41
8. FUNCTION
8-1. Room Temperature Control
●
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room
temperature sensor in the remote control unit.
●
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to
the controller in the indoor unit.
●
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at
least 3 minutes. To protect the compressor from stalling out when trying to start against the high side
refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to
equalize.
●
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of com-
pressor operation.
●
Thermo ON : When the room temperature is above T + 2°F (T°F is set temperature).
Compressor
→
ON
●
Thermo OFF : When the room temperature is equal to or below set temperature T°F.
Compressor
→
OFF
Set temp.
T+2
°
F
Signal from remote control unit
Room temp.
More than
5 minutes
Thermo
OFF
Indoor fan
Outdoor fan
Compressor
Set speed
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
3 minutes
5 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
3 minutes
Thermo
ON
Thermo
OFF
Thermo
ON
Thermo
ON
Thermo
ON
Thermo
OFF
T
°
F
000-215 SM (1-56) 7/5/00 2:49 PM Page 41
Summary of Contents for C0951
Page 36: ...33 7 Printed circuit board POW KS095A POW KS095B for KS0951 ...
Page 37: ...34 8 Printed circuit board POW KS125A POW KS095B for KS1251 ...
Page 38: ...35 9 Printed circuit board POW KS1852 for KS1852 ...
Page 39: ...36 10 Printed circuit board POW CL125 for CL0951 CL1251 and CL1852 ...
Page 58: ...55 INSTRUCTION MANUAL KS0951 C0951 CL0951 KS1251 C1251 CL1251 KS1852 C1852 CL1852 APPENDIX ...