17
■
2 - indoor units in operation A + B
Indoor Unit
SAP – K91GJA (
✕
2)
Outdoor Unit
SAP – CM1821JA
220 V Single phase 60 Hz
g
RATING CAPACITY
5.20 kW
EVAPORATOR
CONDENSER
ENT. TEMP. °C
OUTDOOR AMBIENT TEMP. °C
W.B.
D.B.
20
25
30
35
40
43
TC
5.24
5.01
4.78
4.56
4.28
3.94
CM
1.26
1.37
1.46
1.57
1.71
1.86
21
SHC
3.53
3.41
3.29
3.18
3.04
2.87
15
23
SHC
3.95
3.83
3.71
3.59
3.46
3.29
25
SHC
4.36
4.25
4.13
4.01
3.88
3.71
27
SHC
4.78
4.67
4.55
4.43
4.28
3.94
29
SHC
5.20
5.01
4.78
4.56
4.28
3.94
31
SHC
5.24
5.01
4.78
4.56
4.28
3.94
TC
5.62
5.38
5.13
4.89
4.59
4.23
CM
1.30
1.40
1.50
1.61
1.76
1.90
21
SHC
3.10
2.98
2.86
2.74
2.61
2.44
17
23
SHC
3.52
3.40
3.28
3.16
3.03
2.86
25
SHC
3.94
3.82
3.70
3.58
3.45
3.28
27
SHC
4.36
4.24
4.12
4.00
3.87
3.70
29
SHC
4.78
4.66
4.54
4.42
4.29
4.12
31
SHC
5.19
5.07
4.96
4.84
4.59
4.23
TC
5.98
5.72
5.46
# 5.20
4.89
4.50
CM
1.34
1.45
1.55
1.66
1.81
1.96
21
SHC
2.64
2.52
2.41
2.29
2.16
2.00
19
23
SHC
3.06
2.94
2.83
2.71
2.58
2.42
25
SHC
3.48
3.36
3.25
3.13
3.00
2.83
27
SHC
3.90
3.78
3.67
3.55
3.42
3.25
29
SHC
4.32
4.20
4.09
3.97
3.84
3.67
31
SHC
4.74
4.62
4.51
4.39
4.26
4.09
TC
6.34
6.06
5.79
5.51
5.18
4.77
CM
1.38
1.49
1.59
1.71
1.86
2.01
23
SHC
2.60
2.49
2.37
2.26
2.13
1.96
21
25
SHC
3.02
2.90
2.79
2.68
2.55
2.38
27
SHC
3.44
3.32
3.21
3.10
2.96
2.80
29
SHC
3.86
3.74
3.63
3.52
3.38
3.22
31
SHC
4.28
4.16
4.05
3.94
3.80
3.64
TC
6.73
6.44
6.13
5.79
5.42
5.04
CM
1.40
1.53
1.64
1.76
1.91
2.07
23
25
SHC
2.53
2.42
2.30
2.18
2.04
1.90
27
SHC
2.95
2.84
2.72
2.59
2.46
2.32
29
SHC
3.37
3.26
3.14
3.01
2.88
2.74
31
SHC
3.79
3.68
3.56
3.43
3.30
3.16
TC :
Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM :
Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
NOTE
A : SAP–K91GJA
B : SAP–K91GJA