9-3-7. Electric expansion valve

  When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. Labels are 

applied to the valve body and coil, corresponding to the connector colors, to identify them.

*

 If you have manually checked the electric expansion valve, be sure to reapply the outdoor 220 V after you have replaced the 

wiring. (The position of the electric expansion valve will be changed.)

9-3-8. Branch tubing temperature sensor

Check that the sensor is securely contained in the thermostat holder.

9-3-9. Breaker

Check whether or not the breaker has been tripped.

  Check that the breakers and fuses used are of the specified capacity.

  Check that the breaker and its line are exclusive for A/C use. 

9-3-10. Refrigerant gas pressure

Start a COOL test run, and measure the temperatures of the A/C intake air and discharge air. Compare the values with the 
performance charts.

  If the values are higher than the performance charts: 

Check for refrigerant shortage or blockage of the refrigerant circuit.

 

Assessment of refrigerant shortage:

a

  The low-pressure pressure value is 5 MPa or more below the value in the performance charts.

b

  There is little condensation on the indoor heat exchanger, which overall appears dry.

 

Distinguishing between refrigerant shortage and refrigerant circuit blockage:

 

If the low-pressure pressure does not change when the circuit is charged 2–3 times with refrigerant gas (200 g each time), 
or if the change is small, then the problem may not be refrigerant shortage. The problem may be a blockage of the 
refrigerant circuit.

  Check that the electric expansion valve is not blocked. Check as described on the preceding page.

NOTE:

  Cool the main unit with 

a damp cloth or other 
means while welding.

  When applying 

vacuum, use the 
special service magnet 
and rotate at least 5 
revolutions 
counterclockwise to 
fully open the electric 
expansion valve.

Use a tester to measure the voltage (12 V).

  When the power is turned ON, the needle will move from 

MMV (white) 

 MVA (black) 

 MVB (red) 

 MVC (blue) 

 

MVD (yellow)  in sequence in approximately 10 – 20 seconds 
for each point.

Controller check

No voltage on circuit board

Voltage varies

No temperature change

Temperature changes

0

Approx. 46 

±

 4

Check the coil resistance.

Replace the coil.

Replace the electric 

expansion valve.

This part is normal. 

Check elsewhere.

Check the illumination 

of the red LED.

Check the resistance between the 

gray lead wire and the other wires.

Resistance is OK if it is 46 

±

 4

 at 20

°

C.

Use the special service magnet 
and rotate 5 revolutions 
clockwise to fully close the valve. 
Then start the unit and measure 
the temperatures at the inlet and 
outlet tubes of the electric 
expansion valve. If the 
temperature difference is large, 
the valve is closed. 
Then rotate 5 revolutions 
counterclockwise to open the 
valve. Operation is normal if the 
temperature difference between 
the 2 tubes drops.

Replace the controller.

Open and close the 

electric expansion valve 

by hand to check it.

*

Summary of Contents for SAP-CMRV3143GJ

Page 1: ...ervicing the unit 4 room multi Outdoor unit Combined Indoor Units 1 How these units may be combined is given in the Unit Combination Tables in the Appendix 2 Be sure to operate the air conditioning system only when 2 or more indoor units have been installed If operated with only a single unit installed the returning fluid to the compressor may cause a malfunction NOTE Concealed duct type SAP DMRV9...

Page 2: ...ing Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal fra...

Page 3: ...8 FUNCTIONS 8 1 Current Control 15 8 2 Low Start Current 15 8 3 Compressor Temperature Control 15 8 4 Outdoor Fan Control 15 9 TROUBLESHOOTING 9 1 Outdoor Unit Trouble Diagnostics 17 9 2 Checking the Outdoor System 18 9 3 Unit Problems and Inspection Points 19 9 4 Explanation of Functions 22 10 REFRIGERANT R410A SPECIAL PRECAUTIONS WHEN SERVICING UNIT 10 1 Characteristics of New Refrigerant R410A ...

Page 4: ...1 1 OPERATING RANGE Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Maximum 32 C DB 23 C W B 43 C D B Minimum 19 C DB 14 C W B 19 C D B ...

Page 5: ...nt Amount charged at shipment g R410A 4 000 Refrigerant control Electric Expansion Valve Operation sound Hi dB A 53 53 Refrigerant tubing connections Flare type Max allowable tubing length per unit m 30 Refrigerant Narrow tube mm in 6 35 1 4 4 tube diameter Wide tube mm in 9 52 3 8 3 mm in 12 7 1 2 1 Dimensions Weight Unit dimensions Height mm 880 Width mm 940 Depth mm 340 Package dimensions Heigh...

Page 6: ...t off control YES Compressor discharge temp control YES Operation cut off control in abnormal ambient temp Run capacitor µF VAC Crankcase heater Fan Fan Motor Type Propeller Q ty Dia mm 1 ø460 Fan motor model Q ty KFC6S 61C3PA C 1 No of poles rpm 220V High 6 712 Nominal output W 60 Coil resistance Ambient temp 20 C Ω BRN WHT 66 53 WHT YEL 33 95 YEL PNK 12 50 Safety devices Type Thermal protector O...

Page 7: ...3143GJ 0 0 10 20 30 40 50 60 70 80 90 40 60 80 100 120 140 160 180 200 20 Temperature C Compressor temp sensor Outdoor air temp sensor Narrow tube sensor Wide tube sensor 40 35 30 25 20 15 10 5 0 20 15 10 5 0 5 10 15 20 Temperature C Resistance Ω Resistance Ω ...

Page 8: ... 18 880 940 33 7 Wide tube service valve ø9 52 3 8 Wide tube service valve ø12 7 1 2 Narrow tube service valve ø6 35 1 4 336 256 416 176 25 13 380 AIR DISCHARGE 25 13 465 Unit mm 25 25 10 405 13 13 660 109 Drain hole AIR INTAKE 296 340 AIR INTAKE 15 ...

Page 9: ...ator Insulation of Refrigerant Tubing Because capillary tubing is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a proper insulation material The thickness of the insulation should be a min 8 mm After a tube has been insulated never try to bend it ...

Page 10: ...door air temp 30 C 27 C 24 C Indoor air temp 30 C 27 C 24 C Lo fan Hi fan Lo fan Hi fan Lo fan Hi fan Cooling Characteristics 1 Low pressure performance chart RH 46 Indoor fan speed High fan 2 Operating current performance chart RH 46 Indoor fan speed High fan 50 60Hz 220V 50 60Hz 220V 3 Indoor discharge air performance chart RH 46 Indoor fan speed High fan 50 60Hz 220V Operating current A Low pre...

Page 11: ...n Lo fan Hi fan Cooling Characteristics 1 Low pressure performance chart RH 46 Indoor fan speed High fan 2 Operating current performance chart RH 46 Indoor fan speed High fan 50 60Hz 220V 3 Indoor discharge air performance chart RH 46 Indoor fan speed High fan 50 60Hz 220V Low pressure MPa Indoor discharge air temperature C Outdoor air temperature C Outdoor air temperature C 25 30 35 40 11 10 9 8 ...

Page 12: ... ORG BLU 6 WHT BLK BRN WHT RE1 RE2 RE1 RE2 D TR BD 6 ORG RED 4 FMO 3 2 1 YEL BLU WHT BRN GRY GRN YEL BLK 1 3 1 5 7 3 1 2 3 4 5 1 2 3 4 1 2 GRY WHT 3 1 5 AC200 L1 G1 G2 DC280 DC280 1 2 3 4 5 5 4 3 2 SOLDERED TERMINAL TERMINAL TERMINAL BASE CONNECTOR THERMISTOR ROOM A WIDE PIPE THERMISTOR ROOM A NARROW PIPE THERMISTOR COMPRESSOR TEMP THERMISTOR OUTDOOR TEMP THERMISTOR HEAT EXCHANGER BOARD IN WIRE HE...

Page 13: ...3 H4 above or below the outdoor unit and within a total tubing length L1 L2 L3 L4 from the outdoor unit as detailed in Table 1 and Fig 1 INDOOR UNIT 1 INDOOR UNIT 4 INDOOR UNIT 3 INDOOR UNIT 2 Tubing length L1 L2 L3 L4 Elevation difference H1 H2 H3 H4 OUTDOOR UNIT Fig 1 WARNING To prevent abnormal heat generation and the possibility of fire do not place obstacles enclosures and grilles in front of...

Page 14: ... unit Union φ12 7 Flare φ9 52 φ12 7 D φ12 7 φ9 52 Optional parts STK 43TCA 93 123 types 93 123 types 93 123 types 183 type More than 17 m 2 Connecting indoor unit type 183 at D Length of tube more than 17 m φ6 35 φ6 35 φ6 35 φ6 35 φ9 52 φ9 52 φ9 52 φ9 52 φ9 52 A φ9 52 B φ9 52 C Outdoor unit Indoor unit Union φ9 52 Flare φ12 7 φ12 7 D φ12 7 φ9 52 Supplied Reducer 93 123 types 93 123 types 93 123 ty...

Page 15: ...and that will not magnify operating noise or vibration Fasten in place with the anchor bolts M10 provide a base using concrete or similar material and ensure proper drainage select a location where there is no danger of flammable gas leakage in snowy or rainy regions be sure to construct a roof to keep off the snow and rain and inhibit freezing and condensation select a location that is at least 3...

Page 16: ...to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed A B C D Tubing panel Base not provided concrete or similar material Ensure 150 mm of space if a drain hose is to be used Fasten with anchor bolts not provided 3 8 or M10 4 locations Inspection panel ...

Page 17: ...nit B Unit A Unit C Unit D Unit B Unit C Unit D A Terminal plate 16P Grounding line Power supply Single phase AC 220V 240V B Terminal plate 3P CAUTION Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram The indoor unit draws its power from the outdoor unit 7 5 Wiring System Diagram WARNING Be sure to comply with local codes on running the wire from the indoo...

Page 18: ...ues shown in the table below 8 1 2 Current control The operating frequency upper limits shown in the figure below are established for frequency reduction and increase prohibit Example of operation for cooling Example of operation during cooling Operates at the target frequency at Point A and below Stops increases to the frequency between Points A and B Reduces the frequency by 1 Hz per 0 5 seconds...

Page 19: ... any electrified parts before the control circuit board LED red turns OFF If the outdoor control circuit board is normal approximately 60 seconds will be required for the charge to dissipate However allow at least 30 minutes for the charge to dissipate if it is thought there might be trouble with the outdoor control circuit board If the outdoor control circuit board fuse has blown approximately 30...

Page 20: ...bing D sensor narrow tubing Outdoor air temperature sensor Branch tubing A sensor wide tubing Branch tubing B sensor wide tubing Branch tubing C sensor wide tubing Branch tubing D sensor wide tubing CT current sensor HIC protective device current temperature OTP data failure Current peak exceeded Current control failure Active failure Compressor discharge temperature high Zero cross failure DC com...

Page 21: ...cuit the T RUN terminal to the COM terminal NOTE If the above check items are okay but the outdoor unit does not operate there may be a faulty connection between the indoor unit and the outdoor unit Control No 1 2 The LED red on the control circuit board must illuminate The compressor and fan motor must turn ON They turn ON a few seconds after the power is turned ON Check items unit operation ...

Page 22: ...9 HIC Electrolytic capacitor Compressor Compressor protective thermistor Outdoor fan motor Coil thermistor Electric expansion valve Branch tubing temperature sensor Breaker Refrigerant gas pressure Measure during a test run Operation lamp flashes Indoor fan does not turn Operation lamp does not illuminate The compressor only does not operate The compressor stops on occasion The compressor speed do...

Page 23: ...ctive sensor compressor discharge temperature thermistor Check that the sensor is securely contained in the thermostat holder 9 3 6 Outdoor fan motor Turn the fan slowly by hand If the fan rotates easily a Replace the running capacitor on the outdoor control circuit board b Check for an open circuit in the fan motor coil winding c Use the tester AC range to check whether voltage is reaching the co...

Page 24: ...e circuit is charged 2 3 times with refrigerant gas 200 g each time or if the change is small then the problem may not be refrigerant shortage The problem may be a blockage of the refrigerant circuit Check that the electric expansion valve is not blocked Check as described on the preceding page NOTE Cool the main unit with a damp cloth or other means while welding When applying vacuum use the spec...

Page 25: ... f o g n i n o i t i s o P d e p p o t s d e m r o f r e p s i e v l a v n o i s n a p x e operation F F O N O e h T button on the remote controller is pressed n e e b s a h e d o m n o i t a r e p o c i t a m o t u a f I n o i t a r e p o r e l l o r t n o c e t o m e r e h t h t i w d e t c e l e s begins in SENSOR DRY or COOL mode depending on the temperature at the time operation starts c i t ...

Page 26: ... h t s e t u n i m 3 r e t f A y l l a c i t a m o t u a g n i t a r e p o s i e c n a l a b e r u s s e r p a s e t u n i m 3 e s e h t g n i r u D t r a t s o t r o s s e r p m o c e h t g n i w o l l a d e v e i h c a y l i s a e e r o m n o i t n e v e r p e z e e r F t a e h r o o d n i e h t f o e r u t a r e p m e t e h t n e h W C 2 y l e t a m i x o r p p a o t s p o r d r e g n a h c x e...

Page 27: ...i a m n o i t a r e p o A Y R D n e e w t e b s e g n a h c n a f r o o d n i e h T Low and LL very low over a 6 minute n o i t a r e p o n a f n o i t a u t c u l f f 1 s i s i h T e l c y c g 1 below i F o t r e f e R r i a e h t y f i d i m u h e d y l e v i t c e f f e o t s e t a r e p O r o o d n i e h t g n i c u d e r y l e v i s s e c x e t o n e l i h w e r u t a r e p m e t n o i t a u ...

Page 28: ...its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on whether it is in gaseous or liquid phase and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state Thus always charge the refrigerant while it is in liquid phase 10 2 Checklist Before Servicing Use a clutch typ...

Page 29: ...ng R22 and R407C No addition of compressor oil for R410A No additional charge of compressor oil is permitted No use of refrigerant other than R410A Never use a refrigerant other than R410A If refrigerant R410A is exposed to fire Through welding etc toxic gas may be released when R410A refrigerant is exposed to fire Therefore be sure to provide ample ventilation during installation work Caution in ...

Page 30: ...rging cylinder Refrigerant recovery unit Vacuum pump with anti reverse flow 1 Solenoid valve installed type which prevents oil from flowing back into the unit when the power is off is recommended Vacuum pump 2 can be used if the following adapter is attached Vacuum pump adapter reverse flow prevention adapter 3 Solenoid valve installed adapter attached to a conventional vacuum pump Electronic scal...

Page 31: ...alve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly When using a vacuum pump with exhaust air volume more than 25L min and ultimate vacuum pressure rate of 0 05Torr Standa...

Page 32: ...76Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If using a charging cylinder transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder Prepare an evacuated charging cylinder beforehand Do not use the r...

Page 33: ... refrigerant other than R410A Also do not use oxygen or any flammable gas 5 Evacuation Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be damaged if moisture remains in the tubing thus carry out the evacuation thoroughly When using a vac...

Page 34: ...g 0 76Kg using a capacity of a 10Kg cylinder the minimum necessary amount for the cylinder is 0 76 10 0 20 2 76Kg For the remaining refrigerant refer to the instructions of the refrigerant manufacturer If using a charging cylinder transfer the specified amount of liquid refrigerant from the refrigerant cylinder to the charging cylinder Prepare an evacuated charging cylinder beforehand Do not use t...

Page 35: ...ant R410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 10 8 2 Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit do not use its existing tubing Instead completely new tubing must be used CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit ...

Page 36: ...LES APPENDIX Be sure to operate the air conditioning system only when 2 or more indoor units have been installed If operated with only a single unit installed the returning fluid to the compressor may cause a malfunction NOTE ...

Page 37: ...C Room D Total Performance Power Input W Current A Min Max Min Max 2 8 2 8 Cooling 2 80 2 80 5 6 1 710 8 1 1 1 6 7 540 1 870 2 8 3 6 Cooling 2 80 3 60 6 4 1 780 8 4 1 3 7 6 670 1 920 3 6 3 6 Cooling 3 60 3 60 7 2 1 840 8 7 1 4 8 1 720 1 940 2 8 5 0 Cooling 2 80 5 00 7 8 1 880 8 8 1 4 8 1 720 1 940 3 6 5 0 Cooling 3 60 5 00 8 6 1 920 9 0 1 4 10 5 720 2 380 2 8 7 0 Cooling 2 55 6 45 9 0 1 940 8 8 1 ...

Page 38: ...tion Room A Room B Room C Room D Total Performance Power Input W Current A Min Max Min Max 2 8 2 8 Cooling 2 25 2 25 2 25 2 25 9 0 1 940 8 8 2 8 2 8 1 2 10 5 620 2 380 2 8 2 8 Cooling 2 10 2 10 2 10 2 70 9 0 1 940 8 8 2 8 3 6 1 2 10 5 620 2 380 2 8 2 8 Cooling 2 00 2 00 2 50 2 50 9 0 1 940 8 8 3 6 3 6 1 2 10 5 620 2 380 2 8 2 8 Cooling 1 90 1 90 1 90 3 30 9 0 1 940 8 8 2 8 5 0 1 2 10 5 620 2 380 2...

Page 39: ...SANYO Electric Co Ltd Osaka Japan SM700544 MAY 2003 Printed in Japan ...

Reviews: