background image

General Installation Manual 
 

PV-modules are defined as follows: 
Class  A:  General  access,  hazardous 
voltage, hazardous power applications 
Module  rated  for  use  in  this  application 
class may be used in systems operating at 
greater  than  50  V  DC  or  240  W,  where 
general  contact  access  is  anticipated. 
Modules  qualified  for  safety  through  this 
part of IEC 61730-1 and IEC 61730-2 and 
within 

this 

application 

class 

are 

considered  to  meet  the  requirements  for 
safety class II. 
 
Fire class of product 
Sanyo HIT PV modules fill the fire class C 
that provides to ANSI/UL790. Class C roof 
coverings  are  effective  against  light  fire 
test  exposures.  Under  such  exposures, 
roof  coverings  of  this  class  afford  a  light 
degree  of  fire  protection  to  the  roof  deck, 
do  not  slip  from  position,  and  are  not 
expected to produce flying brands. 
 
Mechanical Loading 

• 

The  modules  should  be  mounted  at 
the  four  (4)  quarter  points  by  the 
means shown in Figures 3-1, 3-2, 3-3.   

• 

This  method  offers  a  maximum  load 
of  2400N/m2  (50PSF,  in  a  static 
state) on the module surface. 

 
CERTIFICATION 
The  HIP-xxxHDE1,  xxxHDE1-2  Modules 
comply 

with 

the 

requirements 

of 

IEC61730-1,      IEC61730-2  and  the  CE 
mark. 
 
WIRING 
General 

• 

All 

wiring 

should 

be  done 

in 

accordance  with  applicable  electrical 
codes.    

• 

All  wiring  should  be  done  by  a 
qualified, licensed professional. 

• 

Wiring  should  be  protected  to  help 
ensure personal safety and to prevent 
its damage.  

• 

All  modules  connected  in  series 
should be of the same model number 
and/or type.  

• 

Do  not  connect  modules  in  parallel 
without using a connection box. 

• 

Do not disconnect terminals while PV 
modules  generate  electricity  and 
connect  electrical  load  to  avoid  the 
hazard of electrical shock. 

• 

To  avoid  the hazard  of  electric  shock 
and  sparks,  please  connect  each 
cable  after  confirming  the  polarity  of 
them is correct.  

 
Module Wiring 

• 

The  maximum  number  of  modules 
that  can  be  wired  in  series  is  twenty-
one (21). 

• 

Modules shall not be wired in parallel 
without 

maximum 

over 

current 

protection. 

• 

SANYO  solar  modules  are  not 
designed  for  “off-grid”  or  battery 
charging  systems,  because  of  their 
operating  voltage.  Therefore,  it  is  not 
recommended  to  use  them  to  charge 
batteries. 

• 

These 

modules 

contain 

factory 

installed  bypass  diodes.  If  these 
modules  are  incorrectly  connected  to 
each other, the bypass diodes, cable, 
or junction box may be damaged. 

 
Array Wiring 

• 

The  term  “array”  is  used  to  describe 
the assembly of several modules on a 
support  structure  with  associated 
wiring.  

• 

Use  copper  wire  that  is  sunlight 
resistant and is insulated to withstand 
the  maximum  possible  system  open 
circuit voltage.   

• 

Check 

your 

local 

codes 

for 

requirements. 

 
Earth Ground Wiring 

• 

The  kind  of  the  earth  construction 
shall conform to IEC61730-1.  

• 

Bonding shall be by a positive means, 
such  as  clamping,  riveting,  bolted  or 
screwed  connections,  or  welding, 
soldering  or  brazing.  The  bonding 
connections  shall  penetrate  all  non-
conductive  coatings,  such  as  paint, 
anodized coatings or vitreous enamel. 

• 

A  wiring  terminal  or  bonding  location 
of  module  intended  to  accommodate 
a  field  installed  equipment-grounding 
conductor  shall  be  identified  with  the 
appropriate  symbol  (IEC  60417-
5019(DB:2002-10))  or  shall  have  a 
green-colored part. 

• 

Grounding  should  be  carried  out  by 
the attachment to the module or array 
frame, to avoid the hazards of electric 
shock or fire. 

 
Module Terminations 

• 

A  junction  box  as  a  terminal 
enclosure  is  equipped  for  electrical 
connections on SANYO modules.   

• 

Modules  are  equipped  with  MC

TM

 

plugs  as  a  terminal  enclosure.  Use 
these  MC

TM

  plugs  for  electrical 

connections.   

• 

If  two  or  more  separable  connectors 
are provided, they shall be configured 
or  arranged  so  that  the  other  and 
vice-versa  will  not  accept  the  mating 
connector for one, if it will result in an 
improper connection. 

• 

Please 

contact 

your 

SANYO 

Authorized 

Representative 

with 

questions  regarding  other  electrical 
connections if needed.  

 
Junction Box and Terminals 

• 

Modules  equipped  with  one  junction 
box contain terminals for both positive 

and  negative  polarity,  and  bypass 
diodes. 

• 

One  terminal  is  dedicated  to  each 
polarity  (with  the  polarity  symbols 
engraved  onto  the  body  of  the 
junction box) (see Figure 2). 

 
Conduit 

• 

For  applications  where  wire  conduits 
are  used,  follow  the  applicable  codes 
for  outdoor  installation  of  wires  in 
conduits.  Minimum  diameter  of  wire 
conduit is 4.0 mm

2

• 

Verify  that  all  fittings  are  properly 
installed  to  protect  wires  against 
damage 

and 

prevent 

moisture 

intrusion.  

 
DIODES 
Bypass Diodes 

• 

When  the  modules  in  series  strings 
are  shaded  partially,  it  may  cause 
reverse  voltage  across  cells  or 
modules,  because  the  current  from 
other  cells  in  the  same  series  is 
forced  to  flow  through  the  shaded 
area.    This  may  cause  undesirable 
heating to occur.  

• 

The  use  of  a  diode  to  bypass  the 
shaded  area  can  minimize  both 
heating and array current reduction. 

• 

All  SANYO  modules  are  equipped 
with  factory  installed  bypass  diodes. 
The  factory  installed  diodes  provide 
proper  circuit  protection  for  the 
systems  within  the  specified  system 
voltage,  so  that  you  do  not  need  any 
other additional bypass diodes.  

• 

Contact  your  SANYO  Authorized 
Representative for proper diode type, 
if  it  is  necessary  to  add  or  change 
diodes due to system specifications. 

 
MAINTENANCE 

• 

Some  maintenance  is  recommended 
to 

maintain 

optimal 

output 

performance of the solar modules.  

• 

If  the  module  surface  becomes  dirty, 
it may reduce output power.  

• 

It  is  recommended  to  clean  the 
surface of the module with water and 
a soft cloth or sponge.  

• 

A  mild  non-abrasive  detergent  may 
be applied for persistent dirt.   

• 

It is also recommended to inspect the 
electrical and mechanical connections 
annually. 

• 

If  you  need  electrical  or  mechanical 
inspection

 

or

 

maintenance, 

 

it

 

is 

recommended  to  have  a  licensed 
authorized  professional  carry  out  the 
inspection  or  maintenance  to  avoid 
the hazards of electric shock or injury. 

• 

The return of any modules will not be 
accepted  by  SANYO  unless  prior 
written  authorization  has  been  given 
by SANYO. 

Summary of Contents for HIP-225HDE1

Page 1: ...odule Do not puncture or damage the back sheet of a module to avoid the hazard of electric shock and fire To avoid the hazard of electric shock and injury children and unauthorized persons should not be allowed near the installation of PV modules To avoid the hazard of electric shock and injury be sure to completely ground all modules To avoid the hazard of electric shock fire and injury do not di...

Page 2: ...modules are as follows 1 The modules should be operated only in terrestrial applications No space or other Special Conditions see below 2 The ambient temperature should be within 20 C 4 F to 40 C 104 F 3 The relative humidity should be within 45 to 95 4 The installation place should be less than 1 000m 3 280ft above sea level Installations more than 1 000m 3 280ft are allowed only if the wind pres...

Page 3: ... all non conductive coatings such as paint anodized coatings or vitreous enamel A wiring terminal or bonding location of module intended to accommodate a field installed equipment grounding conductor shall be identified with the appropriate symbol IEC 60417 5019 DB 2002 10 or shall have a green colored part Grounding should be carried out by the attachment to the module or array frame to avoid the...

Page 4: ...uous improvement SANYO reserves the right to change product specifications at any time without prior notice For further information please visit www sanyo com or contact a SANYO Authorized Representative 2007 Dec SANYO Electric Co Ltd All Rights Reserved 12 28 07 ...

Page 5: ...rrent Isc 7 14 7 07 6 99 Cell Type HIT HIT HIT Maximum System Voltage 1000 1000 1000 Maximum Over current protection rating A 15 15 15 Factory Installed Bypass Diodes 3 3 3 Mechanical Specifications Length mm 1610 Width mm 861 Thickness mm 35 Weight kg 16 5 1 0 0 0 V P V U B 5 0 2 I P 6 5 Figure2 Configuration of junction box negative positive Cable Connector MC Plug Figure3 1 Dimensions Dimension...

Page 6: ...nual 6 Dimension in mm Optional Mounting Range Dimension in mm Optional Mounting Range Note Fixing span is 1050mm or less Note Fixing span is 1050mm or less Figure3 2 Optional Mounting Range Figure3 3 Optional Mounting Range ...

Reviews: