspicuous position.
2
ON
OFF
3 4 5 6
ALL
central control
2
ON
OFF
3 4 5 6
ALL
remote control
Inter-unit control wiring
2
ON
OFF
3 4 5 6
ZONE1
central control
2
ON
OFF
3 4 5 6
1
ZONE1
remote control
2
16
ZONE1
central control
address 1-16
2
ON
OFF
3 4 5 6
ZONE2
central control
2
ON
OFF
3 4 5 6
17
ZONE2
remote control
18
32
ZONE2
central control
address 17-32
2
ON
OFF
3 4 5 6
ZONE3
central control
2
ON
OFF
3 4 5 6
33
ZONE3
remote control
34
48
ZONE3
central control
address 33-48
2
ON
OFF
3 4 5 6
ZONE4
central control
2
ON
OFF
3 4 5 6
49
ZONE4
remote control
50
64
ZONE4
central control
address 49-64
Central control
mode
Remote control
mode
Table 3-1
Central control
Remote control
ALL
1.
ALL/Central
6.
ALL/Remote
ZONE1
2.
ZONE1/Central
7.
ZONE1/Remote
ZONE2
3.
ZONE2/Central
8.
ZONE2/Remote
ZONE3
4.
ZONE3/Central
9.
ZONE3/Remote
ZONE4
5.
ZONE4/Central
10.
ZONE4/Remote
Fig. 3-62
Summary of Contents for SHAKC64AGB