3.12.
Commissioning
The SINUS PENTA drive for the regenerative application is factory-set as follows:
Drive Class
Rated Voltage
(C500)
Rated Frequency
(C501)
2T
230.0 V
50 Hz
4T
400.0 V
50 Hz
5T
575.0 V
50 Hz
6T
690.0 V
50 Hz
Table 7: Default values of parameters C500 and C501 (AC mains)
When rated voltage/frequency values are different from the default values, the relevant parameters must be
set up
before
activating the drive.
For optimum performance, also adjust parameterization of the drive controlling the motor by setting the
Rated Mains Voltage parameter (
C008
for the Sinus Penta
) to xT Regen, where “x” is the voltage class of the
drive being used.
1) Wiring:
Follow the instructions given in the sections of this manual covering the drive wiring
diagrams.
CAUTION
Wrong wiring can cause the equipment malfunction.
2) Power on:
Power on the drive, by keeping the ENABLE-A and ENABLE-B inputs (terminals 15 and
S) still open, so that the drive is disabled.
Make sure that the drive is set up for the regenerative application: this is shown on the
start page (see below; line 1 states that the regenerative unit is waiting for the Enable
signal) or on the product ID screen in the IDP menu.
R E G E N . W A I T
E N A
M 5 0 5 = +
0 . 1 k W
M 5 0 2 =
4 0 9 . 2 V
[ M E A ] P A R C F I D P
NOTE
When the regenerative drive is powered on, the motor drive powers on as
well. Parameters can be changed for both drives.