VOC CONTROLLER
Remove the cover.
Connect the 3 wires from the controller to the same color
wiring coming from the unit. Use the wire connectors
included.
The detector is factory set a t 3.0 V DC; If you wish to set up a
higher sensitivity, please proceed as follow.
SETTING (if necessary)
You will need a voltmeter with alligator probes.
Place the probes one on the positive terminal, the other on the neutral terminal.
Use a small screwdriver to turn the adjustment screw to increase the sensitivity of the controller.
The default setting is 3.0 v dc. The more you increase the voltage, the faster the controller will react to
VOC or smoke.
CHECKING IF IT WORKS
1.
Start the unit: inside the polycarbonate box, the GREEN LED flashes. It will take some time, so
the electronic board initializes itself.
2.
After 5 minutes, the GREEN LED will turn solid. Blow some cigarette smoke into the controller. If
the other RED LED lights up, the relay triggers on the oxidizing lamp (all UVV). This sequence
reproduce itself every minute or so. When there is no more smoke (VOC), the RED LED is turned
off at the same time as the lamp.
MAINTENANCE INSTRUCTIONS
•
MONTHLY:
Change the pre-filters that protects the motor (part # MSCFTR2) to ensure the
optimal performance of the unit. Check the lamps: if there is a cloudy residue please clean then
off with denatured alcohol.
•
YEARLY
: Change lamps (parts -see below) to maintain performance: make sure to put the same
lamp in the same clamp. Do not interchange the lamps as the blue end cap lamp works only with
the VOC controller.
o
LMPHGXJ160-8
lamp UVC/UVV
6’’ exposed
(yellow end cap)
o
LMPHXJ160
lamp all UVV (blue end cap)
•
3-5 years
: Change VOC controller board
setting screw:
triggers at
3.4 V DC
Positive
Neutral
Sensor