User Settings
Guide
No.
Ref. page Item
Menu
Menu LED
Setting
Setting
LED
Default
Setting
Current
Setting
Remarks
Auto
●○○○
*
Switch the UPS operating mode automatically.
Double
Conversion
○●○○
Set the UPS operating mode to Double Conversion mode.
1 4 3.1
UPS operation mode
○
● ○ ○ ○
Economy
●●○○
Set the UPS operating mode to Economy mode
200V
●○○○
Default setting of E11A*U-J
220V
○●○○
230V
●●○○
240V
○○●○
2
5
3.2
Output voltage
(RESTART)
○
○ ● ○ ○
208V
●○●○
See
remarks
Default setting of E11A*U
Set the rated Output voltage.
Same as Input voltage.
Default setting varies
depending on UPS Model.
1%
●○○○
±
1%
3%
○●○○
*
±
3%
3
6
3.3
Frequency sync
range (RESTART)
○
● ● ○ ○
5%
●●○○
±
5%
Output frequency variation range
(%)
50Hz
●○○○
Default setting of
E11A*U-J
4
7
3.4
Battery power
startup frequency
(RESTART)
○
○ ○ ● ○
60Hz
○●○○
See
remarks
Default setting of
E11A*U
Set the output frequency when UPS
starts from the battery power during
AC input power failure. Default setting
varies depending on UPS Model.
Standalone
●○○○
Set when using UPS remote ON/OFF or Standard OS UPS
Services
Workstation
○●○○
*
Set when using a power management software, LAN card or
UPS remote ON and One-touch system shutdown.
Serial Login
●●○○
Shutdown by serial login.
5
8
3.5
PC interface
○
● ○ ● ○
-
○○●○
Do not use this setting.
9600
●○○○
*
9600 bps.
4800
○●○○
4800 bps.
6
9
3.6
Serial baud rate
○
○ ● ● ○
2400
●●○○
2400 bps.
Set the serial baud rate when a
workstation, PC, or optional LAN
card is connected.
Auto
●○○○
*
Auto restart
OFF
○●○○
The UPS stays off.
30%
●●○○
Auto restart when battery
charge reaches 30%.
50%
○○●○
Auto restart when battery
charge reaches 50%.
7
10
3.7
UPS operation upon
power recovery
○
● ● ● ○
80%
●○●○
Auto restart when battery
charge reaches 80%.
Specify when to restart the UPS
after a power outage and
shutdown of the UPS due to final
discharge of the batteries.
All patterns
●○○○
*
All sounds
Pattern 1
○●○○
Emit sounds on serious failure and battery trouble.
Pattern 2
●●○○
Emit alarm and key click sounds.
8
11
3.8
Buzzer sound
○
○ ○ ○ ●
OFF
○○●○
Emit key click sounds only.
1 second
●○○○
*
Turn the UPS off when
pressed for 1 second.
3 seconds
○●○○
Turn the UPS off when
pressed for 3 second.
9
12
3.9
Shutdown operation
○
● ○ ○ ●
Special
operation
●●○○
Turn the UPS off on special
operation.
Set the operation for switch to
stop the UPS power supply.
Auto return
●○○○
*
Auto recovery when a
certain period of time has
elapsed.
10 13 3.10
Overload recovery
operation
○
○ ● ○ ●
Bypass
○●○○
Fixed as bypass power
supply on overload.
Set the UPS operation after
switching to the bypass power
supply because of overload.
OFF
●○○○
*
The UPS stays off.
11 14 3.11
UPS operation at
OFF
(RESTART)
○
● ● ○ ●
Bypass
○●○○
Bypass power supply
Specify the UPS power supply
conditions when
is off.
Battery
voltage
●○○○
*
When low battery voltage
level is detected.
2 minutes
○●○○
When remaining battery
duration is 2 minutes.
12 15 3.12
Low battery voltage
warning timing
○
○ ○ ● ●
3 minutes
●●○○
When remaining battery
duration is 3 minutes.
Set the timing of emitting the low
battery voltage warning alarm
(beep, Red BATT. LOW lit).
5 minutes
●○○○
*
5 minutes backup
20 minutes
○●○○
20 minutes backup
30 minutes
●●○○
30 minutes backup
40 minutes
○○●○
40 minutes backup
60 minutes
●○●○
60 minutes backup
90 minutes
○●●○
90 minutes backup
120 minutes
●●●○
120 minutes backup
13 16 3.13
Battery backup time
○
● ○ ● ●
180 minutes
○○○●
180 minutes backup
Set the UPS backup time on power
outage. An external battery must
be connected for settings of 20
minutes or higher.
5 years
●○○○
*
5 years lifetime type
10 years
○●○○
10 years lifetime type
14 17 3.14
Battery type
○
○ ● ● ●
3 years
●●○○
3 years lifetime type
Set the battery type. Set this when
you replace the battery or connect
an external battery.
180 days
●○○○
*
Test batteries every 180 days.
90 days
○●○○
Test batteries every 90 days.
30 days
●●○○
Test batteries every 30 days.
15 18 3.15
Battery test schedule
○
● ● ● ●
None
○○●○
No battery check.
Set the interval (number of days)
for the automatic battery check.
The check is carried out
automatically when the specified
number of days has elapsed.
Do not reset
●○○○
*
Do not reset.
16
19
3.16
Reset battery
information
●
○ ○ ○ ○
Reset
○●○○
Reset the battery information when you replace the battery.
●
: indicates that LED is blinking.
○
: indicates that LED is off.