8-5. Cold Draft Prevention (Heating)
●
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat
exchange coil have sufficiently warmed up.
●
Indoor fan speed varies according to the indoor heat exchange coil temperature as table shown below.
✽
1 When the coil temperature rises above 36°C, indoor fan operates in set speed. At the same time,
standby lamp on front of the indoor unit lights OFF.
✽
2 If 10 minutes has elapsed after the compressor has been stopped, the indoor fan stops its operation
regardless of the indoor heat exchange coil temperature.
Standby lamp
Compressor
Set Speed
Low
LL
UL
OFF
Set Speed
Low
LL
UL
OFF
Indoor fan
36
°
c
30
°
c
25
°
c
Indoor heat
exch. coil
temp.
Compressor : ON
when the coil
temp. goes up
20
°
c
Compressor : OFF
when the coil
temp. goes down
ON
OFF
OFF
OFF
ON
ON
NOTE
38
Condition
Indoor coil temperature (°C)
Indoor fan speed
Compressor is in operation
(Indoor coil temp. goes up)
below 25°C
OFF
between 25 to 30°C
LL (Very low)
between 30 to 36°C
Low
over 36°C
Set speed
✽
1
Compressor is stopped
(Indoor coil temp. goes down)
over 20°C
UL (Ultra low)
below 20°C
OFF
✽
2