18

8-2. Current Control

 The operating current may rise as a result of causes 

including increasing heating or cooling loads or 
decreases in power voltage. In these cases, the 
operating frequency is automatically reduced, or 
operation is stopped, in order to control the operating 
current so that it is 20 A or less.

   

 

As a result:

•  Power breakers and fuses will not be tripped.
•  Operation can continue during this period with 

somewhat reduced heating or cooling capacity.

•  Operation at normal capacity is restored when the 

cause of the current rise is eliminated.

Description of function

8-3. Low Start Current

 

Operation starts at 10 Hz, and the start current is less than 
the normal operating current. This prevents the flickering of 
fluorescent lights or television screens that occurs when 
ordinary A/C units start.

8-4. Compressor Temperature Control

 

To protect the compressor coil from overheating, the 
operating frequency is controlled based on the compressor 
discharge temperature.

8-5. Outdoor Fan Control

8-5-1. COOL operation

8-2-1. Automatic frequency control

The operating frequency is reduced automatically, or 
operation is stopped, in order to control the operating 
current so that it is at or below the values shown in the 
table below.

8-2-2. Current control

The operating frequency upper limits shown in the figure 
below are established for frequency reduction and 
increase-prohibit.

Example of operation for heating

Example of operation during cooling

•  Operates at the target frequency at Point  A and below.
•  Stops increases to the frequency between Points A and B.
•  Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.
•  Stops operation, and restarts it approximately 3 minutes later, if Point C is 

exceeded.

  (May operate when sudden voltage fluctuations occur. 

 Indicates trouble.)

Current

Frequency

Target

frequency

Power Point C

Point B
Point A

Frequency

Stops operation

Approx. 3 minutes

22.5A
13.0A
12.6A

Frequency (Hz)

Current (A)

Hz reduction

Hz increase prohibit

Hz increase prohibit

Hz reduction

Trip

Hz reduction

Hz increase

prohibit

0

10.1

10.5

30

Point C (peak cut trip) 

22.5 

22.5

Point B (Hz reduction) 

13.0 

14.0

Point A (Hz increase prohibit) 

12.6 

13.6

NOTE:  During defrost operation, the COOL current 

setting value is used.

HEAT

20A

COOL

Compressor discharge temperature

(

°

C)

5Hz every 30 sec. reduction

2Hz every 30 sec. reduction

(Hz reduction)

Increase

prohibit range

No control

Trip

90

100

106

110

Outdoor air temperature

Maintain previous status

Fan L

Fan H

Fan H

Fan H

Fan H

35 Hz or above

Less than 35 Hz

35 Hz

Frequency

31

°

C

29

°

C

*

  Within the increase-prohibit range, the range changes 

to the Hz reduction range (2 Hz every 30 seconds) if 
the compressor temperature rises by 2

°

C.

Summary of Contents for SAP-CMRV3143GJH

Page 1: ...vicing the unit 4 room multi Outdoor unit Combined Indoor Units 1 How these units may be combined is given in the Unit Combination Tables in the Appendix 2 Be sure to operate the air conditioning system only when 2 or more indoor units have been installed If operated with only a single unit installed the returning fluid to the compressor may cause a malfunction NOTE Concealed duct type SAP DMRV93G...

Page 2: ...ing Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal fra...

Page 3: ...urrent Control 18 8 3 Low Start Current 18 8 4 Compressor Temperature Control 18 8 5 Outdoor Fan Control 18 8 6 Control at HEAT Start up 19 9 TROUBLESHOOTING 9 1 Conditions That Do Not Represent Trouble 20 9 2 Outdoor Unit Trouble Diagnostics 21 9 3 Checking the Outdoor System 22 9 4 Unit Problems and Inspection Points 23 9 5 Explanation of Functions 26 10 REFRIGERANT R410A SPECIAL PRECAUTIONS WHE...

Page 4: ...G RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Maximum 32 C D B 23 C W B 43 C D B Minimum 19 C D B 14 C W B 19 C D B Heating Maximum 27 C D B 24 C D B 18 C W B Minimum 16 C D B 15 C W B ...

Page 5: ...m in 6 35 1 4 4 tube diameter Wide tube mm in 9 52 3 8 3 mm in 12 7 1 2 1 Dimensions Weight Unit dimensions Height mm 880 Width mm 940 Depth mm 340 Package dimensions Height mm 981 Width mm 1 016 Depth mm 440 Weight Net kg 90 Shipping kg 92 Shipping volume m3 0 44 DATA SUBJECT TO CHANGE WITHOUT NOTICE 2 Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature ...

Page 6: ...f control YES Compressor discharge temp control YES Operation cut off control in abnormal ambient temp Run capacitor µF VAC Crankcase heater 25W 240V Fan Fan Motor Type Propeller Q ty Dia mm 1 ø460 Fan motor model Q ty KFC6S 61C3PA C 1 No of poles rpm 220V High 6 712 Nominal output W 60 Coil resistance Ambient temp 20 C Ω BRN WHT 66 53 WHT YEL 33 95 YEL PNK 12 50 Safety devices Type Thermal protec...

Page 7: ......

Page 8: ...H 18 880 940 33 7 Wide tube service valve ø9 52 3 8 Wide tube service valve ø12 7 1 2 Narrow tube service valve ø6 35 1 4 336 256 416 176 25 13 380 AIR DISCHARGE 25 13 465 Unit mm 25 25 10 405 13 13 660 109 Drain hole AIR INTAKE 296 340 AIR INTAKE 15 ...

Page 9: ...Main accumulator Receiver tank Indoor unit Insulation of Refrigerant Tubing Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a proper insulation material The thickness of the insulation should be a min 8 mm After a tube ha...

Page 10: ...an 2 Operating current performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operating current A Low pressure MPa High pressure MPa Operating current A Indoor discharge air temperature C Indoor discharge air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air ...

Page 11: ...rmance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operating current A Low pressure MPa High pressure MPa Operating current A Indoor discharge air temperature C Indoor discharge air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air te...

Page 12: ...rformance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 1 High pressure performance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Operating current A Low pressure MPa High pressure MPa Operating current A Indoor discharge air temperature C Indoor discharge air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air...

Page 13: ...erformance chart RH 85 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 50 60Hz 220V Low pressure MPa High pressure MPa Operating current A Indoor discharge air temperature C Indoor discharge air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air temperature C Outdoor air temperature C 25 30 35 40 11 10 9 8 24 C Indoor air temp 30 C 27 C Lo f...

Page 14: ... B WIDE PIPE THERMISTOR ROOM B NARROW PIPE TH6 MECHANICAL VALVE MVA MVD BOARD IN WIRE DEFROST VALVE DEF CONTROL PCB MUL TI P L E I ND O OR U NI T S HE A T P U MP O U TD O OR U N IT FO R F OU R R O OM G1 W W G2 UNIT A INDOOR W W L2 L1 WHT BLK GRN YEL GRN YEL FILTER PCB 7 9 CN35 WHT 3 1 5 SI TERMINAL BASE 3P WHT 6 6 7 7 WHT PAM PAM CN23 4 4 5 5 1 1 2 2 WHT CT CT WHT CN08 1 1 3 3 WHT PRY PRY RED CN21...

Page 15: ... H4 above or below the outdoor unit and within a total tubing length L1 L2 L3 L4 from the outdoor unit as detailed in Table 1 and Fig 1 INDOOR UNIT 1 INDOOR UNIT 4 INDOOR UNIT 3 INDOOR UNIT 2 Tubing length L1 L2 L3 L4 Elevation difference H1 H2 H3 H4 OUTDOOR UNIT Fig 1 WARNING To prevent abnormal heat generation and the possibility of fire do not place obstacles enclosures and grilles in front of ...

Page 16: ... unit Union φ12 7 Flare φ9 52 φ12 7 D φ12 7 φ9 52 Optional parts STK 43TCA 93 123 types 93 123 types 93 123 types 183 type More than 17 m 2 Connecting indoor unit type 183 at D Length of tube more than 17 m φ6 35 φ6 35 φ6 35 φ6 35 φ9 52 φ9 52 φ9 52 φ9 52 φ9 52 A φ9 52 B φ9 52 C Outdoor unit Indoor unit Union φ9 52 Flare φ12 7 φ12 7 D φ12 7 φ9 52 Supplied Reducer 93 123 types 93 123 types 93 123 ty...

Page 17: ...and that will not magnify operating noise or vibration Fasten in place with the anchor bolts M10 provide a base using concrete or similar material and ensure proper drainage select a location where there is no danger of flammable gas leakage in snowy or rainy regions be sure to construct a roof to keep off the snow and rain and inhibit freezing and condensation select a location that is at least 3...

Page 18: ...to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed A B C D Tubing panel Base not provided concrete or similar material Ensure 150 mm of space if a drain hose is to be used Fasten with anchor bolts not provided 3 8 or M10 4 locations Inspection panel ...

Page 19: ...nit B Unit A Unit C Unit D Unit B Unit C Unit D A Terminal plate 16P Grounding line Power supply Single phase AC 220V 240V B Terminal plate 3P CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit 7 5 Wiring System Diagram WARNING Be sure to comply with local codes on running the wire from the indoo...

Page 20: ...ture is less than 0 C Compressor 100 Hz operation 4 way valve ON Outdoor fan OFF Solenoid valve ON for hot gas bypass Indoor fan OFF Temperature of the outdoor heat exchanger is at or above the temperature shown in the table below Defrost operation has continued for 12 minutes max length HEAT operation Frost detection Defrost end Non stop defrost operation Outdoor heat exchanger temperature 13 0 8...

Page 21: ...ent control The operating frequency upper limits shown in the figure below are established for frequency reduction and increase prohibit Example of operation for heating Example of operation during cooling Operates at the target frequency at Point A and below Stops increases to the frequency between Points A and B Reduces the frequency by 1 Hz per 0 5 seconds when Point B is exceeded Stops operati...

Page 22: ...Decrease Stop operation 58 54 60 Fan H Fan H Fan H Fan L Fan L Fan L Less than 35 Hz Above 35 Hz Above 5 C 5 C or below Outdoor air 5 C 19 Hz Frequency 8 6 Control at HEAT Start up If HEAT operation is started when the outdoor air temperature is 15 C or below the unit operates at the HEAT start up frequency 70 Hz or above Reset conditions 1 The compressor frequency exceeds the start up frequency o...

Page 23: ...roximately 60 seconds will be required for the charge to dissipate However allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble with the outdoor control circuit board If the outdoor control circuit board fuse has blown approximately 30 minutes will be required to discharge the high capacity electrolytic capacitors Trouble diagnostics contents 1 Conditions t...

Page 24: ...bing D sensor narrow tubing Outdoor air temperature sensor Branch tubing A sensor wide tubing Branch tubing B sensor wide tubing Branch tubing C sensor wide tubing Branch tubing D sensor wide tubing CT current sensor HIC protective device current temperature OTP data failure Current peak exceeded Current control failure Active failure Compressor discharge temperature high Zero cross failure DC com...

Page 25: ...N NOTE The dashed line for the defrost or clean defrost lamp indicates lamp illumination at clean defrost only The maximum length of defrost operation is 12 minutes Defrost can also be ended based on the below conditions for the outdoor heat exchanger sensor Less than 2 minutes Not ended 2 minutes or more 10 C or higher However the condition is 7 C or higher when the outdoor air temperature is bel...

Page 26: ... Compressor Compressor protective thermistor Outdoor fan motor 4 way valve Coil thermistor Electric expansion valve Branch tubing temperature sensor Breaker Refrigerant gas pressure Measure during a test run Operation lamp flashes Indoor fan does not turn Operation lamp does not illuminate The compressor only does not operate The compressor stops on occasion The compressor speed does not increase ...

Page 27: ...and If the fan rotates easily a Replace the running capacitor on the outdoor control circuit board b Check for an open circuit in the fan motor coil winding c Use the tester AC range to check whether voltage is reaching the connector on the outdoor fan motor circuit board If the needle moves the result is normal If the fan does not rotate easily a Check whether something is obstructing the fan or ...

Page 28: ... the problem may not be refrigerant shortage The problem may be a blockage of the refrigerant circuit a Check that there is no internal leakage inside the 4 way valve At the low pressure side tubing check that there is no temperature difference between the intake and discharge of the 4 way valve b Check that the electric expansion valve is not blocked Check as described on the preceding page NOTE ...

Page 29: ...e h T h g i h e r a s e r u t a r e p m e t r o o d t u o d n a r o o d n i e h t f I y n a g n i p p o t s s e t a v i t c a f f o t u c k a e p t n e r r u c e h t y c n e u q e r f n i s e s a e r c n i e r u t a r e p m e t m o o r e h T d e r i s e d e h t d e h c a e r s a h e r u t a r e p m e t e t o m e r e h t d n a e r u t a r e p m e t r o o d n i e h T e r a g n i t t e s e r u t a r ...

Page 30: ... t s o r f e D N O s n r u t n a f r o o d n I r o f e v l a v d i o n e l o s e h t s d n o c e s 0 1 r e t f A F F O s n r u t s s a p y b s a g t o h d e r a e p p a s i d s a h l e e f r i a d l o c e h t n e h W y l l a u d a r g d n a s t r a t s n a f r o o d n i e h t t e s e h t s e h c a e r t i l i t n u d e e p s s e s a e r c n i d e e p s P O T S t s o r f e d n a e l C d e m r o f r...

Page 31: ... h t s e t u n i m 3 r e t f A y l l a c i t a m o t u a g n i t a r e p o s i e c n a l a b e r u s s e r p a s e t u n i m 3 e s e h t g n i r u D t r a t s o t r o s s e r p m o c e h t g n i w o l l a d e v e i h c a y l i s a e e r o m n o i t n e v e r p e z e e r F t a e h r o o d n i e h t f o e r u t a r e p m e t e h t n e h W C 2 y l e t a m i x o r p p a o t s p o r d r e g n a h c x e...

Page 32: ...i a m n o i t a r e p o A Y R D n e e w t e b s e g n a h c n a f r o o d n i e h T Low and LL very low over a 6 minute n o i t a r e p o n a f n o i t a u t c u l f f 1 s i s i h T e l c y c g 2 below i F o t r e f e R r i a e h t y f i d i m u h e d y l e v i t c e f f e o t s e t a r e p O r o o d n i e h t g n i c u d e r y l e v i s s e c x e t o n e l i h w e r u t a r e p m e t n o i t a u ...

Page 33: ...its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on whether it is in gaseous or liquid phase and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state Thus always charge the refrigerant while it is in liquid phase 10 2 Checklist Before Servicing Use a clutch typ...

Page 34: ...ng R22 and R407C No addition of compressor oil for R410A No additional charge of compressor oil is permitted No use of refrigerant other than R410A Never use a refrigerant other than R410A If refrigerant R410A is exposed to fire Through welding etc toxic gas may be released when R410A refrigerant is exposed to fire Therefore be sure to provide ample ventilation during installation work Caution in ...

Page 35: ...rging cylinder Refrigerant recovery unit Vacuum pump with anti reverse flow 1 Solenoid valve installed type which prevents oil from flowing back into the unit when the power is off is recommended Vacuum pump 2 can be used if the following adapter is attached Vacuum pump adapter reverse flow prevention adapter 3 Solenoid valve installed adapter attached to a conventional vacuum pump Electronic scal...

Page 36: ...alve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly When using a vacuum pump with exhaust air volume more than 25L min and ultimate vacuum pressure rate of 0 05Torr Standa...

Page 37: ...76Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If using a charging cylinder transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder Prepare an evacuated charging cylinder beforehand Do not use the r...

Page 38: ... refrigerant other than R410A Also do not use oxygen or any flammable gas 5 Evacuation Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly When using a vac...

Page 39: ...g 0 76Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If using a charging cylinder transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder Prepare an evacuated charging cylinder beforehand Do not use t...

Page 40: ...ant R410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 10 8 2 Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit do not use its existing tubing Instead completely new tubing must be used CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit ...

Page 41: ...LES APPENDIX Be sure to operate the air conditioning system only when 2 or more indoor units have been installed If operated with only a single unit installed the returning fluid to the compressor may cause a malfunction NOTE ...

Page 42: ... Max Min Max 2 8 2 8 Heating 4 00 4 00 8 0 2 030 9 3 1 6 9 0 800 2 170 Cooling 2 80 2 80 5 6 1 710 8 1 1 1 6 7 540 1 870 2 8 3 6 Heating 4 00 4 80 8 8 2 090 9 4 1 7 9 0 820 2 170 Cooling 2 80 3 60 6 4 1 780 8 4 1 3 7 6 670 1 920 3 6 3 6 Heating 4 80 4 80 9 6 2 130 9 5 1 7 9 8 820 2 170 Cooling 3 60 3 60 7 2 1 840 8 7 1 4 8 1 720 1 940 2 8 5 0 Heating 3 60 6 40 10 0 2 160 9 6 1 7 10 6 820 2 170 Coo...

Page 43: ... 90 3 55 3 55 10 0 2 170 9 7 1 7 10 8 820 2 350 Cooling 2 50 3 25 3 25 9 0 1 940 8 8 1 2 10 5 620 2 380 3 6 3 6 3 6 Heating 3 33 3 33 3 33 10 0 2 170 9 7 1 7 10 8 820 2 350 Cooling 3 00 3 00 3 00 9 0 1 940 8 8 1 2 10 5 620 2 380 2 8 3 6 5 0 Heating 2 50 3 00 4 50 10 0 2 170 9 7 1 7 10 8 820 2 350 Cooling 2 20 2 85 3 95 9 0 1 940 8 8 1 2 10 5 620 2 380 3 6 3 6 5 0 Heating 2 85 2 85 4 30 10 0 2 170 ...

Page 44: ... 9 0 1 940 8 8 1 2 10 5 620 2 380 2 8 3 6 Heating 2 20 2 60 2 60 2 60 10 0 2 170 9 7 3 6 3 6 1 7 10 8 820 2 350 Cooling 1 80 2 40 2 40 2 40 9 0 1 940 8 8 1 2 10 5 620 2 380 2 8 2 8 Heating 2 00 2 00 2 40 3 60 10 0 2 170 9 7 3 6 5 0 1 7 10 8 820 2 350 Cooling 1 75 1 75 2 30 3 20 9 0 1 940 8 8 1 2 10 5 620 2 380 3 6 3 6 Heating 2 50 2 50 2 50 2 50 10 0 2 170 9 7 3 6 3 6 1 7 10 8 820 2 350 Cooling 2 ...

Page 45: ...SANYO Electric Co Ltd Osaka Japan SM700543 MAY 2003 Printed in Japan ...

Reviews: