4. Service procedures
1
2
3
4
5
IV - 51
SM830080
(11) Items to Check Prior to Test Run
(1) Turn on the power supply switch more than 5 hours before in order to charge the crank
case heater.
(2) Fully open the outdoor service valve after making the leak inspection of field connected
tubing, vacuuming, and gas charging if necessary.
(3) Check the capacity code and model code setting.
* The factory setting is as shown in the table. Double check it.
* The capacity code is set by S4 (green, 4P DIP switch) on outdoor control PCB.
The model code is set by S5 (black, 2P DIP switch) on outdoor control PCB.
1
ON
ON side
1577_C_I
OFF side
S4 (green or Blue) capacity code
(4P DIP switch)
2
3
4
1
ON
ON side
OFF side
S5 (black) model code
(2P DIP switch)
2
S5. Model code
• R407 Models: SPW-CR type
No.
Outdoor PCB
Model No.
1
2
3
4
25 type (1 phase)
ON
ON
ON
OFF
25 type (3 phase)
ON
ON
ON
OFF
36 type (3 phase) OFF
ON
OFF
ON
48 type (3 phase) OFF OFF
ON
ON
No.
Outdoor PCB
Model No.
1
2
SPW-CR253GHL5 OFF
ON
SPW-CR253GHL8 OFF
OFF
SPW-CR363GHL8 OFF
OFF
SPW-CR483GHL8 OFF
OFF
S4. Capacity code
No.
Outdoor PCB
Model No.
1
2
SPW-CR253GL5
ON
ON
SPW-CR253GL8
ON
OFF
SPW-CR363GL8
ON
OFF
SPW-CR483GL8
ON
OFF
S5. Model code