2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
2
Applicable indoor unit ... Number SAP – KR128E ... 2
Power Source
220 / 230 / 240 V Single phase 50 Hz
Cooling
Max.Capacity kW 6.70
(230V)
BTU/h 22900
No. of indoor unit
1 – Unit
2 – Units
Capacity kW 3.55 6.70
BTU/h 12100 22900
Available voltage range
V
198 to 264
Running amperes A 6.2 12.5
Power input W 1,320 2,650
Power factor % 94 93
C.O.P. W/W 2.5 2.7
Compressor locked rotor amperes A 33 66
Fan speeds
Auto (Hi, Lo)
Compressor
Rotary (Hermetic)
Refrigerant / Amount charged at shipment g R407c / 2060 (1030 x 2)
Refrigerant control
Capillary tube
Operation sound
dB-A
53.0
Refrigerant tubing connections
Flare type
Max. allowable tubing length at shipment
m
7.5
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1/4)
diameter
Wide tube
mm (in.)
12.7 (1/2)
Refrigerant tube kit
Optional
Unit dimensions
Package dimensions
Height
mm
835
913
Width
mm
850
1,000
Depth
mm
305
400
Net weight
kg
67.5
Shipping weight
kg
76.5
Shipping volume
m
3
0.365
Electrical Rating
Features
Dimensions & Weight
Outdoor Unit SAP – CMR2428E
Performance